MILLTRONICS 7ML12011EF00
Specifications
Beam angle
12°
Max. power consumption
0.75 W (25 mA at 24 V DC)
Measuring range
0.25 to 5 m (0.8 to 16.4 ft)
Metallic mounting
-20 to +60 °C (-4 to +140 °F)
Relay
No
Standard
-40 to +60 °C (-40 to +140 °F)
Supply voltage
12 to 28 V DC, 0.1 A surge
With flange adapter
1.7 kg (3.7 lbs)
Without flange adapter
1.5 kg (3.3 lbs)
Features
- Accurate and reliable
- Easy to install, program and maintain
- Integral temperature compensation
- Patented Sonic Intelligence echo processing
- Sanitary models available
Datasheet
Extracted Text
Level instruments Continuous level measurement - Ultrasonic transmitters The Probe ■ Overview ■ Configuration Parabolic Mounting The Probe is a short-range integrated ultrasonic level transmitter, ideal for liquids and slurries in open or closed vessels. ■ Benefits 5 Flat Mounting and Beam Angle Easy to install, program and maintain Accurate and reliable Sanitary models available fill ® Patented Sonic Intelligence echo processing Integral temperature compensation ■ Application The transducer is available in PVDF copolymer, making the de- vice suitable for use in a wide variety of applications. The Probe is easy to install and maintain, and can be quickly removed for pipe cleaning as required by the food, beverage and pharmaceutical industries. rungs The reliability of the level data is based on the Sonic Intelligence echo processing algorithms. A filter discriminates between the true echo and false echoes from acoustic or electrical noises seams and agitator blades in motion. The ultrasonic pulse propagation 12 time to the material and back is temperature-compensated and beam angle converted into distance for display, analog output and relay ac- tuation. Key Applications: chemical storage vessels, filter beds, mud pits, liquid storage vessels, food applications The Probe mounting Siemens FI 01 · 2010 5/126 Level instruments Continuous level measurement - Ultrasonic transmitters The Probe Order No. ■ Technical specifications Selection and Ordering data C) The Probe 7 M L 1 2 0 1 - Three-wire version Two-wire version Short-range integrated ultrasonic level transmitter, 777 0 0 (standard) ideal for liquids and slurries in open or closed ves- Mode of operation sels Measuring principle Ultrasonic level Ultrasonic level Measuring range measurement measurement 5 m (16.40 ft) 1 Input Transducer/Process connection PVDF copolymer, 2" NPT [(Taper), ANSI/ASME E Measuring range 0.25 to 5 m 0.25 to 5 m B1.20.1] (0.8 to 16.4 ft) (0.8 to 16.4 ft) PVDF copolymer, R 2" [(BSPT), EN 10226] F Output PVDF copolymer, G 2" [(BSPP), EN ISO 228-1] G mA 4 to 20 mA 4 to 20 mA PVDF copolymer, 4" Sanitary mounting J - Span Proportional/ Proportional/ Model/Approval inversely proportional inversely proportional 3 Wire, 24 V DC, CE, C-TICK, CSA, FM E 2 Wire, 24 V DC, CE, C-TICK, CSA F - Max. load 750 at 24 V DC 600 in the loop at 24 V DC Further designs Order code Relay For level alarm or No Please add "-Z" to Order No. and specify Order fault code(s). Acrylic coated, stainless steel tag [13 x 45 mm Y17 Power supply (0.5 x 1.75")]: Measuring-point number/identifica- Supply voltage 18 to 30 V DC, 12 to 28 V DC, tion (max. 20 characters) specify in plain text max. 0.2 A 0.1 A surge Additional Operating Instructions Max. power 5 W 0.75 W C) 3 Wire, 24 V model, Multi-language manual 7ML1998-5GD61 5 consumption (200 mA at 24 V DC) (25 mA at 24 V DC) C) 2 Wire model, Multi-language manual 7ML1998-5GC62 This device is shipped with the Siemens Milltronics Certificates and CE, C-TICK, CE, C-TICK, CSA US/C manual CD containing Quick Starts and Operating approvals CSA , FM US/C Instructions. Accuracy Accessories Error in measurement 0.25 % of measuring range (in air) Universal Box Bracket Mounting kit 7ML1830-1BK Sanitary 4" mounting clamp 7ML1830-1BR Resolution 3 mm (0.125") C) Power Supply, 24 V DC, 200 mA for 2 probes 7ML1930-1AA Temperature compen- Built in (105 to 125 V AC input) sation Power Supply, 24 V DC, 100 mA for 1 probe C) 7ML1930-1AB (105 to 125 V AC input) Echo processing Sonic Intelligence 3" ASME, DN 65 PN 10, JIS 10K 3B ETFE Flange 7ML1830-1BT Rated operation condi- adapter for 2" NPT tions 3" ASME, DN 65 PN 10, JIS 10K 3B ETFE Flange 7ML1830-1BU Beam angle 12° adapter for 2" BSPT 2" NPT locknut, plastic 7ML1830-1DTAmbient temperature 2" BSPT locknut, plastic 7ML1830-1DQ - Standard -40 to +60 °C (-40 to +140 °F) Plastic M20 cable gland with metal locknut 7ML1930-1DB SITRANS RD100 Remote display - - Metallic mounting -20 to +60 °C (-4 to +140 °F) see RD100 on page 5/304 Max. static operating Normal atmospheric pressure SITRANS RD200 Remote display - pressure see RD200 on page 5/306 Degree of protection IP65 C) Subject to export regulations AL: N, ECCN: EAR99 Design Weight - Without flange 1.5 kg (3.3 lbs) adapter - With flange adapter 1.7 kg (3.7 lbs) Material - Electronics enclosure PVC - Transducer PVDF copolymer Degree of protection IP65 Process connection 2" NPT [(Taper), ANSI/ASME B1.20.1] R 2" [(BSPT), EN 10226] or G 2" [(BSPP), EN ISO 228-1] Flange adapter 3" Universal, (fits DN 65, PN 10 and 3" ASME) 4" sanitary Cable inlet 2 inlets for PG 13.5 or ½" NPT cable glands Siemens FI 01 · 2010 5/127 Level instruments Continuous level measurement - Ultrasonic transmitters The Probe ■ Options ■ Dimensional drawings Flange adapter for mating 2” NPT or 2” BSP process connections to 3” ANSI, DN 65 PN10, and JIS 10K 3B flanges 148.8 mm (5.86”) bolt hole circle diameter THE PR OBE 190.2 mm (7.49”) diameter The Probe Optional Flange Adapter 5 The Probe with Optional Mounting Bracket ■ Schematics The Probe dimensions The Probe connections Siemens FI 01 · 2010 5/128 Level instruments Continuous level measurement - Ultrasonic transmitters SITRANS Probe LU ■ Overview ■ Configuration SITRANS Probe LU is a 2-wire loop powered ultrasonic transmit- ter for level, volume and flow monitoring of liquids in open chan- nels, storage vessels and simple process vessels. 5 ■ Benefits Continuous level measurement up to 12 m (40 ft) range Easy installation and simple start-up Programming using infrared Intrinsically Safe handheld ® programmer, SIMATIC PDM or HART Communicator Communication using HART or PROFIBUS PA ETFE or PVDF transducers for chemical compatibility Patented Sonic Intelligence signal processing Extremely high signal-to-noise ratio Auto False-Echo Suppression for fixed obstruction avoidance Level to volume or level to flow conversion ■ Application The SITRANS Probe LU is ideal for level monitoring in the water and wastewater industry and chemical storage vessels. The range of SITRANS Probe LU is 6 or 12 m (20 or 40 ft). Using Auto False-Echo Suppression for fixed obstruction avoidance, as well as an improved signal-to-noise ratio and improved accu- racy of 0.15% of range or 6 mm (0.25"), the Probe LU provides unmatched reliability. SITRANS Probe LU mounting ® SITRANS Probe LU includes Sonic Intelligence signal process- ing from the field-proven Probe and incorporates new echo pro- cessing features and the latest micro-processor and communi- cations technology. The Probe LU offers two communications options: HART or PROFIBUS PA (Profile version 3.0, Class B). The transducer on the Probe LU is available as ETFE or PVDF to suit the chemical conditions of your application. As well, for ap- plications with varying material and process temperatures, the Probe LU incorporates an internal temperature sensor to com- pensate for temperature changes. Key Applications: chemical storage vessels, filter beds, liquid storage vessels Siemens FI 01 · 2010 5/129 Level instruments Continuous level measurement - Ultrasonic transmitters SITRANS Probe LU ■ Technical specifications Mode of operation Process connection Measuring principle Ultrasonic level measurementThreaded connection 2" NPT [(Taper), ANSI/ASME B1.20.1] Typical application Level measurement in storage R 2" [(BSPT), EN 10226] or vessels and simple process vessels G 2" [(BSPP), EN ISO 228-1] InputsFlange connection 3" (80 mm) universal flange Measuring rangeOther connection FMS 200 mounting bracket (see page 5/185) or customer 6 m (20 ft) model 0.25 to 6 m (10" to 20 ft) supplied mount 12 m (40 ft) model 0.25 to 12 m (10" to 40 ft) Display and Controls Frequency 54 kHz Interface Local: LCD display with bar Outputs graph ® Remote: Available via HART or mA/HART PROFIBUS PA Range 4 to 20 mA Configuration Using Siemens SIMATIC PDM Accuracy 0.02 mA (PC) or HART handheld communicator or Siemens infra- PROFIBUS PA Profile 3, Class B red handheld programmer Performance Memory Non-volatile EEPROM Resolution 3 mm (0.12") Power supply Accuracy the greater of 0.15 % of range 4 to 20 mA/HART Nominal 24 V DC with 550 or 6 mm (0.24") 5 maximum; maximum 30 V DC 4 to Repeatability 3 mm (0.12") 20 mA Blanking distance 0.25 m (10") PROFIBUS PA 12, 13, 15, or 20 mA depending on programming (General Pur- Update time 5 seconds pose or Intrinsically Safe version) 4/20 mA/HART version 5 seconds at 4 mA per IEC 61158-2 PROFIBUS version 4 seconds at 15 mA current Certificates and Approvals loop General CSA , FM, CE, C-TICK US/C Temperature compensation Built-in to compensate over temperature range Marine (only applies to HART com-Lloyd’s Register of Shipping munication option) ABS Type Approval Beam angle 10° Hazardous Rated operating conditions Intrinsically Safe (Europe) ATEX II 1G EEx ia IIC T4Ambient conditions Intrinsically Safe (USA/Canada) CSA/FM (barrier required) T4, - Location Indoor/outdoor Class I, Div. 1, Groups A, B, C, D; - Ambient temperature -40 to +80 °C (-40 to +176 °F) Class II, Div. 1, Groups E, F, G; Class III - Relative humidity/ingress Suitable for outdoor protectionIntrinsically Safe (Australia/New ANZEx Ex ia IIC T4, Tamb = -40 to Zealand) +80 °C (-40 to +176 °F) IP67, - Installation category I IP68 - Pollution degree 4 Intrinsically Safe (International) IECEx TSA 04.0020X Ex ia IIC T4 Medium conditions Non-incendive (USA) FM (no barrier required) T5: Class - Temperature at flange or threads -40 to +85 °C (-40 to +185 °F) I, Div. 2, Groups A,B,C, D - Pressure (vessel) 0.5 bar g (7.25 psi g) Handheld Programmer DesignIntrinsically Safe Siemens hand- Infrared receiver held programmer Material (enclosure) PBT (Polybutylene Terephthalate) - Approvals for handheld IS model with ATEX EEx ia IIC T4 Degree of protection Type 4X/NEMA 4X, Type 6/ programmer NEMA 6/IP67/IP68 enclosure CSA/FM Class I, Div. 1, Groups A, B, C, D Weight 2.1 kg (4.6 lbs) Ambient temperature -20 to +40 °C (-5 to +104 °F) Cable inlet 2 x M20x1.5 cable gland or 2 x ½" Interface Proprietary infrared pulse signal NPT thread Power 3 V lithium battery Material (transducer) ETFE (Ethylene Tetrafluoroethyl- ene) or PVDF (Polyvinylidene (non-replaceable) Fluoride) Siemens FI 01 · 2010 5/130 Level instruments Continuous level measurement - Ultrasonic transmitters SITRANS Probe LU Selection and Ordering data Order No. Selection and Ordering data Order No. C) C) SITRANS Probe LU 7 M L 5 2 2 1 - SITRANS Probe LU 7 M L 5 2 2 1 - 2-wire, loop powered ultrasonic transmitter for 77777 2-wire, loop powered ultrasonic transmitter for 77777 level, volume and flow monitoring of liquids in open level, volume and flow monitoring of liquids in open channels, storage vessels and simple process ves- channels, storage vessels and simple process ves- sels. sels. C) Enclosure/Cable Inlet Additional Multi-language Quick Start manual 7ML1998-5QR81 Plastic (PBT), 2 x M20x1.5 (check Approvals for 1 cable gland details) This device is shipped with the Siemens Milltronics Plastic (PBT), 2 x ½" NPT (no cable glands sup- 2 manual CD containing the complete ATEX Quick plied) Start and Operating Instructions library. Operating Instructions for PROFIBUS PA device Range/Transducer material C) 6 meter (20 ft), ETFE A English 7ML1998-5JB02 C) 6 meter (20 ft), PVDF Copolymer B German 7ML1998-5JB32 Note: The Operating Instructions should be 12 meter (40 ft), ETFE C ordered as a separate item on the order. 12 meter (40 ft), PVDF Copolymer D Additional Multi-language Quick Start manual C) 7ML1998-5QV81 Process connection This device is shipped with the Siemens Milltronics 2" NPT [(Taper), ANSI/ASME B1.20.1] A manual CD containing the complete ATEX Quick R 2" [(BSPT), EN 10226] B Start and Operating Instructions library. G 2" [(BSPP), EN ISO 228-1] C Optional equipment Communication/Output ® Handheld programmer, Intrinsically Safe, EEx ia 7ML5830-2AH 4 to 20 mA, HART 1 PROFIBUS PA 2 Handheld programmer, General Purpose approvals 7ML1830-2AN Approvals Handheld programmer, Infrared, Intrinsically Safe, 7ML5830-2AJ General Purpose, FM, CSA, CE, C-TICK 1 PROFIBUS PA 5 Intrinsically Safe, FM Class I, Div. 1, Groups A, B, 2 D) HART modem/RS-232 7MF4997-1DA C, D (barrier required); Class II, Div. 1, Groups E, F, (for use with PC and SIMATIC PDM) G; Class III; ATEX II 1G EEx ia IIC T4, ANZEx, D) HART modem/USB 7MF4997-1DB IECEx (HART model only) (for use with a PC and Intrinsically Safe, CSA Class I, Div. 1, Groups A, B, 3 SIMATIC PDM) C, D (barrier required); Class II, Div. 1, Group G; 2" NPT locknut, plastic 7ML1830-1DT Class III (HART model only) 2" BSPT locknut, plastic 7ML1830-1DQ FM, Class l, Div. 2 (Enclosure option 2 only) 4 3" ASME, DN 65 PN 10, JIS 10K 3B ETFE Flange 7ML1830-1BT Intrinsically Safe, CSA/FM Class I, Div. 1, Groups A, 5 adapter for 2" NPT B, C, D (barrier required); Class II, Div. 1, Groups E, F, G; Class III (PROFIBUS PA model only) 3" ASME, DN 65 PN 10, JIS 10K 3B ETFE Flange 7ML1830-1BU Intrinsically Safe, ATEX II 1G EEx ia IIC T4 6 adapter for 2" BSPT (PROFIBUS PA model only) One General Purpose polymeric cable gland 7ML1930-1AM M20x1.5, rated for -20 to +80 °C (-4 to +176 °F) Further designs Order code One metallic cable gland M20x1.5, rated -40 to 7ML1930-1AP Please add "-Z" to Order No. and specify Order +80 °C (-40 to +176 °F) for General Purpose or code(s). ATEX EEx e installations (available for HART only) Stainless steel tag [69 x 50 mm (2.71 x 1.97")]: Y15 One metallic cable gland M20x1.5, rated -40 to 7ML1930-1AQ Measuring-point number/identification (max. 16 +80 °C (-40 to +176 °F) with integrated shield con- characters) specify in plain text nection (available for PROFIBUS PA) SITRANS RD100 Remote display - Operating Instructions for HART/mA device Order No. see RD100 on page 5/304 English C) 7ML1998-5HT02 SITRANS RD200 Remote display - C) French 7ML1998-5HT11 see RD200 on page 5/306 C) German 7ML1998-5HT32 Note: The Operating Instructions should be Spare Parts ordered as a separate item on the order. Plastic lid 7ML1830-1KB C) Subject to export regulations AL: N, ECCN: EAR99 D) Subject to export regulations AL: N, ECCN: EAR99H ■ Options Flange adapter for mating 2” NPT or 2” BSP process connections to 3” ANSI, DN 65 PN10, and JIS 10K 3B flanges 148.8 mm (5.86”) bolt hole circle diameter 190.2 mm (7.49”) diameter SITRANS Probe LU optional flange adapter SITRANS Probe LU with optional mounting bracket Siemens FI 01 · 2010 5/131 Level instruments Continuous level measurement - Ultrasonic transmitters SITRANS Probe LU ■ Dimensional drawings 5 SITRANS Probe LU dimensions ■ Schematics SITRANS Probe LU connections Siemens FI 01 · 2010 5/132
Frequently asked questions
What makes Elite.Parts unique?

What kind of warranty will the 7ML12011EF00 have?

Which carriers does Elite.Parts work with?

Will Elite.Parts sell to me even though I live outside the USA?

I have a preferred payment method. Will Elite.Parts accept it?

Why buy from GID?

Quality
We are industry veterans who take pride in our work

Protection
Avoid the dangers of risky trading in the gray market

Access
Our network of suppliers is ready and at your disposal

Savings
Maintain legacy systems to prevent costly downtime

Speed
Time is of the essence, and we are respectful of yours
What they say about us
FANTASTIC RESOURCE
One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!
Bucher Emhart Glass
EXCELLENT SERVICE
With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.
Fuji
HARD TO FIND A BETTER PROVIDER
Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.
Applied Materials
CONSISTENTLY DELIVERS QUALITY SOLUTIONS
Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.
Nidec Vamco
TERRIFIC RESOURCE
This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.
Trican Well Service
GO TO SOURCE
When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.
ConAgra Foods