Thermo-cooler
Series HRG
How to Order
HRG 010 A
Cooling capacity Option
-A Cooling capacity 9.0/9.5 kW (50/60 Hz) Nil None
010
With casters
-W Cooling capacity 10.0/11.0 kW (50/60 Hz) A
With earth leakage breaker
-A Cooling capacity 13.0/14.5 kW (50/60 Hz) B
015
C With communications function (RS485)
-W Cooling capacity 14.5/16.5 kW (50/60 Hz)
∗ Refer to page 21 for the specifications of each option.
Cooling method
Air-cooled
A
refrigeration
Water-cooled
W
refrigeration
Specifications
HRG010, 015
Model
HRG010 HRG015
Cooling method Air-cooled refrigeration Water-cooled refrigeration Air-cooled refrigeration Water-cooled refrigeration
Refrigerant R407C (HFC)
Control method Compressor ON/OFF control
Note 1)
Ambient temperature/humidity Temperature: –5 to 40°C, Humidity: 30 to 70%RH
Note 2)
Circulating fluid Clear water, Deionized water, 15% ethylene glycol aqueous solution
Note 1)
Temperature range setting (°C) 5 to 35
Note 3)
9.0/9.5 10.0/11.0 13.0/14.5 14.5/16.5
Cooling capacity (50/60 Hz)
(kW) (at 20°C) (at 20°C) (at 20°C) (at 20°C)
Note 4)
Heating capacity (kW) — — — —
Note 5)
Temperature stability (°C) ±1.0
Note 6)
Pump capacity (50/60 Hz) (MPa) 0.29/0.33 (at 37/49 L/min, total lifting height 25/25 m) 0.28/0.31 (at 42/53 L/min, total lifting height 25/25 m)
Note 7)
Rated flow (50/60 Hz)(L/min) 37/49 42/53
Tank capacity (L) 40 60
Port size Rc3/4
Stainless steel, Brass, PVC, Nylon 12, Stainless steel, Brass, PVC, Nylon 12,
Wetted parts material
Polyurethane, Copper brazing (Heat exchanger) Polyurethane, Copper brazing (Heat exchanger)
Temperature range (°C) — 5 to 32 — 5 to 32
Pressure range (MPa)
— 0.3 to 0.5 — 0.3 to 0.5
Note 8)
Required flow rate (50/60 Hz)(L/min)
— 33/34 — 38/40
Port size
— Rc1/2 — Rc3/4
Wetted parts material Stainless steel, Brass, Synthetic rubber, Copper brazing (Heat exchanger)
Power supply 3-phase 200 VAC 50 Hz, 3-phase 200 to 220 VAC 60 Hz Allowable voltage fluctuation ±10%
Note 9)
Applicable earth leakage breaker capacity (A) 40 60
Rated operating current (50/60 Hz) (A) 14/16 12/12.5 21/22 18/19
Rated power consumption (50/60 Hz) (kW) 4.0/5.0 3.2/3.8 5.5/6.7 4.7/5.8
Remote operation signal input Remote startup with 8 mA input at 24 VDC, shutdown at 0 VDC
Operation signal output Relay contact output (switch closed when operating, switch open when stopped, switch open when shut down)
Alarm stop signal output Relay contact output (switch closed when alarm is turned off, switch open when alarm is turned on, switch closed when shut down)
Alarm Refer to page 19.
Note 10)
Weight (kg) 205 200 230 220
Note 1) It should have no condensation.
During seasons or in locations where the ambient temperature is likely to fall below freezing point, please use ethylene glycol aqueous solution.
Note 2) If clear water is used, please use water that conforms to Water Quality Standards of the Japan Refrigeration and Air Conditioning Industrial Association (JRA GL-02-1994
cooling water system - circulating type - make-up water). If deionized water is used, supply water with electrical conductivity of 1 µS/cm or more (or electrical resistivity of 1
MΩ·cm or less).
If ethylene glycol aqueous solution is used, maintain the concentration at 15%.
Note 3) q Ambient temperature: 32°C, Facility water temperature: 25°C (water-cooled refrigeration), w Circulating fluid temperature: 20°C, e Circulating fluid flow rate: Values at
rated circulating fluid flow rate.
Note 4) Thermo-cooler specifications do not have heating capability.
Note 5) Value with a stable load without turbulence in the operating conditions. It may be out of this range depending on operating conditions.
Note 6) The capacity at the Thermo-cooler outlet when the circulating fluid temperature is 20°C.
Note 7) Required flow rate for cooling capacity or maintaining the temperature stability.
When used below the rated flow, open the standard by-pass valve and maintain a circulating fluid flow rate equivalent to the rated flow.
Also, use the individually sold, “By-pass Piping Set” (Refer to pages 22 through to 25).
Note 8) Required flow rate when a load for the cooling capacity is applied at a facility water temperature of 32°C.
Note 9) Purchase an earth leakage breaker with current sensitivity of 30 mA separately. (A product with an optional earth leakage breaker (option B) is also available. Refer to “How to Order”.)
Note 10) Weight in the dry state without circulating fluids
14
Facility water
Electrical system Circulating fluid system
system
Thermo-cooler Series HRG
Cooling Capacity
HRG010-A HRG010-W
12
12
60 [Hz]
60 [Hz]
10
10
50 [Hz]
50 [Hz]
8
8
6
6
4
4
2
2
0
0
0 10 20 30 40 0 10 20 30 40
Circulating fluid temperature (°C) Circulating fluid temperature (°C)
HRG015-A HRG015-W
18
16
60 [Hz]
16
60 [Hz]
14
14
50 [Hz]
12 50 [Hz]
12
10
10
8
8
6
6
4
4
2 2
0 0
0 10 20 30 40 0 10 20 30 40
Circulating fluid temperature (°C) Circulating fluid temperature (°C)
Pump Capacity Facility Water Required Flow Rate
HRG010-A, HRG010-W
50
0.5
50
Outlet [60 Hz]
0.4
40
Outlet [50 Hz]
0.3
30
40
0.2
20
Return port
HRG015-W
10 0.1
30
0 0.0
0 10 20 30 40 50 60 70 80
Lifting height Pressure
[m] [MPa]
Circulating fluid flow rate (L/min)
HRG010-W
HRG015-A, HRG015-W
20
0.5
50
Outlet [60 Hz]
0.4
40
Outlet [50 Hz]
0.3
30
10
0.2
20
Return port
0.1
10
0
0 0.0
0 10 20 30 40
0 10 20 30 40 50 60 70 80
Lifting height Pressure
Facility water inlet temperature (°C)
[m] [MPa]
Circulating fluid flow rate (L/min)
∗ For all common models, temperature stability will decline in the flow rate
∗ This is the required flow rate of facility water at the rated cooling capacity and
range where circulating fluid is deduced (dotted line). Also, in this range, the
circulating fluid flow, operating at 60 Hz, when the facility water inlet tempera-
circulating fluid outlet pressure will exceed the maximum operating pressure
ture is between 5°C and 32°C.
(0.5 MPa) (HRG010 to HRG015).
15
Cooling capacity (kW) Cooling capacity (kW)
Cooling capacity (kW) Cooling capacity (kW)
Facility water required flow rate (L/min)
Related Technical
HED HEB HEC HRW HRZD HRZ HRS HRG
Products Data
Series HRG
Dimensions: Air-Cooled Refrigeration
HRG010-A (-A)
(991)
Refrigerant high
pressure gauge
Ventilation air outlet
Circulating fluid
Eye bolt M12
pressure gauge
Ventilation air inlet
Automatic water
Operation
supply port Rc1/2
display panel
Circulating fluid outlet Rc3/4
Circulating fluid return port Rc3/4
Ventilation
hole
(19)
By-pass valve
(507)
(500) (30)
(440) (85) (918) (37)
(4 x ø37)
Handle
Power cable entry
4 x ø13 Fluid level gauge
(Grommet with membrane)
Caster with
(For anchor bolt) With casters (-A)
level foot
(Option)
Signal cable entry
(Grommet with membrane)
Overflow port Rc1/2
Tank drain port Rc1/2
(Plugged)
HRG015-A (-A)
(991)
Circulating fluid
pressure gauge
Refrigerant high
pressure gauge
Ventilation air outlet
Ventilation air inlet
Eye bolt M12
Ventilation air inlet
Ventilation air inlet
Automatic water
Operation
supply port Rc1/2
display panel
Circulating fluid outlet Rc3/4
Circulating fluid return port Rc3/4
Ventilation
By-pass valve
hole
(19)
(507)
(500) (30)
(440) (85) (918) (37)
(4 x ø37) Handle
Power cable entry
4 x ø13
Fluid level gauge
With casters (-A) (Grommet with membrane)
Caster with
(For anchor bolt)
(Option) level foot
Signal cable entry
(Grommet with membrane) Overflow port Rc1/2
Tank drain port Rc1/2
(Plugged)
16
(83) (83)
(51)
(595)
(1300)
(1300) (51) (595)
(442)
(582)
Thermo-cooler Series HRG
Dimensions: Water-Cooled Refrigeration
(990)
HRG010-W (-A)
Refrigerant high
pressure gauge
Facility water outlet Rc1/2
Facility water inlet Rc1/2
Y-strainer 1/2
(Accessory)
Operation display panel
Eye bolt M12
Automatic water
supply port Rc1/2
Circulating fluid outlet Rc3/4
(111)
Circulating fluid return port Rc3/4
Ventilation
hole
(19)
By-pass valve
Circulating fluid
(507) (500)
pressure gauge
(918)
(4 x ø37)
Fluid level gauge
Handle
4 x ø13
(440) (85)
Power cable entry
(For anchor bolt)
(30)
(Grommet with membrane)
Overflow port Rc1/2
With casters (-A)
(Option)
Signal cable entry
Tank drain port Rc1/2
(Grommet with membrane)
(Plugged)
HRG015-W (-A)
(990)
Refrigerant high
pressure gauge
Facility water outlet
Rc3/4
Facility water inlet
Y-strainer 3/4
Rc3/4
(Accessory)
Operation display panel
Eye bolt M12
Automatic water
supply port Rc1/2
Circulating fluid outlet Rc3/4
(133)
Circulating fluid return port Rc3/4
Ventilation
hole
(19)
By-pass valve
Circulating fluid
(507) (500)
pressure gauge
(918)
(4 x ø37)
Fluid level gauge
Handle
4 x ø13
(440) (85)
(For anchor bolt) Power cable entry
(30)
(Grommet with membrane)
Overflow port Rc1/2
With casters (-A)
(Option)
Signal cable entry
Tank drain port Rc1/2
(Grommet with membrane)
(Plugged)
17
(83)
(83)
(1300) (51) (595) (1300) (51) (595)
(442) (442)
Related Technical
HED HEB HEC HRW HRZD HRZ HRS HRG
Products Data
Series HRG
Piping Connection and Installation Dimensions
HRG010, HRG015
991
j
i
h
g
f
e
507 440 500 918
dc b a
∗ Example figure: HRG010-W
(mm)
Model a b c d e f g h i j
HRG010-A 242 342 402 452 115 230 400 560 — —
HRG010-W 242 342 402 452 115 230 400 560 850 1100
242 342 402 452 115 230 400 560 — —
HRG015-A
HRG015-W 242 342 402 452 115 230 400 560 850 1100
18
1300 595
83
Thermo-cooler Series HRG
Operation Display Panel
i o !0 !1 !2 !3
Function
No. Description
HRG010, HRG015
w
e
PV Displays the current temperature of the circulating fluid outlet.
7-segment
q
display screen
SV Displays the set temperature of the circulating fluid outlet.
q
w [ON] switch Starts the operation.
e [OFF] switch Stops the operation.
Note 1) Note 1)
r [MODE] key Changes the display between the temperature and control value .
Reduces the set temperature of the circulating fluid outlet.
t [DOWN] key
y [UP] key Increases the set temperature of the circulating fluid outlet.
Note 2) Note 2)
u [FUNC] key Activates functions that have been set.
r t y u
i [POWER] indicator Lights up when the power is being supplied to the unit.
Lights up when the unit is running.
o [RUN] indicator
!0 [PUMP] indicator Lights up when the pump is running independently, or when the main unit is running.
[ALARM] indicator,
!1 Lights up when ALARM 1 is active.
[ALARM1] indicator
!2 [ALARM2] indicator Lights up when ALARM 2 is active.
Lights up when ALARM 3 is active.
!3 [ALARM3] indicator
Note 1) All control values used in normal operation are displayed, but are locked and cannot be changed. It is not necessary
to unlock these values except during maintenance.
Note 2) However, functions are not set. Pressing this key will have no effect.
Alarm/Alarm Indicators and Explanation
The 6 basic temperature controller alarms are displayed on the operation display panel with alarm indicators (red LED). Operation
stops if an alarm is active, assuring safety. When the source of the problem has been eliminated, the equipment must be restarted.
Explanation of Alarms
Indicator Alarm Operation status Main reason
Prevention of reverse electrical current to the pump and compressor Stop Power supply to this unit is incorrect.
Note 3)
Low level of fluid in tank Stop Level switch activated because fluid level in tank fell below LOW.
[ALARM1]
Note 1)
Interrupted or abnormal facility water supply Stop Pressure switch activated because inadequate heat dissipation caused refrigerant pressure to rise.
Note 4)
Circulating fluid temperature abnormally high Stop Temperature sensor activated because circulating fluid temperature became too high.
[ALARM2]
Overload of pump Stop Circulation pump overload relay activated.
Note 2)
Note 5)
Overheating of fan motor Stop Fan motor thermostat activated.
[ALARM3]
Overload of compressor Stop Compressor overload relay activated.
Note 1) Only for water-cooled refrigeration (HRG-W)
Note 2) Only for air-cooled refrigeration (HRG-A)
Note 3) ALARM 1 lights up when power supply is turned on but operation has not commenced due to abnormal installation status: incorrect installation or inadequate preparation.
Note 4) ALARM 2 lights up if a water delivery circuit error occurs after operation has begun.
Note 5) ALARM 3 lights up if a refrigeration circuit error occurs after operation has begun.
19
Related Technical
HED HEB HEC HRW HRZD HRZ HRS HRG
Products Data
Series HRG
Contact Input/Output Function
The Thermo-cooler is equipped with terminals that allow remote start/stop, and enable output of an operation signal or abnormal
status stop signal. These should be used for synchronizing startup and shutdown with your other equipment, or when adding new
patrol lights or buzzers. However, the contact output volume is limited, so please add patrol lights and/or buzzers for special
relays (for amplification) if they are necessary.
Specifications
Item
HRG010 HRG015
Connector type M3 terminal block
Signal type DC voltage input
Remote
Input voltage range 24 VDC ±5 V
operation
Input current 0.5 to 8 mA
signal input
Note)
Terminal number 24 (24 VDC), 25 (24 VCOM)
Signal type Non-voltage contact output
Alarm stop
signal Contact capacity 250 VAC, 1 A (Resistance load)
output
Note)
Terminal number 28, 29
Signal type Non-voltage contact output
Operation
signal Contact capacity 250 VAC, 1 A (Resistance load)
output
Note)
Terminal number 30, 31
Customer’s machine side To the Thermo-cooler
Internal circuit
DC + 24 V
Remote operation signal
Voltage input
24 COM
Alarm stop signal
Circuit diagram
Contact output
Operation signal
Contact output
Note) For terminal numbers shown in the diagram, please refer to the terminal numbers
for each type of signal listed in the table.
Input/output signal connection location
Other Features
Remove the front panel and connect a signal cable to the terminal block inside
Automatic water supply function
the electrical component enclosure.
(Built-in ball tap)
The tank contains a built-in ball tap for
water supply valve.
By installing a water supply connection,
you can automatically keep the water
level at its rated position (halfway
between HI and LOW).
R S T E E E 24 25 28 29 30 31 37 38
Modified product with remote
operation signal
Remote operation is possible with a contact
Signal cable
input. No need for DC power supply.
∗ HRG010, 015---X106
Anti-freezing function
Signal cable outlet
Front side
(also used as communication cable outlet)
This function detects the circulating fluid
temperature. If the temperature
approaches freezing point, e.g. in winter
at night, the pump operates automatically
and the heat generated by the pump
warms the circulating fluid, preventing
freezing.
20
Series HRG
Note) Options have to be selected when
ordering the Thermo-cooler. It is
not possible to add them after
Options
purchasing the unit.
Option symbol Option symbol
A B
With Casters With Earth Leakage Breaker
HRG A HRG B
With casters With earth leakage breaker
The casters allow easy movement when delivering the equipment for In the event of a short circuit, overcurrent or overheating, the earth
installation or when altering the production area. A level foot may be used leakage breaker will automatically shut off the power supply. The power
instead of a brake. supply can be switched on or off easily from the main unit.
Applicable model HRG010--A HRG015--A Applicable model HRG010--B HRG015--B
Pole number 3
Level foot height adjustment
0 to 15
range (mm)
30
Rated current sensitivity (mA)
Product weight (kg) 220 215 245 235 Rated shutdown current (A) 40 60
Product height (mm) 1383 Short circuit display method Mechanical button
Caster mounting location Breaker mounting location
Rotating casters with level foot at the four corners are attached to the Remove the front panel. The breaker is mounted inside the electrical com-
caster bases. ponent enclosure.
Earth leakage breaker
Rotation
With casters
Level foot
Caster
Option symbol
C
With Communications Function (RS-485)
Communication connection location
HRG C
Remove the front panel, and connect your communication cable to the
terminal block mounted inside the electrical component enclosure.
With communications function (RS-485)
With a host PC programmed in accordance with your manufacturing
processor method, the communications function allows you to set (write)
or monitor (read) the circulating fluid temperature.
R S T E E E 24 25 28 29 30 31 37 38
Circulating fluid temperature setting (SV)
Circulating fluid present temperature (PV)
Communication cable
Circulating fluid temperature setting (SV)
Applicable model HRG010--C HRG015--C
Connector no. 37 (TRD+), 38 (TRD–)
M3 terminal block
Connector type (on this product side)
Standards EIA RS-485 compliant
Protocol Special protocol: For details, refer to the Communications Specifications document.
Customer’s machine To the Thermo-cooler
side
37
Circuit diagram
TRD (A+)
Internal
38
Communication
circuit
TRD (B–)
cable outlet
(also used as signal
cable outlet)
21
Related Technical
HED HEB HEC HRW HRZD HRZ HRS HRG
Products Data
Series HRG
Note) Please order separately.
Necessary to be fitted by
Optional Accessories
the customer.
Specifications
Description Description Specifications Applicable Thermo-cooler
For preventing a decline in the performance Maximum ambient
of air-cooled refrigerated Thermo-coolers, temperature
Dustproof filter set HRG010-A to 015-A
even in a dusty atmosphere. 40°C
For preventing the pump from overloading at
Circulating fluid
HRG010-A to 015-A
low flow rates when the maximum Thermo-
temperature range
By-pass piping set
cooler operating pressure of 0.5 MPa is
HRG010-W to 015-W
5°C to 35°C
exceeded.
Maximum ambient
temperature HRG010-A to 015-A
Separately installed Power supply and voltage for those other
40°C
than the standard.
power transformer
HRG010-W to 015-W
(Relative humidity 85% or less)
For fixing the Thermo-cooler to the founda- HRG010-A to 015-A
Foundation bolt set Stainless steel
tion. Easy to use – just drive in the core rod.
HRG010-W to 015-W
HRG010-A to 015-A
For converting the thread type used in the
Piping adapter Copper alloy
connection port of the Thermo-cooler.
HRG010-W to 015-W
How to Order
[Dustproof filter set] [By-pass piping set]
HRG FL HRG BP
Applicable Thermo-cooler Applicable Thermo-cooler
Symbol Applicable Thermo-cooler Quantity per set Set pressure
Symbol Applicable Thermo-cooler
(Blow pressure)
010 HRG010-A 1
010 HRG010- 0.31 [MPa]
(Large) 1
015 HRG015-A
(Small) 2
015 HRG015- 0.32 [MPa]
Note) Refer to page 23 for dimensions and page 25 for Note) Refer to page 23 for dimensions and pages 25 for
mounting. mounting and flow-rate characteristics.
[Separately installed power transformer]
IDF TR
Volume Power supply voltage
Symbol Applicable Thermo-cooler Volume Symbol Inlet voltage Outlet voltage Type
14000 HRG010- 14 kVA 220, 240, 380, 400, 3-phase
8 200 VAC (50/60 Hz)
415, 440 VAC (50/60 Hz) double
18000 HRG015- 18 kVA
Note) Refer to page 24 for dimensions.
[Foundation bolt set] [Piping adapter]
IDF AB IDF AP
Size Size
Symbol Applicable Thermo-cooler Material Quantity per set Thread type and port size
Quantity
Symbol Applicable Thermo-cooler Material
per set
HRG010- Male side A Female side B
Stainless steel 4
501
HRG015-
Copper
HRG010-
R3/4 NPT3/4 2
603
alloy
HRG015-
Note) Refer to page 24 for dimensions.
Note) Refer to page 24 for dimensions. Specify the quantity of units necessary
for use with your piping system.
22
Optional Accessories Series HRG
Dimensions
[Dustproof filter set]
HRG-FL010
A (10)
(mm)
Part no. Quantity per 1 set
A B C
HRG-FL010 880 440 10 1
(Large) 880 (Large) 440 (Large) 10 (Large) 1
HRG-FL015
(Small) 330 (Small) 440 (Small) 10 (Small) 2
(390) (390)
HRG-FL015
A (10) A (10)
(Large) (Small)
(390) (390)
[By-pass piping set]
HRG-BP010 HRG-BP015
C
A
E
D
Note)
Connection thread
Connection thread
(mm)
Part no. Connection thread R, Rc Weight (kg)
A B C D E H (Width across flats)
3/4 206 170 150 114 138 49 2.6
HRG-BP010
HRG-BP015 3/4 236 170 150 122 138 49 3.2
Note) The connection thread of the nipple comes with PTFE seal tape.
23
B B
(25) (25) (25) (25)
B
(25) (25)
H
B
Related Technical
HED HEB HEC HRW HRZD HRZ HRS HRG
Products Data
Series HRG
Dimensions
[Separately installed power transformer]
Specifications
Transformer part no. Applicable Thermo-cooler Volume Type Inlet voltage Outlet voltage
HRG010- 14 kVA
IDF-TR14000-8 3-phase
220, 240, 380, 400,
200 VAC (50/60 Hz)
double
415, 440 VAC (50/60 Hz)
IDF-TR18000-8 HRG015- 18 kVA
IDF-TR- -8
C E
øG
(mm)
Transformer part no. Weight (kg)
A B C D E F G
IDF-TR14000-8 400 650 450 300 350 13 40 152
A D IDF-TR18000-8 400 650 450 300 350 13 40 179
4 x øF
[Foundation bolt set]
(mm)
Part no. Applicable Thermo-cooler Nominal thread size Quantity per set
A
Mounting hole
HRG010-
70 4
IDF-AB501 M10
diameter: ø10.5
HRG015-
E (Width across flats)
[Piping adapter]
Female side B
Male side A
D
C
(mm)
Thread type and port size
Part no.
Applicable Thermo-cooler C D E Quantity per set
Male side A Female side B
HRG010-
IDF-AP603 R3/4 NPT3/4 43 23 32 2
HRG015-
24
B
A
Optional Accessories Series HRG
Mounting Example
Note) Please order separately. Necessary to be fitted by the customer.
[Dustproof filter set]
q This dustproof filter is secured with hook-and-loop tape. This is sewed onto the male side of the surface fastener, and has
adhesive tape backing for fixing to the female side.
w Remove the paper covering of the adhesive tape and affix the loop tape to the external panel of the ventilation hole on the
Thermo-cooler.
e Simply press the hook tape on to the loop tape to mount the dustproof filter.
Loop tape
(Surface fastener with adhesive tape backing)
w Affix to external panel.
q Dustproof filter (with surface
fastener and hook tape)
e Press on to secure the dustproof filter.
[By-pass piping set]
q This set consists of a body with assembly of relief valve and union (female), along with a nipple, union (male) and union seal.
w To mount, screw the union (male) and nipple onto the circulating fluid outlet and circulating fluid return port of the Thermo-cooler.
e Next, place the union seal between the union (male) and union (female) of the body, and gently tighten screw on
tentatively (manually), in the appropriate mounting direction for the model used (refer to Operation Manual), paying
attention to the direction of flow of the body (relief valve).
Note)
r Finally, tightly fasten the union (female) of the body to the union (male) tightly.
To thermo-cooler
circulating fluid outlet
By-pass (relief valve) piping set
To thermo-cooler
circulating fluid
return port
Nipple
Union (male)
Union seal
To customer’s
machine
Union (female) From customer’s
Relief valve
machine
Body
Note) Refer to “Temperature Control Equipment Precautions” on back page 3 for the nipple
tightening torque.
Refer to “Series HRG, Specific Product Precautions” on page 28 for the female union
tightening torque.
[Pump capacity for each Thermo-cooler after mounting the by-pass piping set]
HRG010- (After mounting HRG-BP010) HRG015- (After mounting HRG-BP015)
0.5 0.5
50 50
Outlet: 60 [Hz]
Outlet: 60 [Hz]
0.4 0.4
40 40
Outlet: 50 [Hz]
Outlet: 50 [Hz]
0.3 0.3
30 30
20 0.2 20 0.2
Return port: 60 [Hz]
Return port: 60 [Hz]
Return port: 50 [Hz] Return port: 50 [Hz]
10 0.1 10 0.1
0 0
0.0 0.0
0 10 20 30 40 50 60 70 80 0 10 20 30 40 50 60 70 80
Lifting height Pressure Lifting height Pressure
[m] [MPa] [m] [MPa]
Circulating fluid flow rate (L/min) Circulating fluid flow rate (L/min)
25
Related Technical
HED HEB HEC HRW HRZD HRZ HRS HRG
Products Data
Series HRG
Specific Product Precautions 1
Be sure to read this before handling.
Refer to back page 1 for Safety Instructions and back pages 2 to 5 for Temperature
Control Equipment Precautions.
Design Operating Environment/Storage Environment
Warning Warning
1. This catalog shows the specifications of a single 3. Conduct ventilation and cooling to discharge heat.
(Air-cooled refrigeration)
unit.
The heat which is cooled down through air-cooled condenser is discharged.
1. Confirm the specifications of the single unit (contents of this
When using in a room which is shut tightly, ambient temperature
catalog) and thoroughly consider the adaptability between the
will exceed the specification range stipulated in this catalog, which
customer’s system and this unit.
will activate the safety detector and stop the operation.
2. Although the protection circuit as a single unit is installed,
In order to avoid this situation, discharge the heat outside of a
prepare a drain pan, water leakage sensor, discharge air facility,
room by ventilation or cooling facilities.
and emergency stop equipment, depending on the customer’s
operating condition. Also, the customer is requested to carry out
Circulating Fluid
the safety design for the whole system.
2. When attempting to cool areas that are open to
Caution
the atmosphere (tanks, pipes), plan your piping
1. Avoid oil or other foreign objects entering the
system accordingly.
circulating fluid.
When cooling open-air external tanks, arrange the piping so that
there are coil pipes for cooling inside the tanks, and to carry back
2. Use an ethylene glycol aqueous solution that
the entire flow volume of circulating fluid that is released.
does not contain additives such as preservatives.
3. When using ethylene glycol aqueous solution,
Selection
maintain a maximum concentration of 15%.
Overly high concentrations can overload the pump, and cause
Warning
safety protection devices to commence operation, stopping the
operation of the unit.
1. Model selection
Low concentrations, however, can lead to freezing at cold
For selecting a model of Thermo-cooler, it is required to know the
temperatures and cause the Thermo-cooler to break down.
heat generation amount of a customer’s machine.
Obtain the heat generation amount, referring to the model selection 4. When using clear water as a circulating fluid,
example on pages 8 and 9 before selecting a model.
use water that conforms to the appropriate
water quality standards.
2. Indication of model number
Use water that conforms to the standards shown in the table below
Select the cooling method and temperature stability depending on
(including water used for dilution of ethylene glycol aqueous solution).
the customer’s application.
Clear Water (as Circulating Fluid) Quality Standards
Handling
The Japan Refrigeration and Air Conditioning Industry Association
JRA GL-02-1994 “Cooling water system – Circulation type – Make-up water”
Warning
Influence
Item Unit Standard value Scale
1. Thoroughly read the Operation Manual. Corrosion
generation
Read the Operation Manual completely before operation, and keep
pH (at 25°C) — 6.0 to 8.0
this manual available whenever necessary.
∗ ∗
Electrical conductivity (25°C) [µS/cm] 100 to 300
–
Chloride ion (Cl ) [mg/L] 50 or less
Operating Environment/Storage Environment
2–
Standard Sulfuric acid ion (SO ) [mg/L] 50 or less
4
item
Acid consumption amount (at pH4.8) [mg/L] 50 or less
Warning
Total hardness [mg/L] 70 or less
Calcium hardness (CaCO )
3 [mg/L] 50 or less
1. Do not use in the following environment
Ionic state silica (SiO ) [mg/L] 30 or less
2
because it will lead to a breakdown.
Iron (Fe) [mg/L] 0.3 or less
1. Environment like written in “Temperature Control Equipment
Copper (Cu) [mg/L] 0.1 or less
Precautions”.
–
Sulfide ion (S ) [mg/L] Should not be detected.
Reference 2
2. Locations where spatter will adhere to when welding.
+
item Ammonium ion (NH ) [mg/L] 0.1 or less
4
3. Locations where it is likely that the leakage of flammable gas
Residual chlorine (Cl) [mg/L] 0.3 or less
may occur.
Free carbon (CO ) [mg/L] 4.0 or less
2
4. Locations having a large quantity of dust.
∗ In the case of [MΩcm], it will be 0.003 to 0.01.
If it is necessary to use the unit in an environment where there is
: Factors that have an effect on corrosion or scale generation.
a risk of the fin portion of the air-cooled condenser becoming
Even if the water quality standards are met, complete prevention of corrosion is not guaranteed.
clogged, please use the dustproof filter set (sold separately).
5. It is possible to use or supply the unit with
2. Install in an environment where the unit will not
deionized water, but it is not possible to
come into direct contact with rain or snow.
maintain specific resistance.
(HRG010/015)
When using deionized water, make sure to supply water with an
These models are built to rainproof enclosure IPx3, but are not
electrical conductivity of 1 µS/cm or more. (In case of electrical
completely waterproof to rain, etc. (as with IPx4 or higher).
resistivity, it should be 1 MΩcm or less.) However, it is not
To prolong the lifespan of this equipment, we recommend
possible to maintain electrolyte concentration, as elements of the
installation under an awning or other shelter.
parts coming into contact with fluid may dissolve.
26
Series HRG
Specific Product Precautions 2
Be sure to read this before handling.
Refer to back page 1 for Safety Instructions and back pages 2 to 5 for Temperature
Control Equipment Precautions.
Transportation/Transfer/Movement Mounting/Installation
Warning Warning
1. Transportation by forklift 1. Do not place heavy objects on top of this
1. A licensed driver should drive the forklift. propiping, or step on it.
2. The proper place to insert the tines of the forklift differs
The external panel can be deformed and danger can result.
depending on the model of cooler. Check the Operation
2. Do not directly touch the edge of the external
Manual to confirm, and be sure to drive the fork in far
enough for it to come out the other side.
panel when removing and installing it.
3. Be careful not to bump the fork to the cover panel or piping
It may cause injury. Be sure to wear protective gloves.
ports.
(When using optional casters HRG--A)
2. Hanging transportation
3. Lower the level foot and do not move.
1. Crane manipulation and slinging work should be done by an
Be sure to lower all four level foot to the level of the floor.
eligible person.
2. Do not grip the piping on the right side or the handles of the
panel.
3. When hanging by the eye bolts, be sure to use a 4-point
hanging method. For the hanging angle, use caution
regarding the position of the center of gravity and hold it Caution
within 60°.
1. Install on a rigid floor which can withstand
Hanging position
this product’s weight.
60° or less
2. Secure with bolts, anchor bolts, etc.
Fasteners such as bolts or anchor bolts should be tighten with
the recommended torque shown below.
Forklift insertion side
Fixing Thread Tightening Torque
Connection thread Applicable tightening torque Nm
M5 3
M6
5.2
Front side
Forklift insertion side M8 12.5
M10 24.5
M12 42
(When using optional casters HRG--A)
1. Transportation by casters
(When using optional accessories/dustproof
1. This product is heavy and should be moved by at least two
filter set)
people.
2. Do not grip the piping port on the right side or the handles of
1. Use the attached surface fastener (with
the panel.
adhesive tape) to affix the dustproof filter to
3. When transporting using a forklift, be sure not to let it hit the
the panel of the Thermo-cooler.
casters or adjusters, and drive the fork all the way through
until it comes out the other side.
2. Mounting the filter will create a certain
amount of resistance to ventilation that will
reduce the volume of airflow.
For this reason, be sure to keep the ambient temperature at
40°C or less.
3. Depending on the installation height of the
Thermo-cooler and/or the cooled substrates,
circulating fluid may overflow from the tank
lid or overflow outlet.
In particular, avoid overflow from the lid of the built-in tank by
installing with a height difference of 10 m or less.
Be sure to pipe the overflow outlet to a wastewater collection
pit, etc.
27
Related Technical
HED HEB HEC HRW HRZD HRZ HRS HRG
Products Data
Series HRG
Specific Product Precautions 3
Be sure to read this before handling.
Refer to back page 1 for Safety Instructions and back pages 2 to 5 for Temperature
Control Equipment Precautions.
Piping
Caution
1. Regarding the circulating fluid pipings, (When using optional accessories/by-pass piping set)
consider carefully the suitability for shutoff
1. In order to prevent foreign objects from
pressure, temperature and circulating fluid.
entering during shipment, a polyethylene cap is
If the operating performance is not sufficient, the pipings may burst
attached to the inlets and outlets.
during operation.
Remove these caps before piping.
2. For the circulating fluid pipings, use clean
2. Pay attention to the flow direction of the relief
pipings which have no dust, piping debris or
valve.
other foreign objects inside the pipings, and
Refer to the mounting example shown in the separate operating
manual for the by-pass piping set when mounting.
blow with air prior to undertaking any piping
works.
3. Tighten to the applicable torque shown below
If piping debris or other foreign objects remain inside the circulating
when tightening the cap nut (female) of the
fluid circuit, it can result in blockage, insufficient cooling or damage
union.
to the pump impeller.
Union (Female) Tightening Torque
3. Select the piping port size which can exceed
Nominal size Applicable tightening torque Nm
the rated flow.
Rc1/2 64 to 125
For the rated flow, refer to the pump capacity table.
Rc3/4 106 to 208
4. When tightening at the circulating fluid inlets
and outlets, tank drain port or overflow outlet of
Electrical Wiring
this product, use a pipe wrench to clamp the
connection ports.
Warning
5. For the circulating fluid piping connection,
1. Never change the set value of the safety instrument.
install a drain pan and wastewater collection pit
If the set value is changed, it will likely cause a breakdown or
just in case the circulating fluid may leak.
cause the product to catch on fire.
6. While cleaning the inside of the tank, attach a
2. Before wiring, be sure to cut the power supply.
valve to the tank drain outlet to drain the
Never perform any job while the product is energized.
circulating fluid (clear water).
3. When connecting the power, confirm the phase
7. This product series consists of circulating fluid
sequence (R, S, T) of the three-phase AC power
temperature controllers with built-in tanks.
supply.
Do not install equipment on your system side such as pumps that
An incorrect phase sequence will cause the anti-reversal safety
forcibly return the circulating fluid to the unit. Also, if you attach an
protection device to be activated, and the unit will fail to operate.
external tank that is open to the air, it may become impossible to
If this occurs, switch the two wires to the correct phase sequence.
circulate the circulating fluid. Proceed with caution.
4. Secure the cable so that its force, etc. is not
(Water-cooled refrigeration HRG-W-)
applied to the terminal connector parts.
When the connection or attachment is incomplete, it will likely
1. When tightening at the facility water inlets and
lead to an electrical shock, a fire, etc.
outlets of this product, use a pipe wrench to
5. Grounding should never be connected to a
clamp the connection ports.
water line, gas line or lightning rod.
2. Install by-pass piping.
6. Multiple wiring is dangerous because it will lead
This product has a built-in water control valve, so when the
to heat generation or cause a fire.
refrigeration circuit is stopped, facility water does not flow out in
order to save energy.
For this reason, by-pass piping is necessary for conducting
Caution
maintenance of your facility water equipment, so be sure to install it.
1. Power supply, signal cable and connecting
3. When tightening at the water supply ports of
terminal should be prepared by the customer.
this product, use a pipe wrench to clamp these
2. In the event of wiring the signal for operation/stop
ports.
commands (remote control), use caution
This product has a built-in ball (float) tap. If you attach it to the
regarding the correct polarity (+, –) of 24 VDC.
faucet of a sink, etc. it will automatically supply water to the rated
fluid level of the tank (halfway between HIGH and LOW.)
(When using the HRG--C with optional
4. Supply water at a pressure of 0.5 MPa or less. communications function)
If the water supply pressure is too high, the pipes may burst during
1. Communication cables and adapters should be
use. Proceed with caution.
prepared by the customer.
Prepare parts that conform to the connector specifications of your
host computer.
2. Pay attention to the polarity (TRD+, TRD–) when
connecting communication cables.
28
Series HRG
Specific Product Precautions 4
Be sure to read this before handling.
Refer to back page 1 for Safety Instructions and back pages 2 to 5 for Temperature
Control Equipment Precautions.
Facility Water Supply Operation
Warning Caution
(Water-cooled refrigeration HRG-W-) 1. The temperature set value can be written to
EEPROM, but only up to approx. 1 million
1. Before startup, be sure to open the valve of
times.
your facility water equipment.
Especially when using communication function, save data with
Prepare before startup, so that facility water can flow when the
STOR before stoppage, and do not carry out frequent saving
fitted water control valve (facility water control valve) opens during
(STOR) of temporary setting values.
operation.
2. Supply pressure of 0.5 MPa or less.
If the supply pressure is high, it will cause water leakage. Operation Restart Time
3. Be sure to prepare your utilities so that the
Caution
pressure of the Thermo-cooler facility water
outlet is at 0 MPa (atmospheric pressure) or
1. Wait five minutes or more before restarting
more.
operation after it has been stopped. If the
If the facility water outlet pressure becomes negative, the internal
operation is restarted within five minutes, the
facility water piping may collapse, and proper flow control of facility
water will be impossible.
protection circuit may activate and the
operation may not start properly.
Operation
Protection Circuit
Warning
Caution
1. Confirmation before operation
1. The fluid level of a tank should be within the specified range of
1. If operating in the below conditions, the
“HIGH” and “LOW”.
protection circuit will activate and an operation
When exceeding the specified level, the circulating fluid will
overflow.
may not be performed or will stop.
2. Remove the air.
• Power supply voltage is not within the rated voltage range of
Conduct a trial operation, looking at the fluid level.
±10%.
Since the fluid level will go down when the air is removed from a
• The order of the 3-phase power supply, R, S, T is different.
customer’s piping system, supply water once again when the
• In case the water level inside the tank is reduced abnormally.
fluid level is reduced. When there is no reduction in the fluid
• Facility water is not supplied. (HRG-W)
level, the job of removing the air is completed.
• Transfer pressure of the circulating fluid is too high.
3. Handling of by-pass valve • Circulating fluid temperature is too high.
At the time this product is shipped from our factory, the by-pass • Compared to the cooling capacity, the heat generation amount
valve is fully open. of a customer’s machine is too high.
Operation with it fully closed will cause the circulating fluid outlet • Ambient temperature is too high. (40°C or higher)
pressure to increase high and it may safely stop in order to • Refrigerant pressure is too high.
prevent the pump’s operation from overloading. • Ventilation hole is clogged with dust or dirt. (Especially
When operating for the first time after installation, be sure to HRG-A)
operate it with the by-pass valve fully open.
2. Confirmation during operation
Maintenance
1. Adjust the by-pass valve.
Monitor the external piping, pressure gauge, or flow meter
Warning
mounted on the equipment from the customer’s side, in order to
adjust the open angle of the by-pass valve, so that the required
1. Do not operate the switch with wet hands or
pressure or flow can be obtained.
touch electrical parts. This will lead to an
2. Confirm the circulating fluid temperature.
The operating temperature range of the circulating fluid is
electrical shock.
between 5 and 35°C.
2. Do not splash water directly on this product for
When the amount of heat generated from a customer’s machine
cleaning.
is greater than the product’s capability, the circulating fluid
temperature may exceed this range. Use caution regarding this
This will lead to an electrical shock or a fire.
matter.
3. When the panel was removed for the purpose of
3. Emergency stop method
inspection or cleaning, mount the panel after
• When an abnormality is confirmed, stop the equipment
works were done.
immediately.
If the panel is still open, or running the equipment with the panel
After pushing the (OFF) switch, be sure to turn off the power
removed, it may cause an injury or electric shocks.
supply breaker.
4. When cleaning the air-cooled condenser, do
(When using optional accessories/by-pass piping set)
not touch the fin directly.
1. Do not adjust or change the preset pressure.
This may lead to injuries.
When persons other than experts carry out adjustments, leakage
can occur from the shaft seal of the adjustment screw. Proceed
with caution.
29
Related Technical
HED HEB HEC HRW HRZD HRZ HRS HRG
Products Data
Series HRG
Specific Product Precautions 5
Be sure to read this before handling.
Refer to back page 1 for Safety Instructions and back pages 2 to 5 for Temperature
Control Equipment Precautions.
Maintenance
Caution
(Air-cooled refrigeration HRG-A-)
1. Keep the pump operating.
1. Clean the ventilation hole.
• Keep the power supply running (POWER light
If the fin portion of the air-cooled condenser becomes clogged with
on, RUN light off), and fully open the valves
dust or debris, a decline in cooling performance can result.
in the circulating fluid piping.
In order to avoid deforming or damaging the fin, clean it with a long-
haired brush or air gun. If the circulating fluid temperature falls below 3°C, the pump will
start operating automatically. The heat generated by the pump
(When using optional accessories/dustproof
operation will warm up the circulating fluid. When the
temperature rises above 5°C, the pump will stop automatically.
filter set)
Consequently, the circulating fluid temperature is kept between
1. Clean the dustproof filter.
3°C and 5°C to avoid being frozen.
To prevent dirt or clogging of the dustproof filter from leading to
2. Make water-removal arrangements before-
a decline in heat-releasing performance of the air-cooled
condenser, clean or wash it regularly.
hand.
In extremely cold weather conditions, the heat generated by the
2. Remove the filter from the Thermo-cooler
pump as described above may not be enough to prevent
before cleaning it.
freezing.
Do not directly splash water on the filter to clean it while it is still
If you expect these kind of conditions, remove the circulating
attached to the Thermo-cooler.
fluid (especially clear water or deionized water) beforehand.
This can lead to electric shock or fires in the main unit of the
3. Consult a professional.
Thermo-cooler.
For additional methods to prevent freezing (such as
commercially available tape heaters, etc.), consult a
professional for advice.
1. Inspect the circulating fluid.
1. When using clear water or deionized water
• Replacement of clear water or deionized water
Failure to replace the clear water or deionized water can
lead to the development of bacteria or algae. Replace it
regularly depending on your usage conditions.
• Tank cleaning
Consider whether dirt, slime or foreign objects may be
present in the circulating fluid inside the tank, and carry out
regular cleanings of the tank.
2. When using ethylene glycol aqueous solution
Use a concentration measurement device to confirm that the
concentration does not exceed 15%.
Dilute or add as needed to adjust the concentration.
2. Check the water quality of facility water.
Regarding the water quality standards for facility water, refer to
“Temperature Control Equipment Precautions”.
1. Inspect the circulating fluid.
1. Remove the panel and inspect if there is abnormal leakage
from the pump’s mechanical seal.
2. Leakage amount of a mechanical seal
Leakage of the mechanical seal cannot be completely
avoided due to its construction (rotating machine).
Although this amount of leakage is stipulated as 3 (cc/h) or
less (reference value) according to the JIS standard, replace
the mechanical seal when the amount of leakage is 0.3
(cc/h) or greater.
Also, as a guide for periodically replacement, the operation
Note)
hours is 6000 to 8000 hours. (normally 1 year)
Note) In placing an order of mechanical seal set (service parts), inform
us of the complete model number and the production lot number
of the product in use.
30
What they say about us
FANTASTIC RESOURCE
One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!
Bucher Emhart Glass
EXCELLENT SERVICE
With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.
Fuji
HARD TO FIND A BETTER PROVIDER
Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.
Applied Materials
CONSISTENTLY DELIVERS QUALITY SOLUTIONS
Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.
Nidec Vamco
TERRIFIC RESOURCE
This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.
Trican Well Service
GO TO SOURCE
When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.
ConAgra Foods