Elite.Parts chervon right Manufacturers chervon right R chervon right RED LION CONTROLS chervon right IAMA3535
About product Specifications Features Datasheet FAQ

RED LION CONTROLS IAMA3535

Image of RED LION CONTROLS IAMA3535

Description

Red Lion Controls IAMA3535 Universal Signal Conditioning Module

Part Number

IAMA3535

Price

Request Quote

Manufacturer

RED LION CONTROLS

Lead Time

Request Quote

Category

CONTROLS, PROCESS

Specifications

ACCURACY (INCLUDING LINEARITY)

Factory: ±0.1% of span max. for all ranges except 1 mA, 2 mA, and 20 mV. These ranges are

INPUT PROTECTION

Surge suppressor diodes

INPUT RESISTANCE

Current: 10 ? Voltage: > 100 K

INPUT/OUTPUT RANGE

See Tables 2 and 3

ISOLATION LEVEL INPUT TO OUTPUT

1.5 kV @ 50/60 Hz, 1 mi

LOAD RESISTANCE

Current Output: =600 ? Voltage Output: =1 K?

MAX INPUT SIGNAL

Current Input: 110 mA DC, 1.1 VDCVoltage Inputs: Terminal 7- 1 VDC +10%

MAX OUTPUT CURRENT

Current Output: 22 mA Voltage Output: 10 mA

OUTPUT COMPLIANCE

Current: 4 to 20 mA, 0 to 20 mA: 12 V min (=600 ?)0 to 1 mA: 10 V min (=10 K?)Voltage: 10 VDC across a min. 1 K?load (10 mA). Factory calibrated for loads of > 1 M?.

POWER

11 to 36 VDC, 3 W max. or 24 VAC, ±10%, 50/60 Hz, 4.8 VA ma

RESOLUTION

0.01% full scale input, 0.01% full scale output

STEP RESPONSE

To within 99% of full scale: 300 msec

ZERO/SPAN ADJUSTMENTS

Digital (DIP Switch Transition)

Features

Datasheet

pdf file

Red Lion-IAMA3535-Datasheet1-2045678408.pdf

1177 KiB

Extracted Text

Bulletin No. IAMA-F Drawing No. LP0413 Released 3/07 Tel +1 (717) 767-6511 Fax +1 (717) 764-0839 www.redlion.net MODEL IAMA - UNIVERSAL SIGNAL CONDITIONING MODULE z 3-WAY ISOLATION OF ANALOG SIGNALS z UNIVERSAL CONVERSION MODULE - INPUTS AND OUTPUTS SELECTED VIA DIP SWITCH SETTINGS z OVER 100 INPUT AND OUTPUT ANALOG CONVERSION COMBINATIONS z CHOOSE LINEAR OR SQUARE ROOT EXTRACTION MODEL z ALL RANGES ARE FACTORY PRECALIBRATED. CUSTOM FIELD CALIBRATION IS AVAILABLE FOR ALL RANGES WHILE MAINTAINING THE FACTORY CALIBRATION FOR FUTURE USE z 11 to 36 VDC AND 24 VAC MODULE POWER UL Recognized Component, File # E179259 GENERAL DESCRIPTION SAFETY SUMMARY The IAMA – Universal Signal Conditioning Module Series can isolate and All safety related regulations, local codes and instructions that appear in the convert over 100 combinations of analog signal ranges. The IAMA3535 manual or on equipment must be observed to ensure personal safety and to converts and transmits signals linearly proportional to the input, while the prevent damage to either the instrument or equipment connected to it. If IAMA6262 transmits the scaled square root of the input signal. This allows the equipment is used in a manner not specified by the manufacturer, the protection IAMA6262 to provide a signal that is linear to flow rate in applications utilizing provided by the equipment may be impaired. a differential pressure transducer. DIP switch range selection eliminates the need to order and stock different modules for each input and output signal range, and allows quick and convenient setup for over 100 standard signal conversions. By utilizing the CAUTION: Risk of Danger. CAUTION: Risk of electric shock. Field mode of calibration, the user can customize the input and output scaling Read complete instructions prior for odd applications, including reversal of the output relative to the input. to installation and operation of the unit. In addition to the conversion capabilities, the IAMA modules feature optically isolated Input/Output signal circuits and transformer isolated Power to ORDERING INFORMATION Input, Power to Output circuits. The modules’ overall full scale accuracy typically exceed 0.05% depending MODEL NO. DESCRIPTION PART NUMBER upon range selection and scaling. The microprocessor based design provides Linear Universal Signal Conditioning Module IAMA3535 2 ease of field scaling and the onboard E PROM stores scaling values for future IAMA Square Root Universal Signal Conditioning Module IAMA6262 recall. Both models come factory precalibrated for all input and output ranges. Factory or custom field scaling can be selected by a simple mode switch change. The IAMA can be factory recalibrated in the field if desired. SPECIFICATIONS The modules’ environmental operating temperature range is -20°C to +65°C. 1. POWER: 11 to 36 VDC, 3 W max. or 24 VAC, ±10%, 50/60 Hz, 4.8 VA max. DIN rail mounting saves time and panel space. The units are equipped with 2. INPUT/OUTPUT RANGES: See Tables 2 and 3 universal mounting feet for attachment to standard DIN style rails, including top 3. ZERO/SPAN ADJUSTMENTS: Digital (DIP Switch Transition) hat profile rail according to EN50022 - 35x7.5 and 35 x 15 and G profile rail 4. MAX INPUT SIGNAL: according to EN50035-G32. Current Input: 110 mA DC, 1.1 VDC Voltage Inputs: Terminal 7- 1 VDC +10% Terminal 8- 10 VDC +10% Terminal 9- 100 VDC +10% DIMENSIONS In inches (mm) 5. INPUT RESISTANCE: Current: 10 Ω Voltage: > 100 K 6. INPUT PROTECTION: Surge suppressor diodes 7. MAX OUTPUT CURRENT: Current Output: 22 mA Voltage Output: 10 mA 8. LOAD RESISTANCE: Current Output: ≤ 600 Ω Voltage Output: ≥ 1 KΩ 9. OUTPUT COMPLIANCE: Current: 4 to 20 mA, 0 to 20 mA: 12 V min (≤ 600 Ω) 0 to 1 mA: 10 V min (≤10 KΩ) Voltage: 10 VDC across a min. 1 KΩ load (10 mA). Factory calibrated for loads of > 1 MΩ. 10. ISOLATION LEVEL INPUT TO OUTPUT: 1.5 kV @ 50/60 Hz, 1 min 11. STEP RESPONSE: To within 99% of full scale: 300 msec 12. ACCURACY (INCLUDING LINEARITY): Factory: ±0.1% of span max. for all ranges except 1 mA, 2 mA, and 20 mV. These ranges are accurate to ±0.2% of span max. All ranges can be field calibrated to 0.1% of span max. 13. RESOLUTION: 0.01% full scale input, 0.01% full scale output 1 14. ENVIRONMENTAL CONDITIONS: OVERVIEW Operating Temperature Range: -20 to +65 °C The IAMA3535 continuously monitors a voltage or current input and Storage Temperature Range: -40 to +85 °C provides a linearly proportional voltage or current output, while the IAMA6262 Operating and Storage Humidity: 85% max. relative humidity (non- transmits the scaled square root of the input signal. This allows the IAMA6262 condensing) from -20 to +65 °C to provide a signal that is linear to flow rate in applications utilizing a Temperature Coefficient: ± 0.01%/°C (100 PPM/°C) max. differential pressure transducer. Both units have two modes of operation known Altitude: Up to 2000 meters as Factory and Field modes. Factory mode is used when the default input and 15. CERTIFICATIONS AND COMPLIANCES: output ranges are suitable. Field mode can be independently selected for both SAFETY the input and output, and allows the user to custom calibrate, or scale the signal. UL Recognized Component, File #E179259, UL3101-1, CSA C22.2 If Factory mode is selected, the IAMAs use factory presets for the selected input No. 1010-1 or output range. If Field mode is selected, the IAMAs can be custom scaled Recognized to U.S. and Canadian requirements under the Component within a selected input or output range. Field mode also allows the IAMA to Recognition Program of Underwriters Laboratories, Inc. reverse its output in relation to its input. IECEE CB Scheme Test Certificate # US/5141B/UL, The units are factory precalibrated for minimum and full scale for all input CB Scheme Test Report # 01ME11540-0702001 and output ranges. The factory calibration values are permanently stored in Issued by Underwriters Laboratories, Inc. 2 E PROM and should not be changed in the field, unless unacceptable error or a IEC 61010-1, EN 61010-1: Safety requirements for electrical equipment factory checksum error occurs. See Factory Recalibration for details. Field for measurement, control, and laboratory use, Part 1. scaling is achieved by applying minimum and full scale values from a ELECTROMAGNETIC COMPATIBILITY calibration source and storing the values by a single DIP switch transition. Field Notes: scaling is available for all input and output ranges and the values are Immunity to EN 50082-2 2 permanently stored in E PROM until reprogramming occurs. Electrostatic discharge EN 61000-4-2 Level 2; 4 Kv contact After field scaling, the IAMAs can be changed between Factory and Field Level 3; 8 Kv air modes for a particular range, which restores the respective setting. The Factory 1 Electromagnetic RF fields EN 61000-4-3 2 Level 3; 10 V/m and Field E PROM locations contain the same calibration values when the 80 MHz - 1 GHz IAMA is received from the factory. Therefore, until the IAMA is field scaled, 2 Fast transients (burst) EN 61000-4-4 Level 4; 2 Kv I/O factory and field modes perform identically. See SCALING PROCEDURE for 2 Level 3; 2 Kv power detailed instructions on field programming the IAMA. RF conducted interference EN 61000-4-6 Level 3; 10 V/rms The units can be scaled to any minimum scale and full scale values within the 150 KHz - 80 MHz extent of the selected range. The closer together the minimum and full scale Simulation of cordless telephone ENV 50204 Level 3; 10 V/m values are to each other, the less accurate the signal will be. For example, if the 0 to 1 V input range is selected, and the unit is scaled for 0 to 0.5 V, the signal 900 MHz ± 5 MHz has the same resolution as the 0 to 1 V range. Since this resolution will be two 200 Hz, 50% duty cycle times the percentage of span for 0.5 V, more accuracy can be achieved by using Emissions to EN 50081-2 the 0 to 0.5 V range. RF interference EN 55011 Enclosure class A The input may exceed the full scale value for the selected range by 10% of Power mains class A span, but the IAMA will not update the output beyond 10% over range. The red and green LED’s indicate the status of the modules during scaling and 1. Self-recoverable loss of performance during EMI disturbance at 10 V/m: normal operation. Table 1, LED Indications, details the LED indications for Analog output signal deviation less than 5% of full scale. various unit conditions. For operation without loss of performance: The IAMA – Signal Conditioning Module Series is designed for use in Install power line filter, RLC #LFIL0000 or equivalent on DC power industrial environments. Suppressor diodes protect both input and output lines at unit. circuits from wiring errors and transient high voltage conditions. OR Install 2 ferrite cores, RLC #FCOR0000 or equivalent, to DC power lines at unit. INPUTS 2. Criteria A: No loss of performance within the unit’s specifications. The IAMAs accept a full range of process signal inputs and isolate and Refer to EMC Installation Guidelines section of this bulletin for additional convert these signals to common industrial control signals. The input signal information. combinations are configured by making specific DIP switch selections on the 10 16. CONSTRUCTION: Case body is black high impact plastic position DIP switch. 17. CONNECTIONS: 14 AWG max 18. MOUNTING: Standard DIN top hat (T) profile rail according to EN50022 OUTPUTS - 35x7.5 and 35 x 15 and G profile rail according to EN50035-G32. As with the input choices, the process signal output of the modules is DIP 19. WEIGHT: 4.5 oz. (127.57 g) switch selectable. A 1 position DIP switch is used to select between the 1 mA/20 mA output ranges. The maximum output current signal is 22 mA with ≤600 Ω output resistance and the maximum output voltage signal is 11 V with ≥1 KΩ BLOCK DIAGRAM output resistance. ZERO AND SPAN The input zero and span are set by first applying the minimum value then transitioning S1-2 to store that value. Next, the full scale value is applied and the DIP switch transition stores the value. The output scaling is performed in a similar manner but the output is driven to the desired minimum and full scale values by the calibration source applied to the input. S1-1 is used to store the minimum and full scale output values. The span is defined by: span = (full scale - minimum scale). ILLEGAL RANGE SELECTIONS AND CHANGES The ranges should only be selected before power is applied. If an invalid input * Terminal number is dependent on max. input voltage. or output range is selected when power is applied the output is set to approximately 0 VDC and the red LED indicates the error according to Table 1. Power must be removed and valid ranges selected for the IAMA to operate properly. MODULE ISOLATION If S1 switches 3 through 10 are changed while the IAMA is operating, the red IAMA modules feature “3-Way” Signal Isolation. The 3-Way isolation is a LED indicates a range change according to Table 1, LED Indications and the combination of optical and transformer isolation. The optical isolation provides output goes to the previously stored range minimum scale value. Normal common mode voltage (CMV) isolation up to 1.5 kV between the sensor input and operation will be resumed if the switches are placed back in the previous the process signal output. The IAMA’s power is isolated from the sensor signal positions or power is removed and restored. input and the process signal output by a DC/DC transformer isolation circuit. 2 CHECKSUM ERRORS FIELD OR FACTORY MODE SELECTION A checksum is performed every time power is applied to the IAMA. If a SELECTING FIELD MODE (2 Methods): checksum error occurs, the LEDs will indicate where the error occurred 1. Scale the input or output according to SCALING PROCEDURE 2.0 or 4.0 according to Table 1, LED Indications. Operation with a checksum error is not 2. Before applying power, set the input or output (or both) field/factory switch recommended but can be done in critical situations. If an error occurs, re- to the up (field) position. Field calibration values will be restored upon calibration of the field or factory ranges to be used must be performed. 2 power-up. If the IAMA has not been previously field calibrated, the E PROM If a field checksum error occurs, the IAMA will operate only in factory mode. will contain the factory calibration values which will be restored. If a factory checksum occurs, the IAMA will operate only in a previously calibrated field mode. Do not perform a field scaling until the factory checksum SELECTING FACTORY MODE (2 Methods): is cleared. Since a checksum error is a high priority LED indication, the LEDs will 1. Before applying power to the IAMA set the input or output (or both) indicate the error until it is cleared. This will exclude other LED information. field/factory switch to the down (factory) position. Factory calibration values will be restored upon power-up. TABLE 1, LED INDICATIONS 2. While power is applied to the IAMA and it is operating in the field input and/or output mode, set the desired field/factory switch(s) to the down CONDITION GREEN LED RED LED (factory) position. The factory calibration values will be restored. Normal Operation On Off Scaling Mode Alternate with Red Alternate with Green EMC INSTALLATION GUIDELINES Under Range Off Slow Flash (0.8 sec rate) Although this unit is designed with a high degree of immunity to Over Range Off Fast Flash (0.4 sec rate) ElectroMagnetic Interference (EMI), proper installation and wiring methods must Invalid Range Off On be followed to ensure compatibility in each application. The type of the electrical Illegal Range Change Off On noise, source or coupling method into the unit may be different for various Factory Checksum Off On, short off installations. Cable length, routing, and shield termination are very important and Field Checksum On, short off Off can mean the difference between a successful or troublesome installation. Listed below are some EMC guidelines for successful installation in an User Factory Calibration Fast Flash for 2 sec Off industrial environment. 1. Use shielded (screened) cables for all Signal and Control inputs. The shield GETTING STARTED (screen) pigtail connection should be made as short as possible. The One method for the Input (1 or 2 below) should be configured, and one connection point for the shield depends somewhat upon the application. method for the Output (3 or 4 below) should be configured. Listed below are the recommended methods of connecting the shield, in order 1. FACTORY preprogrammed settings for the Input, see Section 1.0 of their effectiveness. 2. FIELD scaling method for the Input, see Section 2.0 a. Connect the shield only at the rail where the unit is mounted to earth 3. FACTORY preprogrammed setting for the Output, see Section 3.0 ground (protective earth). 4. FIELD scaling method for the Output, see Section 4.0 b. Connect the shield to earth ground at both ends of the cable, usually when the noise source frequency is above 1 MHz. Note: The ranges should only be changed while power is removed from the IAMA. c. Connect the shield to common of the unit and leave the other end of the shield unconnected and insulated from earth ground. TABLE 2, OUTPUT RANGE SETTINGS 2. Never run Signal or Control cables in the same conduit or raceway with AC RANGE DIP power lines, conductors feeding motors, solenoids, SCR controls, and OUTPUT SWITCHES RANGE heaters, etc. The cables should be run in metal conduit that is properly 3 4 5 grounded. This is especially useful in applications where cable runs are long 0 - 5 V 0 0 0 VOLTAGE and portable two-way radios are used in close proximity or if the installation OUTPUTS 0 - 10 V 0 0 1 is near a commercial radio transmitter. 0 - 1 mA 0 1 0 3. Signal or Control cables within an enclosure should be routed as far away as CURRENT 4 - 20 mA 0 1 1 OUTPUTS possible from contactors, control relays, transformers, and other noisy 0 - 20 mA 1 0 0 components. Note: DIP switch settings 0 = OFF 1 = ON 4. In extremely high EMI environments, the use of external EMI suppression devices, such as ferrite suppression cores, is effective. Install them on Signal and Control cables as close to the unit as possible. Loop the cable through the core several times or use multiple cores on each cable for additional protection. TABLE 3, INPUT RANGE SETTINGS Install line filters on the power input cable to the unit to suppress power line RANGE DIP SWITCHES RANGE interference. Install them near the power entry point of the enclosure. The 6 7 8 9 10 following EMI suppression devices (or equivalent) are recommended: 0 - 20 mV 0 0 0 0 0 Ferrite Suppression Cores for signal and control cables: 0 - 50 mV 0 0 0 0 1 Fair-Rite # 0443167251 (RLC #FCOR0000) 0 - 100 mV 0 0 0 1 0 TDK # ZCAT3035-1330A 0 - 200 mV 0 0 0 1 1 Steward #28B2029-0A0 0 - 500 mV 0 0 1 0 0 Line Filters for input power cables: 0 - 1 V 0 0 1 0 1 Schaffner # FN610-1/07 (RLC #LFIL0000) INPUT 0 - 2 V 0 0 1 1 0 Schaffner # FN670-1.8/07 VOLTAGE 1 - 5 V Corcom #1VR3 0 0 1 1 1 0 - 5 V Note: Reference manufacturer’s instructions when installing a line filter. 0 1 0 0 0 5. Long cable runs are more susceptible to EMI pickup than short cable runs. 0 - 10 V 0 1 0 0 1 Therefore, keep cable runs as short as possible. 0 - 20 V 0 1 0 1 0 0 - 50 V 0 1 0 1 1 0 - 100 V 0 1 1 0 0 WIRING CONNECTIONS 0 - 1 mA 0 1 1 0 1 All conductors should meet voltage and current ratings for each terminal. 0 - 2 mA 0 1 1 1 0 Also cabling should conform to appropriate standards of good installation, local 0 - 5 mA 0 1 1 1 1 codes and regulations. It is recommended that power supplied to the unit be 0 - 10 mA 1 0 0 0 0 INPUT protected by a fuse or circuit breaker. When wiring the unit, use the numbers on CURRENT 4 - 20 mA 1 0 0 0 1 the label to identify the position number with the proper function. Strip the wire, 0 - 20 mA 1 0 0 1 0 leaving approximately 1/4" (6 mm) of bare wire exposed. Insert the wire into 0 - 50 mA 1 0 0 1 1 the terminal, and tighten the screw until the wire is clamped tightly. 0 - 100 mA 1 0 1 0 0 Note: DIP switch settings 0 = OFF 1 = ON 3 POWER AND OUTPUT CONNECTIONS INPUT CONNECTIONS Current Input Power Wiring for a current input is Primary power is connected to terminals 2 and 3 (labeled VDC- and VDC+). connected to terminals 10 (IIN) and For best results, the Power should be relatively “clean” and within the specified 12 (INPUT COMMON). variation limits. Drawing power from heavily loaded circuits or from circuits that also power loads that cycle on and off, should be avoided. Voltage Input Wiring for a voltage input is Current Output connected to terminal 12 (INPUT Wiring for a current output is connected to terminals 1 (IOUT-) and 4 (IOUT+). COMMON) and one of the three DIP switch S2 should be set for the desired full scale output current. (20 mA = available voltage terminals listed ON; 1 mA = OFF). below, depending on maximum Voltage Output input voltage. Wiring for a voltage output is connected to terminals 5 (VOUT-) and 6 Terminal 7: 1 VDC max. (VOUT+). Terminal 8: 10 VDC max. Terminal 9: 100 VDC max. Note: Although signals are present at voltage and current outputs at the same time, only the selected range is in calibration at any one time. Example: A 0 to 10 VDC output is selected. The voltage level present at the voltage output terminals is in calibration, but the signal appearing at the current output terminals does not conform to any of the current output ranges. SCALING PROCEDURE The accuracy of the IAMA is dependent on the accuracy of the calibration source and the voltage or current meter used in the scaling process. If an out of range (see Table 1 for LED indications) or illegal (full scale less than minimum scale) scaling is attempted, the factory calibration values will be stored in place of the field values. This will prohibit erroneous operation of the IAMA. The scaling procedure will have to be repeated. 2 The final storage of the zero and full scale values to E PROM is not done until the last transition of the mode/calibration DIP switches (S1-1 or S1-2). Therefore, the scaling can be aborted any time before the full scale value is saved. This is accomplished by cycling power to the IAMA. The IAMA will restore the factory or previous field scaling values at power up depending on the setting of the DIP switches. See Mode Selection for more detailed instructions for selecting factory and field modes at power up. See Table 2 and 3 for the input and output range DIP switch settings. 1.0 INPUT SET-UP USING FACTORY CONFIGURATION 1.1 Remove power. 1.2 Connect signal wires to the correct input terminals based on the maximum signal input. Terminal 7: max. signal input 1 VDC Terminal 8: max. signal input 10 VDC Terminal 9: max. signal input 100 VDC Terminal 10: max. signal input 100 mA Terminal 12: signal common 1.3 Set Input Range switches (S1 switches 6 through 10) to the desired Input Range (See Table 3). (0 to 10 VDC range shown). Step 1.3 1.4 Set Input Field/Fact. switch (S1 switch 2) to the off position. Step 1.4 1.5 Apply power to the IAMA. Solid illumination of Green LED if signal is within the minimum and maximum limits of the selected input range. Slow blinking of Red LED if signal decreases below minimum limit of selected input range. Rapid blinking of Red LED if signal increases above maximum limit of selected input range. 1.6 Input set-up complete. Go to Step 3.0 or Step 4.0. 4 2.0 INPUT SCALING USING FIELD CONFIGURATION 2.1 Remove power. 2.2 Connect signal source to the correct input terminals based on the maximum signal input. Terminal 7: max. signal input 1 VDC Terminal 8: max. signal input 10 VDC Terminal 9: max. signal input 100 VDC Terminal 10: max. signal input 100 mA Terminal 12: signal common 2.3 Set Input Range switches (S1 switches 6 through 10) to the desired input range (See Table 3). Select the lowest possible range that will support the desired Step 2.3 maximum signal. Example: if the desired span is 20 mV to 85 mV, the best range selection is 0 to 100 mV. The 0 to 200 mV will also suffice, but the accuracy will be reduced. (0 to 10 VDC range shown). 2.4 Set Input Field/Fact. switch (S1 switch 2) to the off position. Step 2.4 2.5 Apply power to the IAMA and allow a warm up period of five minutes. Follow the manufacturer’s warm up procedure for the calibration source. 2.6 Set Input Field/Fact. switch (S1 switch 2) to the on position. The Red and Green LEDs will alternately blink. Step 2.6 2.7 Apply desired minimum scale signal. 2.8 Set Input Field/Fact. switch (S1 switch 2) to the off position. The Red and Green LEDs will alternately blink. If the signal is equal or below the minimum limit of the selected range, the Red LED Step 2.8 blinks slowly and the Green LED turns off. Removing power aborts scaling, begin at Step 2.1. 2.9 Apply maximum scale input. The Red and Green LEDs will alternately blink. 2.10 Set Input Field/Fact. switch (S1 switch 2) to the on position. Red LED extinguishes and Green LED becomes solid. Your scaled values are now saved and recalled if the Input Field/Fact. switch (S1 switch 2) is in the on Step 2.10 position when power is applied. Red LED will blink slowly if signal is equal to or below minimum limit and blinks rapidly if signal increases above maximum limit. 2.11 Input scaling complete. Go to Step 3.0 or Step 4.0. 3.0 OUTPUT SET-UP USING FACTORY CONFIGURATION 3.1 Remove power. 3.2 For voltage output values, go to Step 3.4 For current output values, continue at Step 3.3 3.3 Set 20 mA/1 mA switch (S2) to desired full scale output. (20 mA - on; 1 mA - off) Step 3.3 & 3.4 3.4 Set Output Field/Fact. switch (S1 switch 1) to the off position. 3.5 Set Output Range switches (S1 switches 3, 4, and 5) to the desired Output Range (See Table 2). (4 to 20 mA range shown) Step 3.5 3.6 Connect external device to appropriate IAMA output terminals. Terminal 6: + Voltage Terminal 5: - Voltage Terminal 4: + Current Terminal 1: - Current 3.7 Apply power to the IAMA and allow a warm up period of five minutes. Output set-up complete. 5 4.0 OUTPUT SCALING USING FIELD CONFIGURATION 4.1 Remove power. 4.2 For voltage output scaling, go to Step 4.4. For current output scaling, continue at Step 4.3. 4.3 Set 20 mA/1 mA switch (S2) to desired full scale output. (20 mA - on; 1 mA - off) Step 4.4 4.4 Set Output Field/Fact. switch (S1 switch 1) to the off position. 4.5 Set Output Range switches (S1 switches 3, 4, and 5) to the desired Output Range Step 4.5 (See Table 2). Select the lowest possible range that will support the desired full scale output. Example: if the desired span is 1 V to 4 V, the best range selection is 0 to 5 V. (0 to 5 VDC range shown) 4.6 Connect volt or current meter to appropriate IAMA output terminals. Terminal 6: + Voltage Terminal 5: - Voltage Terminal 4: + Current Terminal 1: - Current 4.7 An input signal is required to complete output scaling. If previous scaled input is used (completed in Step 2.0), Input Field/Fact. switch (S1 switch 2) and Input Range switches (S1 switches 6 through 10) must remain in the same positions. If another signal source is used, set Input Field/Fact. switch (S1 switch 2) to off position and Input Range switches (S1 switches 6 through 10) to the desired input range (See Table 3). 4.8 Connect input signal source to the correct input terminals based on the maximum signal input. Terminal 7: max. signal input 1 VDC Terminal 8: max. signal input 10 VDC Terminal 9: max. signal input 100 VDC Terminal 10: max. signal input 100 mA Terminal 12: signal common 4.9 Apply power to the IAMA and allow a warm up period of five minutes. 4.10 Set Output Field/Fact. switch (S1 switch 1) to the on position. The Red and Green LEDs will alternately blink. If Red LED blinks slowly, increase signal until Red and Green LEDs alternately blink. Step 4.10 4.11 Adjust the input signal until the desired * minimum output level is displayed on the volt or current meter. The Red and Green LEDs will alternately blink. 4.12 Set Output Field/Fact. switch (S1 switch 1) to the off position. The Red and Green LEDs alternately blink. Step 4.12 If the signal is equal to or below the minimum limit of the selected range, the Red LED blinks slowly and the Green LED turns off. Removing power aborts scaling. Start over at Step 4.1. 4.13 Adjust the input signal until the desired * maximum output level is displayed on the volt or current meter. 4.14 Set Output Field/Fact. switch (S1 switch 1) to the on position. Red LED extinguishes and Green LED becomes solid. Your scaled values are now Step 4.14 saved and will be recalled if the Output Field/Fact. switch (S1 switch 1) is in the on position when power is applied. 4.15 Output scaling is complete. * If the minimum output is higher than the maximum output the module reverses its output behaviour accordingly. 6 RECALIBRATING FACTORY STORED VALUES INPUT RECALIBRATION WARNING: Read the complete procedure at least 1. To enter the factory calibration mode, set switches S1-1 and S1-2 down, S1- 3 through S1-5 up, and S1-6 through S1-10 down. once before attempting to recalibrate the factory 2. Connect a signal source to the correct input terminals based on the values. This procedure should only be maximum signal input to be calibrated. If an output range will be calibrated performed due to factory checksum error or after the input range is calibrated, connect a voltage or current meter to the unacceptable error. This procedure should be appropriate output terminals at this time. performed by qualified technicians using 3. Apply power to the IAMA. After the version number indication, the green accurate calibration equipment. LED will flash rapidly for 2 seconds indicating the factory calibration mode has been entered. Allow the IAMA to warm up for 5 minutes minimum and follow the manufacturer’s warm up procedure for the calibration source. The following list outlines conditions that are unique to factory recalibration: 4. Set the Input Range DIP switches to the desired input range according to 1. Unlike the field scaling procedures, there are no software under and over Table 3. range indications while performing a factory recalibration. Therefore, 5. Complete Steps 2.6 through 2.10 of Input Scaling Using Field care must be taken to insure the selected range extents are not exceeded. Configuration. Note: There will be no over or under range indication of the The minimum scale and full scale calibration values must be set to the LED’s during this procedure, so use care not to exceed the range extents. extents of the range being calibrated. 6. If an output is to be calibrated, continue from #2 of Output Recalibration For example: If the Input Range DIP switches are set for the 4-20 mA below. If no further input or output calibration is to be completed, return range, minimum scale must be set at 4 mA, and full scale must be set S1-1 and S1-2 to the down position and remove power from the IAMA. at 20 mA. Apply power and check for accurate operation of the newly calibrated range or ranges. 2. At least one input calibration must be completed before calibrating any output range. When calibrating the input voltage range, it is OUTPUT RECALIBRATION recommended that a range above 1 V be used to provide better accuracy. 1. Complete 1 through 5 of the input recalibration procedure for at least 3. If multiple input or output ranges are to be calibrated, DO NOT one range. REMOVE POWER TO CHANGE THE RANGE. Place the appropriate 2. For current output, set 20 mA/1 mA switch (S2) to desired full scale output. Field/Fact. DIP switch; S1-1 for outputs, and S1-2 for inputs to the down (20 mA - on; 1 mA - off) position, and set the remaining DIP switches for the range to be 3. Set Output Field/Fact. switch (S1 switch 1) to the off position. calibrated. Note: Be sure to change the terminal wiring to match the Input 4. Set the Output Range DIP switches to the desired output range according to or Output range DIP switch settings before performing the calibration Table 2. procedure. Set calibration source to 0 V or 0 mA before changing wiring. 5. Complete Steps 4.10 through 4.14 of Output Scaling Using Field Configuration. Note: There will be no over or under range indication of the LED’s during this procedure, so use care not to exceed the range extents. 6. If no further calibration is to be completed, return S1-1 and S1-2 to the down position and remove power from the IAMA. Apply power and check for accurate operation of the newly calibrated range or ranges. TROUBLESHOOTING For further technical assistance, contact technical support at the appropriate company numbers listed. INSTALLATION The unit is equipped with a universal mounting foot for attachment to standard DIN style mounting rails, including G profile rail according to EN50035 - G32 , and top hat (T) profile rail according to EN50022 - 35 x 7.5 and 35 x 15. The unit should be installed in a location that does not exceed the maximum operating temperature and provides good air circulation. Placing the unit near devices that generate excessive heat should be avoided. T Rail Installation G Rail Installation To install the IAMA on a “T” To install the IAMA on a “G” style rail, angle the module so style DIN rail, angle the module that the top groove of the “foot” so that the upper groove of the is located over the lip of the top “foot” catches under the lip of the rail. Push the module toward the top rail. Push the module toward rail until it snaps into place. To the rail until it snaps into place. remove a module from the rail, To remove a module from the insert a screwdriver into the slot rail, push up on the bottom of the on the bottom of the “foot”, and module while pulling out and pry upwards on the module until away from the rail. it releases from the rail. 7 APPLICATION Cost efficiency measurements of a printing company included the reduction of bulk stock of the various inks used in their printing processes. The company currently had various ink flow and level devices with different current and voltage outputs and wanted to record these measurements into a control room PC. Several IAMA Universal Signal Conditioning Modules were the answer. The IAMA’s universal input allowed for easy signal conditioning of the various output signals to the required PC’s Bus Board 0 to 10 VDC input signal. The factory calibration settings of the IAMA could be used with the devices in which the flow and level pressure was linear to the signal. The IAMA could also be scaled utilizing the field calibration method with the devices where pressure affected the signal slope specifications. In this case, the IAMA’s re-transmitted 0 to 10 VDC output was field calibrated, negating the expense and time required to rewrite the PC’s software parameters. In addition to accepting multiple signal types and field calibration features, the IAMA also provides the necessary electrical isolation between the control room PC and the hazards of the printing floor electrical noise. LIMITED WARRANTY The Company warrants the products it manufactures against defects in materials and workmanship for a period limited to two years from the date of shipment, provided the products have been stored, handled, installed, and used under proper conditions. The Company’s liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The Company’s option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products. The customer agrees to hold Red Lion Controls harmless from, defend, and indemnify RLC against damages, claims, and expenses arising out of subsequent sales of RLC products or products containing components manufactured by RLC and based upon personal injuries, deaths, property damage, lost profits, and other matters which Buyer, its employees, or sub-contractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (P.L. 93-637), as now in effect or as amended hereafter. No warranties expressed or implied are created with respect to The Company’s products except those expressly contained herein. The Customer acknowledges the disclaimers and limitations contained herein and relies on no other warranties or affirmations. Red Lion Controls AP Red Lion Controls Red Lion Controls BV 31, Kaki Bukit Road 3, 20 Willow Springs Circle Printerweg 10 #06-04/05 TechLink York PA 17406 NL - 3821 AD Amersfoort Singapore 417818 Tel +1 (717) 767-6511 Tel +31 (0) 334 723 225 Tel +65 6744-6613 Fax +1 (717) 764-0839 Fax +31 (0) 334 893 793 Fax +65 6743-3360

Frequently asked questions

What makes Elite.Parts unique?

chervon down
At GID Industrial (Elite.Parts' parent company), we specialize in procuring industrial parts. We know where to find the rare and obsolete equipment that our customers need in order to get back to business. There are other companies who claim to do what we do, but we're confident that our commitment to quality and value is unparalleled in our field.

What kind of warranty will the IAMA3535 have?

chervon down
Warranties differ by part and by which suppliers we use to procure it for you. Sometimes, a part will be sold as-is and without a warranty. Our specialty, single board computers, tend to receive a one-year warranty.

Which carriers does Elite.Parts work with?

chervon down
Elite.Parts can ship via FedEx, UPS, DHL, and USPS. We have accounts with each of them and generally ship using one of those, but we can also ship using your account if you would prefer. However, we can use other carriers if it will be more convenient for you.

Will Elite.Parts sell to me even though I live outside the USA?

chervon down
Absolutely! We are happy to serve customers regardless of location. We work with international clients all the time, and we are familiar with shipping to destinations all across the globe.

I have a preferred payment method. Will Elite.Parts accept it?

chervon down
All major credit cards are accepted: Visa, MasterCard, Discover, and American Express. We will also accept payment made with wire transfer or PayPal. Checks will only be accepted from customers in the USA. Terms may available for larger orders, upon approval.

Why buy from GID?

quality

Quality

We are industry veterans who take pride in our work

protection

Protection

Avoid the dangers of risky trading in the gray market

access

Access

Our network of suppliers is ready and at your disposal

savings

Savings

Maintain legacy systems to prevent costly downtime

speed

Speed

Time is of the essence, and we are respectful of yours

What they say about us

FANTASTIC RESOURCE

star star star star star

One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!

Bucher Emhart Glass

EXCELLENT SERVICE

star star star star star

With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.

Fuji

HARD TO FIND A BETTER PROVIDER

star star star star star

Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.

Applied Materials

CONSISTENTLY DELIVERS QUALITY SOLUTIONS

star star star star star

Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.

Nidec Vamco

TERRIFIC RESOURCE

star star star star star

This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.

Trican Well Service

GO TO SOURCE

star star star star star

When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.

ConAgra Foods

Related Products

ANALOG 3 PHASE FAULT DETECTOR W/RELAY 4

3PRESET, REFLECTIVE, NPN OC, RLY

3PRESET, BACKLIT, NPN OC, RLY

Counter; Dual Preset; 85 VAC to 250 VAC/11 VDC to 14 VDC; Relay; 6; 50/60 Hz

Counter, LCD, Backlit, 2 Preset,

Counter; Din; 85 to 250 VAC; Relay; LCD; 6; Screw Terminal; 50/60 Hz; EEPROM