DELTA VFD007S11B
Specifications
AC Line Regenerative
No
Amps (CT)
1 Amps
Braking Type
DC Injection;Dynamic Braking
Closed Loop
No
Dynamic Braking Trans
Included
Enclosure Rating
IP20
HP (CT)
1 Horsepower
Input Phase
1
Input Range VAC
100 to 120 Volts AC
Max. Frequency
400 Hertz
Motor Control-Max Level
V/Hz (Scalar)
Nominal Input VAC
120 Volts AC
Operator Controls
Built In
Features
- 0.5 to 3 HP
- 120 to 480 Volt Models 1 & 3 Phase
- General Purpose Micro Drive
- IP20
- V/Hz
Datasheet
Extracted Text
Preface
Thank you for choosing DELTA’s high-performance VFD-S Series. The VFD-S Series is
manufactured with high-quality components and materials and incorporate the latest microprocessor
technology available.
This manual is to be used for the installation, parameter setting, troubleshooting, and daily
maintenance of the AC motor drive. To guarantee safe operation of the equipment, read the following
safety guidelines before connecting power to the AC motor drive. Keep this operating manual at
hand and distribute to all users for reference.
To ensure the safety of operators and equipment, only qualified personnel familiar with AC motor
drive are to do installation, start-up and maintenance. Always read this manual thoroughly before
using VFD-S series AC Motor Drive, especially the WARNING, DANGER and CAUTION notes.
Failure to comply may result in personal injury and equipment damage. If you have any questions,
please contact your dealer.
PLEASE READ PRIOR TO INSTALLATION FOR SAFETY.
DANGER!
1. AC input power must be disconnected before any wiring to the AC motor drive is made.
2. A charge may still remain in the DC-link capacitors with hazardous voltages, even if the power
has been turned off. To prevent personal injury, please ensure that power has been turned off
before opening the AC motor drive and wait ten minutes for the capacitors to discharge to safe
voltage levels.
3. Never reassemble internal components or wiring.
4. The AC motor drive may be destroyed beyond repair if incorrect cables are connected to the
input/output terminals. Never connect the AC motor drive output terminals U/T1, V/T2, and W/T3
directly to the AC mains circuit power supply.
5. Ground the VFD-S using the ground terminal. The grounding method must comply with the laws
of the country where the AC motor drive is to be installed. Refer to the Basic Wiring Diagram.
6. VFD-S series is used only to control variable speed of 3-phase induction motors, NOT for 1-
phase motors or other purpose.
7. VFD-S series shall NOT be used for life support equipment or any life safety situation.
WARNING!
1. DO NOT use Hi-pot test for internal components. The semi-conductor used in the AC motor
drive is easily damaged by high-pressure.
2. There are highly sensitive MOS components on the printed circuit boards. These components
are especially sensitive to static electricity. To prevent damage to these components, do not
touch these components or the circuit boards with metal objects or your bare hands.
3. Only qualified personnel are allowed to install, wire and maintain AC motor drive.
CAUTION!
1. Some parameter settings will cause the motor to run immediately after applying power.
2. DO NOT install the AC motor drive in a place subjected to high temperature, direct sunlight,
high humidity, excessive vibration, corrosive gases or liquids, or airborne dust or metallic
particles.
3. Only use AC motor drives within specification. Failure to comply may result in fire, explosion or
electric shock.
4. To prevent personal injury, please keep children and unqualified people away from the
equipment.
5. When the motor cable between the AC motor drive and motor is too long, the layer insulation of
the motor may be damaged. Please use a frequency inverter duty motor or add an AC output
reactor to prevent damage to the motor. Refer to appendix B Reactor for details.
6. The rated voltage for the AC motor drive must be ≤ 240V (≤ 480V for 460V models) and the
mains supply current capacity must be ≤ 5000A RMS (≤10000A RMS for the ≥ 40hp (30kW)
models).
Table of Contents
Preface ..............................................................................................................i
Table of Contents ...........................................................................................iii
Chapter 1 Introduction.................................................................................1-1
1.1 Receiving and Inspection.................................................................... 1-1
1.1.1 Nameplate Information................................................................ 1-1
1.1.2 Model Explanation ...................................................................... 1-1
1.1.3 Series Number Explanation ........................................................ 1-2
1.1.4 Drive Frames .............................................................................. 1-2
1.2 Appearances....................................................................................... 1-2
1.3 Installation Steps ................................................................................ 1-3
1.4 Storage ............................................................................................... 1-4
Chapter 2 Installation and Wiring ...............................................................2-1
2.1 Ambient Conditions............................................................................. 2-1
2.2 Installation........................................................................................... 2-1
2.3 Dimensions......................................................................................... 2-3
2.4 Wiring ............................................................................................... 2-16
2.4.1 Basic Wiring.............................................................................. 2-17
2.4.2 External Wiring.......................................................................... 2-21
2.4.3 Main Terminals Connections .................................................... 2-22
2.4.4 Control Terminals...................................................................... 2-24
2.4.5 Main Circuit Terminals .............................................................. 2-28
Chapter 3 Start Up........................................................................................3-1
3.1 Preparations before Start-up............................................................... 3-1
3.2 Operation Method............................................................................... 3-2
3.3 Trial Run ............................................................................................. 3-2
Chapter 4 Digital Keypad Operation ...........................................................4-1
4.1 Description of the Digital Keypad........................................................ 4-1
4.2 Explanation of LED Indicators............................................................. 4-1
4.3 Explanations of Display Messages ..................................................... 4-1
4.4 How to Operate the Digital Keypad..................................................... 4-3
Chapter 5 Parameters ..................................................................................5-1
5.1 Summary of Parameter Settings......................................................... 5-2
5.2 Parameter Settings for Applications.................................................. 5-12
5.3 Description of Parameter Settings .................................................... 5-17
Chapter 6 Fault Code Information...............................................................6-1
6.1 Common Problems and Solutions ...................................................... 6-1
6.2 Reset .................................................................................................. 6-4
Chapter 7 Troubleshooting..........................................................................7-1
7.1 Over Current (OC) .............................................................................. 7-1
7.2 Ground Fault....................................................................................... 7-2
7.3 Over Voltage (OV) .............................................................................. 7-2
7.4 Low Voltage (Lv)................................................................................. 7-3
7.5 Over Heat (OH)................................................................................... 7-4
7.6 Overload ............................................................................................. 7-4
7.7 Keypad Display is Abnormal............................................................... 7-5
7.8 Phase Loss (PHL)............................................................................... 7-5
7.9 Motor cannot Run ............................................................................... 7-6
7.10 Motor Speed cannot be Changed..................................................... 7-7
7.11 Motor Stalls during Acceleration ....................................................... 7-8
7.12 The Motor does not Run as Expected .............................................. 7-8
7.13 Electromagnetic/Induction Noise ...................................................... 7-9
7.14 Environmental Condition................................................................... 7-9
7.15 Affecting Other Machines ............................................................... 7-10
Chapter 8 Maintenance and Inspections....................................................8-1
Appendix A Specifications ......................................................................... A-1
Appendix B Accessories ............................................................................B-1
B.1 All Brake Resistors & Brake Units Used in AC Motor Drives..............B-1
B.1.1 Dimensions and Weights for Brake resistors..............................B-2
B.2 EMI Filters ..........................................................................................B-3
B.2.1 Dimensions.................................................................................B-6
B.3 AC Reactor.......................................................................................B-10
B.3.1 AC Input Reactor Recommended Value...................................B-10
B.3.2 AC Output Reactor Recommended Value................................B-11
B.3.3 Applications for AC Reactor .....................................................B-11
B.4 DC Choke Recommended Values....................................................B-15
B.5 Zero Phase Reactor (RF220X00A) ..................................................B-16
B.6 Din Rail-DR01 ..................................................................................B-17
B.7 Remote Controller RC-01.................................................................B-18
B.8 Conduit Bracket (BK-S) ....................................................................B-19
B.9 Non-fuse Circuit Breaker Chart ........................................................B-20
Appendix C How to Select the Right AC Motor Drive............................... C-1
C.1 Capacity Formulas .............................................................................C-2
C.2 General Precautions ..........................................................................C-4
C.3 How to Choose a Suitable Motor........................................................C-5
Appendix D CE ............................................................................................D-1
Chapter 1 Introduction
1.1 Receiving and Inspection
This VFD-S AC motor drive has gone through rigorous quality control tests at the factory before
shipment. After receiving the AC motor drive, please check for the following:
� Check to make sure that the package includes an AC motor drive, the User
Manual/Quick Start and CD, dust covers and rubber bushings.
� Inspect the unit to assure it was not damaged during shipment.
� Make sure that the part number indicated on the nameplate corresponds with the part
number of your order.
1.1.1 Nameplate Information
Example for 1HP/0.75kW 3-phase 230V AC motor drive
AC Drive Model
MODEL : VFD007S23A
Input Spec.
INPUT : 3PH 200-240V 50/60Hz 5.1A
Output Spec.
OUTPUT : 3PH 0-240V 4.2A 1.6kVA 0.75kW/1HP
Output Frequency Range Frequency Range : 1-400Hz
Serial Number & Bar Code
007S23A0T7010001
DELTA ELECTRONICS INC. MADE IN XXXXX
1.1.2 Model Explanation
VFD 007 S 23 A
Version Type
Input Voltage
11:Single phase 115V
21:Single phase 230V
23:Three phase 230V
43:Three phase 460V
S Series
Applicable motor capacity
002: 0.25HP(0.2kW)
004: 0.5HP(0.4kW)
007: 1 HP(0.7kW)
022: 3 HP(2.2kW)
Series Name
Revision August 2006, SE08, SW V2.61 1-1
Chapter 1 Introduction|VFD-S Series
1.1.3 Series Number Explanation
007S23A 0T 6 01
Production number
Production week
Production year 2006
Production factory
(Taoyuan)
230V 3-phase 1HP(0.75kW)
Model
If the nameplate information does not correspond to your purchase order or if there are
any problems, please contact your distributor.
1.1.4 Drive Frames
Frame Power range Models
VFD002S11A/11B/21A/21B/21E/23A,
0.25-2hp
S1 VFD004S11A/11B/21A/21B/21E/23A/43A/43B/43E,
(0.2-1.5kW)
VFD007S21A/21B/21E/23A/43A/43B/43E, VFD015S23D
1-5hp VFD007S11A/11B, VFD015S21D/21E/21U/43D/43E/43U,
S2
(0.75-3.7kW) VFD022S21D/21E/21U/23D/43D/43E/43U
Please refer to Chapter 2.3 for exact dimensions.
1.2 Appearances
VFD002S11A/11B/21A/21B/23A, Frame S1: VFD002S21E, VFD004S21E,
VFD004S11A/11B/21A/21B/23A/43A/43B/43E, VFD007S21E, VFD015S23D,
VFD007S21A/21B/23A/43A/43B/43E, Frame S2: VFD007S11A/11B,
VFD015S21D/21E/21U/43D/43E/43U,
VFD022S21D/21E/21U/23D/43D/43E/43U
1-2 Revision August 2006, SE08, SW V2.61
Chapter 1 Introduction|VFD-S Series
1.3 Installation Steps
KNOB
COVER
CASE
HEAT SINK
SCREW
DIVISION
PLATE
Installation Steps
1. Remove front cover screw and open.
2. Remove Division Plate. If using optional
conduit bracket, please refer to next
page.
3. Connect AC Input Power and motor leads.
Never connect the AC drive output
terminals U/T1, V/T2, W/T3 to main AC
Input power.
4. Reinstall Division Plate.
SCREW
SCREW
For Optional Conduit Bracket:
Make sure to fasten both screws on conduit
bracket as shown in the drawing for safety
grounding purpose. Bring all the wires out
through the conduit bracket.
Screw Torque: 5 to 6 kgf-cm (4.3 to 5.2 in-lbf)
CONDUIT
BRACKET
Revision August 2006, SE08, SW V2.61 1-3
Chapter 1 Introduction|VFD-S Series
SCREW
DIVISION
PLATE
Reinstall Division Plate.
Screw Torque: 5 to 6 kgf-cm (4.3 to 5.2 in-lbf)
CONDUIT
BRACKET
SCREW
SCREW
Install Conduit Bracket cover and tighten screws.
1.4 Storage
The AC motor drive should be kept in the shipping carton or crate before installation. In order to
retain the warranty coverage, the AC motor drive should be stored properly when it is not to be used
for an extended period of time. Storage conditions are:
Store in a clean and dry location free from direct sunlight or corrosive fumes.
° °
Store within an ambient temperature range of -20 C to +60 C.
Store within a relative humidity range of 0% to 90% and non-condensing environment.
Store within an air pressure range of 86kPa to 106kPa.
CAUTION!
1. DO NOT store in an area with rapid changes in temperature. It may cause condensation and
frost.
2. DO NOT place on the ground directly. It should be stored properly. Moreover, if the surrounding
environment is humid, you should put exsiccator in the package.
1-4 Revision August 2006, SE08, SW V2.61
Chapter 1 Introduction|VFD-S Series
3. If the AC motor drive is stored for more than 3 months, the temperature should not be higher
than 30 °C. Storage longer than one year is not recommended, it could result in the degradation
of the electrolytic capacitors.
4. When the AC motor drive is not used for a long time after installation on building sites or places
with humidity and dust, it’s best to move the AC motor drive to an environment as stated above.
Revision August 2006, SE08, SW V2.61 1-5
Chapter 1 Introduction|VFD-S Series
This page intentionally left blank.
1-6 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring
2.1 Ambient Conditions
Install the AC motor drive in an environment with the following conditions:
Operation Air Temperature: -10 ~ +50°C (14 ~ 122°F)
-10 ~ +40°C (14 ~ 104°F) for side-by-side
mounting
Relative Humidity: <90%, no condensation allowed
Atmosphere pressure: 86 ~ 106 kPa
Installation Site Altitude: <1000m
2
Vibration: <20Hz: 9.80 m/s (1G) max
2
20 ~ 50Hz: 5.88 m/s (0.6G) max
Storage Temperature: -20°C ~ +60°C (-4°F ~ 140°F)
Transportation Relative Humidity: <90%, no condensation allowed
Atmosphere pressure: 86 ~ 106 kPa
2
Vibration: <20Hz: 9.80 m/s (1G) max
2
20 ~ 50Hz: 5.88 m/s (0.6G) max
Pollution Degree 2: good for a factory type environment.
CAUTION!
1. Operating, storing or transporting the AC motor drive outside these conditions may cause
damage to the AC motor drive.
2. Failure to observe these precautions may void the warranty!
2.2 Installation
1. Mount the AC motor drive vertically on a flat vertical surface by using bolts or screws. Other
directions are not allowed.
2. The AC motor drive will generate heat during operation. Allow sufficient space around the unit
for heat dissipation.
3. The heat sink temperature may rise to 90°C when running. The material on which the AC motor
drive is mounted must be noncombustible and be able to withstand this high temperature.
4. When the AC motor drive is installed in a confined space (e.g. cabinet), the surrounding
temperature must be within 10 ~ 40°C with good ventilation. DO NOT install the AC motor drive
in a space with bad ventilation.
Revision August 2006, SE08, SW V2.61 2-1
50mm
(2inch)
50mm
(2inch)
Chapter 2 Installation and Wiring|VFD-S Series
5. When installing multiple AC motor drives in the same cabinet, they should be adjacent in a row
with enough space. When installing one AC motor drive below another one, use a metal
separation barrier between the AC motor drives to prevent mutual heating. Refer to figure below
for details.
6. Prevent fiber particles, scraps of paper, saw dust, metal particles, etc. from adhering to the
heatsink.
Mounting Clearances
150mm
(6inch)
Air Flow
150mm
(6inch)
2-2 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
2.3 Dimensions
(Dimensions are in millimeter and [inch])
Frame S1: VFD002S11A, VFD002S21A, VFD002S23A
85.0 [3.35] 5.8 [0.23] 88.0 [3.47]
13.0 [0.51]
74.0 [2.92]
5.0 [0.20]
5.0 [0.20]
Revision August 2006, SE08, SW V2.61 2-3
132.2 [5.21]
148.0 [5.83]
3.0 [0.12]
11.1 [0.44]
8.1 [0.32]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD002S11B, VFD002S21B
85 .0 [3 .3 5] 5.8 [0.23 ] 88 .0 [3 .4 7]
74 .0 [2 .9 2] 13 .0 [0 .5 1]
73 .0 [2 .8 8]
67 .8 [2 .6 7] 13 .0 [0 .5 1]
5.0 [0. 20 ]
5. 0 [0.20 ]
2-4 Revision August 2006, SE08, SW V2.61
13 2.2 [5.21]
5.83]
1 6.0 [ 0.63] 14 8.0 [
3.0 [0.12]
1 1.1 [ 0.44]
[0.32]
8.1
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD004S11A, VFD004S21A, VFD004S23A
85 .0 [3 .3 5] 5.8 [0.23 ] 10 2.0 [4.02]
74 .0 [2 .9 2] 2.8 [0.11 ]
5.0 [0.20 ]
5.0 [0.20 ]
Revision August 2006, SE08, SW V2.61 2-5
1 32.2 [5.21]
1 48.0 [5.83]
3.0 [ 0.12]
11.1 [0.44]
8.1 [0.32]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD004S11B, VFD004S21B
85 .0 [3 .3 5] 5. 8 [0. 23 ] 10 2. 0 [ 4. 02]
7 74 4 ..0 0 [2 [2 .9 .9 2 2]] 2. 8 [0.11 ]
73 .0 [2 .8 8]
67 .8 [2 .6 7] 27 .0 [1 .0 6]
5. 0 [0. 20 ]
5.0 [0.20 ]
2-6 Revision August 2006, SE08, SW V2.61
1 32.2 [5.21]
16.0 [0.63]
1 48.0 [5.83]
3.0 [0.12]
11.1 [0.44]
8.1 [ 0.32]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD007S21A, VFD007S23A
85 .0 [3 .3 5] 5. 8 [0.23 ] 12 4.0 [4. 89]
74 .0 [2 .9 2] 2. 8 [0.11 ]
5.0 [0. 20 ]
5.0 [0. 20 ]
Revision August 2006, SE08, SW V2.61 2-7
13 2.2 [ 5.21]
14 8.0 [ 5.83]
0 [0 .12]
3.
1 1.1 [ 0.44]
8.1 [ 0.32]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD007S21B
85 .0 [3 .3 5] 5.8 [0. 23 ] 12 4.0 [ 4.89]
7 74 4 .0 .0 [2 [2 .9 .9 2 2]]
2.8 [0. 11 ]
67 .8 [2 .6 7] 50 .0 [1 .9 7]
73 .0 [2 .8 8]
5.0 [0.20 ]
5.0 [0. 20 ]
2-8 Revision August 2006, SE08, SW V2.61
1 32.2 [5.21]
16.0 [0.63] 148.0 [5.83]
3. 0 [0.12]
11 .1 [0.44]
8.1 [0.32]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD004S43A, VFD004S43E, VFD007S43A, VFD007S43E
85 .0 [3 .3 5] 5. 8 [0. 23 ] 12 6. 0 [ 4. 96]
74 .0 [2 .9 2] 3.0 [0.12 ]
5. 0 [0. 20 ]
5. 0 [0. 20 ]
Revision August 2006, SE08, SW V2.61 2-9
13 2.2 [ 5.21]
14 8.0 [ 5.83]
3.0 [0 .12]
1 1.1 [ 0.44]
8.1 [0.32]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD004S43B, VFD007S43B
85 .0 [3 .3 5] 5.8 [0. 23 ] 12 6.0 [4.96]
74 .0 [2 .9 2]
3. 0 [0.12 ]
73 .0 [2 .8 8]
67 .8 [2 .6 7] 51 .0 [2 .0 1]
5. 0 [0.20 ]
5.0 [0.20 ]
2-10 Revision August 2006, SE08, SW V2.61
1 32.2 [5.21]
16.0 [0.63] 148.0 [5.83]
3. 0 [0.12]
11 .1 [0 .44]
8.1 [0 .32]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S1: VFD002S21E, VFD004S21E, VFD007S21E, VFD015S23D
85 .0 [3 .3 5] 5. 8 [ 0. 23 ] 12 7.0 [5.00]
74 .0 [2 .9 2] 8. 5 [ 0. 33 ]
5.0 [0.20 ]
Revision August 2006, SE08, SW V2.61 2-11
13 3.7 [ 5.27]
14 8.0 [ 5.83]
8.3 [ 0.33]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S2: VFD007S11A
10 0.0 [3. 94]
86 .5 [3 .4 1] 5. 4 [0.21 ] 12 9.0 [5. 08]
5. 5 [0. 22 ]
5. 5 [0.22 ]
2-12 Revision August 2006, SE08, SW V2.61
1 73.0 [6.81]
1 86.0 [7.33]
1 .0 [0 .04]
9 .5 [0 .38]
6.5 [ 0.26]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S2: VFD007S11B
10 0.0 [3.94]
86 .5 [3 .4 1] 5.4 [0.21 ] 12 9.0 [5.08]
73 .0 [2 .8 8] 67 .8 [2 .6 7] 53 .5 [2 .11]
5.5 [0. 22 ]
5. 5 [0. 22 ]
Revision August 2006, SE08, SW V2.61 2-13
173 .0 [6.82]
16 .0 [0 .63] 18 6.0 [7.33]
1.0 [0 .04]
9.5 [0 .38]
6.5 [0.26]
Chapter 2 Installation and Wiring|VFD-S Series
Frame S2: VFD015S21D, VFD015S21E, VFD015S43D, VFD015S43E, VFD022S21D,
VFD022S21E, VFD022S23D, VFD022S43D, VFD022S43E
10 0.0 [3.94] 5.4 [0.21 ] 12 9.3 [5.09]
86 .5 [3 .4 1] 8.5 [0.33 ]
5. 5 [0.22 ]
5.5 [0.22 ]
2-14 Revision August 2006, SE08, SW V2.61
17 3.0 [ 6.82]
18 6.0 [ 7.33]
1.0 [0.04]
9 .5 [0 .37]
]
6.5 [0.26
Chapter 2 Installation and Wiring|VFD-S Series
Frame S2: VFD015S21U, VFD015S43U, VFD022S21U, VFD022S43U
5.4 [0.21] 129.3 [5.09]
100.0 [3.94]
86.5 [3.41] 8.5 [0.33]
67.8 [2.67] 53.9 [2.12]
73.0 [2.88]
5.5 [0.22]
5.5 [0.22]
Revision August 2006, SE08, SW V2.61 2-15
173.0 [6.82]
16.0 [0.63] 186.0 [7.33]
1.0 [0.04]
9.5 [0.37]
6.5 [0.26]
Chapter 2 Installation and Wiring|VFD-S Series
2.4 Wiring
After removing the front cover, check if the power and control terminals are clear of debris. Be sure
to observe the following precautions when wiring.
General Wiring Information
�
Applicable Codes
All VFD-S series are Underwriters Laboratories, Inc. (UL) and Canadian Underwriters
Laboratories (cUL) listed, and therefore comply with the requirements of the National
Electrical Code (NEC) and the Canadian Electrical Code (CEC).
Installation intended to meet the UL and cUL requirements must follow the instructions
provided in “Wiring Notes” as a minimum standard. Follow all local codes that exceed UL
and cUL requirements. Refer to the technical data label affixed to the AC motor drive and
the motor nameplate for electrical data.
The "Line Fuse Specification" in Appendix B, lists the recommended fuse part number
for each S-Series part number. These fuses (or equivalent) must be used on all
installations where compliance with U.L. standards is a required.
2-16 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
2.4.1 Basic Wiring
� Make sure that power is only applied to the R/L1, S/L2, T/L3 terminals. Failure to comply
may result in damage to the equipment. The voltage and current should lie within the
range as indicated on the nameplate.
� Check the following items after completing the wiring:
1. Are all connections correct?
2. No loose wires?
3. No short-circuits between terminals or to ground?
A charge may still remain in the DC bus capacitors with hazardous voltages even if the
power has been turned off. To prevent personal injury, please ensure that the power is
turned off and wait ten minutes for the capacitors to discharge to safe voltage levels
before opening the AC motor drive.
DANGER!
1. All the units must be grounded directly to a common ground terminal to prevent electric shock,
fire and interference.
2. Only qualified personnel familiar with AC motor drives are allowed to perform installation, wiring
and commissioning.
3. Make sure that the power is off before doing any wiring to prevent electric shocks.
Basic Wiring Diagrams
Users must connect wires according to the circuit diagrams on the following pages. Do not plug a
modem or telephone line to the RS-485 communication port or permanent damage may result.
Terminals 1 & 2 are the power supply for the optional copy keypad only and should not be used for
RS-485 communication.
Revision August 2006, SE08, SW V2.61 2-17
Chapter 2 Installation and Wiring|VFD-S Series
For VFDXXXSXXA/B/D/U
Main Circuit Power
E
NFB
R/L1
R/L1
S/L2
S/L2
T/L3
T/L3
17V
SA
Recommended Circuit
RB Grounding resistance
when power supply
MC
less than 100
is turned OFF by a RC
ON
OFF
fault output
MC
17V
4.7k
17V
4.7k
17V
4.7k
17V
4.7k
17V
4.7k
17V
4.7k
47K
2-18 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
For VFDXXXSXXE
NPN (sink mode)
Braking resistor (optional)
Jumper
select 80ΩΩ 120W, 200 120W
400Ω 120W
Main Circuit Power
B2
+1 AC Motor
+2/B1
E
U/T1
NFB
R/L1 IM
R/L1
V/T2
S/L2
S/L2 +17V 3~
W/T3
T/L3
T/L3
Grounding resistance
SA CPU
E
less than 100Ω
Recommended Circuit
RB
when power supply
MC
Potentiometer(1KΩ)
is turned OFF by a RC 2.4Ω
47ΩAFM
ON
OFF
fault output
MC
Analog output
+
Factory default
47KΩ
DC 0~10V
17V
-
11V
Forward/Stop
M0
Factory default: indicate
Reverse/Stop
GND
M1
output frequency
Reset
M2
NPN
RA
Multi-function indication
Multi-step 1
PNP
output contacts below
M3
RB
120VAC/24VDC 5A
Multi-step 2 J2
M4
RC
Multi-step 3 Factory default:
M5
indicates malfunction
Comm. signal (sink)
GND
Mo1
Multi-function Photocoupler
E
output below 48VDC 50mA
+10V 10mA
Analog voltage
3
Factory default: Indicates
01 ~0VDC (MAX)
1
2 during operation
2 MCM
Potentiometer
Pot.
3K~Ω 5K
AVI
RJ-11
3 RJ-11 communication port with
Analog current 1 47KΩ
250Ω
RS-485 serial interface
1:17V
GND
61 ←
2:GND
Factory default: output freq. (Pot.)
3:SG-
determined by the Potentiometer
4:SG+
on the control panel.
Main circuit (power) terminals
Control circuit terminals Shielded leads
NOTE: Do not plug in a Modem or telephone line to the RS-485 communication
port, permanent damage may result. Terminal 1 & 2 are the power
sources for the optional copy keypad and should not be used while
using RS-485 communication.
* If it is single phase model, please select any of the two input power
terminals in main circuit power.
Revision August 2006, SE08, SW V2.61 2-19
Chapter 2 Installation and Wiring|VFD-S Series
For VFDXXXSXXE
PNP (source mode)
Braking resistor (optional)
Jumper
select 80ΩΩ 120W, 200 120W
400Ω 120W
Main Circuit Power
+1 +2/B1 B2
E
NFB
AC Motor
R/L1
R/L1
U/T1
S/L2
S/L2 IM
V/T2
T/L3
T/L3
+17V 3~
SA W/T3
Recommended Circuit
Grounding resistance
RB
when power supply
MC CPU
E
less than 100Ω
RC
is turned OFF by a
ON
OFF
fault output
MC
2.4Ω Potentiometer(1KΩ)
AFM
47Ω
Common signal (source)
Analog output
+
47KΩ
DC 0~10V
17V 20mA
-
11V
Forward/Stop
M0
Factory default: indicate
Reverse/Stop
GND
M1
output frequency
Reset
M2
NPN
RA
Multi-function indication
Multi-step 1
PNP output contacts below
M3
RB
120VAC/24VDC 5A
Multi-step 2 J2
M4
RC
Multi-step 3
Factory default:
M5
indicates malfunction
GND
Mo1
Multi-function Photocoupler
E
output below 48VDC 50mA
+10V 10mA
Analog voltage
3
Factory default: Indicates
01 ~0VDC (MAX)
1
2 MCM during operation
Potentiometer 2
Pot.
3K~Ω 5K
AVI
RJ-11
3 RJ-11 communication port with
1 47KΩ
Analog current
250Ω
RS-485 serial interface
1:17V
GND
61 ←
2:GND
Factory default: output freq. (Pot.)
3:SG-
determined by the Potentiometer
4:SG+
on the control panel.
Main circuit (power) terminals
Control circuit terminals Shielded leads
NOTE: Do not plug in a Modem or telephone line to the RS-485 communication
port, permanent damage may result. Terminal 1 & 2 are the power
sources for the optional copy keypad and should not be used while
using RS-485 communication.
* If it is single phase model, please select any of the two input power
terminals in main circuit power.
2-20 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
2.4.2 External Wiring
Power Supply
Items Explanations
Please follow the specific power
Power
supply requirements shown in
supply
FUSE/NFB
Appendix A.
There may be an inrush current
during power up. Please check the
Fuse/NFB
Magnetic chart of Appendix B and select the
(Optional)
contactor
correct fuse with rated current. Use of
an NFB is optional.
Please do not use a Magnetic
Magnetic
Input AC
contactor as the I/O switch of the AC
Line Reactor contactor
motor drive, as it will reduce the
(Optional)
operating life cycle of the AC drive.
Zero-phase
Reactor
Used to improve the input power
factor, to reduce harmonics and
provide protection from AC line
EMI Filter
disturbances. (surges, switching
Input AC
spikes, short interruptions, etc.). AC
Line Reactor
line reactor should be installed when
(Optional)
R/L1 S/L2 T/L3 the power supply capacity is 500kVA
DC
+1
Choke or more and exceeds 6 times the
+2/B1
inverter capacity, or the mains wiring
Braking
Resistor distance ≤ 10m.
B2
Zero phase reactors are used to
U/T1 V/T2 W/T3
reduce radio noise especially when
Zero-phase
audio equipment is installed near the
Reactor
inverter. Effective for noise reduction
Zero-phase
(Ferrite Core
Reactor
on both the input and output sides.
Common
Attenuation quality is good for a wide
Output AC Choke)
range from AM band to 10MHz.
Line Reactor
(Optional)
Appendix B specifies the zero phase
reactor. (RF220X00A)
To reduce electromagnetic
EMI filter
Motor
interference, please refer to Appendix
(Optional)
B for more details.
Used to reduce the deceleration time
Brake
of the motor. Please refer to the chart
resistor
in Appendix B for specific brake
(Optional)
resistors.
Motor surge voltage amplitude
Output AC
depends on motor cable length. For
Line Reactor
applications with long motor cable
(Optional)
(>20m), it is necessary to install a
reactor at the inverter output side.
Revision August 2006, SE08, SW V2.61 2-21
Chapter 2 Installation and Wiring|VFD-S Series
2.4.3 Main Terminals Connections
Terminal Symbol Explanation of Terminal Function
R/L1, S/L2, T/L3 AC line input terminals (3-phase)
L/L1, N/L2 AC line input terminals (1-phase)
AC drive output terminals for connecting 3-phase
U/T1, V/T2, W/T3
induction motor
+2/B1, B2 Connections for Brake resistor (optional)
+2/B1, +1 Connections for DC Link Reactor (optional)
Earth connection, please comply with local regulations.
Mains power terminals (R/L1, S/L2, T/L3 and L/L1, N/L2)
� Connect these terminals via a non-fuse breaker or earth leakage breaker to 3-phase AC
power (some models to 1-phase AC power) for circuit protection. It is unnecessary to
consider phase-sequence.
� It is recommended to add a magnetic contactor (MC) in the power input wiring to cut off
power quickly and reduce malfunction when activating the protection function of AC
motor drives. Both ends of the MC should have an R-C surge absorber.
� Do NOT run/stop AC motor drives by turning the power ON/OFF. Run/stop AC motor
drives by RUN/STOP command via control terminals or keypad. If you still need to
run/stop AC drives by turning power ON/OFF, it is recommended to do so only ONCE
per hour.
� Do NOT connect 3-phase models to a 1-phase power source.
Control circuit terminals (U/T1, V/T2, W/T3)
� When the AC drive output terminals U/T1, V/T2, and W/T3 are connected to the motor
terminals U/T1, V/T2, and W/T3, respectively, the motor will rotate counterclockwise (as
viewed on the shaft end of the motor) when a forward operation command is received.
To permanently reverse the direction of motor rotation, switch over any of the two motor
leads.
Forward
running
2-22 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
� DO NOT connect phase-compensation capacitors or surge absorbers at the output
terminals of AC motor drives.
� With long motor cables, high capacitive switching current peaks can cause over-current,
high leakage current or lower current readout accuracy. To prevent this, the motor cable
should be less than 20m for 3.7kW models and below. And the cable should be less than
50m for 5.5kW models and above. For longer motor cables use an AC output reactor.
� Use a well-insulated motor, suitable for inverter operation.
Terminals [+2/B1, +1] for connecting DC reactor
� This is the connector for the DC reactor to improve the power factor. Please remove the
short jumper when connecting DC reactor.
Terminals [+2/B1, B2] for connecting brake resistor
BR
+2/B1 B2
Connect a brake resistor in applications with frequent deceleration ramps, short
�
deceleration time, too low braking torque or requiring increased braking torque.
When not used, please leave the terminals [+2/B1, B2] open.
�
WARNING!
Short-circuiting [+2/B1, B2] can damage the AC motor drive.
Grounding terminals ( )
� Make sure that the leads are connected correctly and the AC drive is properly grounded.
Ω
(Ground resistance should not exceed 0.1 .)
� Use ground leads that comply with local regulations and keep them as short as possible.
� Multiple VFD-S units can be installed in one location. All the units should be grounded
directly to a common ground terminal, as shown in the figure below. Ensure there are
no ground loops.
excellent good not allowed
Revision August 2006, SE08, SW V2.61 2-23
Chapter 2 Installation and Wiring|VFD-S Series
2.4.4 Control Terminals
Control Terminal Wiring (Factory Setting)
A. XXXSXXA/B/D/U
+10V AVIAFM M0 M1 M2 M3 M4 M5GND
RA
Relay contactor output
RB
Factory setting : Fault indication
RC
MO1 Photo coupler output
Operation freq.
setting
MCM
Factory setting : in work
potentiometer
VR : 3K~5K
Corrector RJ11
RS485 Communication port
potentiometer
Multi-step speed 3
VR : 1K~5K
Multi-step speed 2
6 ~ 1
Multi-step speed 1
Reset
Freq. meter
Wire Gauge: 24-12 AWG
Reverse/Stop
0~10 VDC
Full scale voltmeter Forward/Stop Wire Type: Copper Only
Torque: 4 kgf-cm (3.5 in-lbf)
B. XXXSXXE
* *
Multi-step speed 3
Wire Gauge: 24-16 AWG
Wire Type: Copper Only
Torque: 2 kgf-cm (1.7 in-lbf)
Terminal symbols and functions
Terminal Factory Settings (NPN mode)
Terminal Function
Symbol ON: Connect to GND
Refer to Pr.4-04 to Pr.4-08 for programming the
M0 Multi-function auxiliary input
Multi-function Inputs.
ON: the activation current is 16mA.
M1 Multi-function input 1
OFF: leakage current tolerance is 10μA.
M2 Multi-function input 2
M3 Multi-function input 3
2-24 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
Terminal Factory Settings (NPN mode)
Terminal Function
Symbol ON: Connect to GND
M4 Multi-function input 4
M5 Multi-function Input 5
+17V DC Voltage Source +17VDC, 20mA used for PNP mode.
Common for digital inputs and used for NPN
GND Digital Signal Common
mode.
AFM circuit
AFM
0~10V
AFM Analog output meter ondometer
Max. 2mA
GND
Internal Circuit
Multi-function Relay output
RA
Resistive Load:
(N.O.) a
5A(N.O.)/3A(N.C.) 240VAC
5A(N.O.)/3A(N.C.) 24VDC
Multi-function Relay output Inductive Load:
RB
(N.C.) b 1.5A(N.O.)/0.5A(N.C.) 240VAC
1.5A(N.O.)/0.5A(N.C.) 24VDC
Refer to Pr.3-06 for programming
RC Multi-function Relay common
Maximum 48VDC, 50mA
Refer to Pr.3-01 for programming
Max: 48Vdc
MO1-DCM
50mA
Mo1
Multi-function Output 1
MO1
(Photocoupler)
MCM
internal circuit
MCM Multi-function output common Max. 48Vdc 50mA
+10V Potentiometer power supply +10VDC 10mA (variable resistor: 3~5kohm)
Revision August 2006, SE08, SW V2.61 2-25
Chapter 2 Installation and Wiring|VFD-S Series
Terminal Factory Settings (NPN mode)
Terminal Function
Symbol ON: Connect to GND
0~+10V/4-20mA corresponds to 0-max.
operation frequency (Pr.01-00)
PID feedback signal
AVI input impedance: 100kohm
ACI input impedance: 250kohm
AVI
AVI circuit
+10V
ACI
J1
Analog voltage Input
AVI
(AVI/ACI)
AVI
GND
Internal Circuit
AVI
ACI circuit
ACI
ACI
J1
GND
Internal Circuit
2
Control signal wiring size: 18 AWG (0.75 mm ) with shielded wire.
Analog input terminals (AVI, GND)
� Analog input signals are easily affected by external noise. Use shielded wiring and keep
it as short as possible (<20m) with proper grounding. If the noise is inductive, connecting
the shield to terminal GND can bring improvement.
� If the analog input signals are affected by noise from the AC motor drive, please connect
μ
a capacitor (0.1 F and above) and ferrite core as indicated in the following diagrams:
AVI
C
GND
ferrite core
wind each wires 3 times or more around the core
Digital inputs (M0~M5, GND)
� When using contacts or switches to control the digital inputs, please use high quality
components to avoid contact bounce.
2-26 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
Digital outputs (MO1, MCM)
� Make sure to connect the digital outputs to the right polarity, see wiring diagrams.
� When connecting a relay to the digital outputs, connect a surge absorber or fly-back
diode across the coil and check the polarity.
General
� Keep control wiring as far as possible from the power wiring and in separate conduits to
avoid interference. If necessary let them cross only at 90º angle.
� The AC motor drive control wiring should be properly installed and not touch any live
power wiring or terminals.
NOTE
� If a filter is required for reducing EMI (Electro Magnetic Interference), install it as close as
possible to AC drive. EMI can also be reduced by lowering the Carrier Frequency.
� When using a GFCI (Ground Fault Circuit Interrupter), select a current sensor with
sensitivity of 200mA, and not less than 0.1-second detection time to avoid nuisance
tripping.
DANGER!
Damaged insulation of wiring may cause personal injury or damage to circuits/equipment if it comes
in contact with high voltage.
Revision August 2006, SE08, SW V2.61 2-27
Chapter 2 Installation and Wiring|VFD-S Series
2.4.5 Main Circuit Terminals
VFD002S11A/11B, VFD004S11A/11B
Power terminal
AC Input Line Motor
Terminal Connection
Ground Braking Resistor
Power Terminal:
Torque: 12 kgf-cm (10 lbf-in)
2
Wire Gauge: 14-20 AWG (2.1-0.5mm )
o
Wire Type: Copper only, 75 C
2-28 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
VFD002S21B/23A, VFD004S21B/23A/43A/43B/43E, VFD007S21B/23A/43A/43B/43E,
VFD015S23D
Power terminal
AC Input Line Motor
Terminal Connection
Ground Braking DC Reactor
Resistor
Power Terminal:
Torque: 12 kgf-cm (10 lbf-in)
2
Wire Gauge: 14-20 AWG (2.1-0.5mm )
o
Wire Type: Copper only, 75 C
Revision August 2006, SE08, SW V2.61 2-29
Chapter 2 Installation and Wiring|VFD-S Series
VFD002S21A/E, VFD004S21A/E, VFD007S21A/E
Power terminal
AC Input Line Motor
Terminal Connection
Braking
Ground DC Reactor
Resistor
Power Terminal:
Torque: 12 kgf-cm (10 lbf-in)
2
Wire Gauge: 14-20 AWG (2.1-0.5mm )
o
Wire Type: Copper only, 75 C
2-30 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
VFD007S11A/B
Power terminal
AC Input Line Motor
Terminal Connection
Ground Braking Resistor
Power Terminal:
Torque: 20 kgf-cm (17.4 lbf-in)
2
Wire Gauge: 10-18 AWG (5.3-0.8mm )
o
Wire Type: stranded copper only, 75 C
Revision August 2006, SE08, SW V2.61 2-31
Chapter 2 Installation and Wiring|VFD-S Series
VFD015S21U/43D/43E/43U, VFD022S21U/23D/43D/43E/43U
Power terminal
AC Input Line Motor
Terminal
Connection
Braking
Ground DC Reactor
Resistor
Power Terminal:
Torque: 20 kgf-cm (17.4 lbf-in)
2
Wire Gauge: 10-18 AWG (5.3-0.8mm )
o
Wire Type: stranded copper only, 75 C
2-32 Revision August 2006, SE08, SW V2.61
Chapter 2 Installation and Wiring|VFD-S Series
VFD015S21D/E, VFD022S21D/E
Power terminal
AC Input Line Motor
Terminal Connection
Ground Braking DC Reactor
Resistor
Power Terminal:
Torque: 20 kgf-cm (17.4 lbf-in)
2
Wire Gauge: 10-18 AWG (5.3-0.8mm )
o
Wire Type: stranded copper only, 75 C
Revision August 2006, SE08, SW V2.61 2-33
Chapter 2 Installation and Wiring|VFD-S Series
This page intentionally left blank
2-34 Revision August 2006, SE08, SW V2.61
Chapter 3 Start Up
3.1 Preparations before Start-up
Carefully check the following items before proceeding.
� Make sure that the wiring is correct. In particular, check that the output terminals U/T1,
V/T2, W/T3 are NOT connected to power and that the drive is well grounded.
� Verify that there are no short-circuits between terminals and from terminals to ground or
mains power.
� Check for loose terminals, connectors or screws.
� Verify that no other equipment is connected to the AC motor.
� Make sure that all switches are OFF before applying power to ensure that the AC motor
drive doesn’t start running and there is no abnormal operation after applying power.
� Make sure that the front cover is correctly installed before applying power.
� Do NOT operate the AC motor drive with humid hands.
� Check the following items after applying power: The display without digital keypad should
be as following.
-The keypad should light up as follows (normal status with no error)
RUN STOP
FWD
REV
When power is ON,
LEDs “STOP” and “FWD”
should light up. The
STOP/RESET
RUN
MIN. MAX.
display will show “F60.0”.
PROG
MODE
DATA
- If the drive has built-in fan, it should run.
Revision August 2006, SE08, SW V2.61 3-1
Chapter 3 Start Up| VFD-S Series
3.2 Operation Method
Refer to 4.2 How to operate the digital keypad and chapter 5 parameters for setting. Please choose
a suitable method depending on application and operation rule. The operation is usually done as
shown in the following table.
Operation Command
Operation Method Frequency Source
Source
Keypad RUN STOP/RESET
MI2
Parameter
setting:
External terminals
MI3
4-05=10
Operate from input:
4-06=11
external signal M0-GND
GND
M1-GND
AVI, ACI
3.3 Trial Run
After finishing checking the items in “3.1 preparation before start-up”, you can perform a trial run.
1. After applying power, verify that the display shows “F60.0”.
2. Setting frequency to about 5Hz by using key.
RUN
3. Pressing key for forward running. And if you want to change to reverse running, you
should press key in page. And if you want to decelerate to stop, please
STOP/RESET
press key.
4. Check following items:
� Check if the motor direction of rotation is correct.
� Check if the motor runs steadily without abnormal noise and vibration.
� Check if acceleration and deceleration are smooth.
If the results of trial run are normal, please start the formal run.
3-2 Revision August 2006, SE08, SW V2.61
Chapter 3 Start Up| VFD-S Series
NOTE
1. Stop running immediately if any fault occurs and refer to the troubleshooting guide for solving the
problem.
2. Do NOT touch output terminals U/T1, V/T2, W/T3 when power is still applied to R/L1, S/L2, T/L3
even when the AC motor drive has stopped. The DC-link capacitors may still be charged to
hazardous voltage levels, even if the power has been turned off.
3. To avoid damage to components, do not touch them or the circuit boards with metal objects or
your bare hands.
Revision August 2006, SE08, SW V2.61 3-3
Chapter 3 Start Up| VFD-S Series
This page intentionally left blank
3-4 Revision August 2006, SE08, SW V2.61
Chapter 4 Digital Keypad Operation
4.1 Description of the Digital Keypad
LED Display
LED indication
Indicate frequency, motor
Light during RUN,
parameter setting value
STOP, FWD and
and alarm contents.
REV operation.
RUN STOP RUN Key
FWD Start inverter drive operation.
REV
STOP/RESET Key
Potentiometer for
Stop inverter drive operation
frequency setting.
and reset the inverter after
Could be the Master
faults occurred.
Frequency input
STOP/RESET
RUN
by setting Pr.2-00.
PROG/DATA Key
MIN. MAX.
Set the different parameters
and enter information.
Mode Key
PROG
Change between MODE UP and DOWN Key
DATA
Sets the parameter number
different display
modes. or changes the numerical
data such as the freq.
reference.
4.2 Explanation of LED Indicators
Stop AC drive when STOP
button has been pressed.
RUN
STOP
FWD
REV
REV LED lights during reverse operation.
FWD LED lights during forward operation.
RUN LED lights during RUN operation.
4.3 Explanations of Display Messages
Display Message Descriptions
Displays the AC drive Master Frequency.
Displays the actual output frequency at terminals U/T1, V/T2, and W/T3.
User defined unit (where U = F x Pr.00.05)
Displays the output current at terminals U/T1, V/T2, and W/T3.
Revision August 2006, SE08, SW V2.61 4-1
Chapter 4 Digital Keypad Operation|VFD-S Series
Display Message Descriptions
The internal PLC process step currently being performed.
Displays the DC-BUS voltage
Displays the output voltage
Displays the AC motor drive forward run status.
Displays the AC motor drive reverse run status.
The counter value (C).
Displays the selected group.
Displays the selected parameter.
Displays the actual stored value of the selected parameter.
Display “End” for approximately 0.5 second if input has been. After a
parameter value has been set, the new value is automatically stored in
memory. To modify an entry, use the keys.
Display “Err”, if the input is invalid.
4-2 Revision August 2006, SE08, SW V2.61
Chapter 4 Digital Keypad Operation|VFD-S Series
4.4 How to Operate the Digital Keypad
Setting Mode
START
GO START
Note: In the selection mode, press to set the parameters.
Setting parameters
move down to the previous display
or
Success to
Input data error
set parameter.
move up to the previous display
NOTE:
In the parameter setting mode, you can press
to return the selecting mode.
To shift data
START
Setting direction (When operation source is digital keypad)
or or
Revision August 2006, SE08, SW V2.61 4-3
Chapter 4 Digital Keypad Operation|VFD-S Series
This page intentionally left blank
4-4 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters
The VFD-S parameters are divided into 11 groups by property for easy setting. In most applications,
the user can finish all parameter settings before start-up without the need for re-adjustment during
operation.
The 11 groups are as follows:
Group 0: User Parameters
Group 1: Basic Parameters
Group 2: Operation Method Parameters
Group 3: Output Function Parameters
Group 4: Input Function Parameters
Group 5: Multi-Step Speed and PLC Parameters
Group 6: Protection Parameters
Group 7: Motor Parameters
Group 8: Special Parameters
Group 9: Communication Parameters
Group A: PID Parameters
Revision August 2006, SE08, SW V2.61 5-1
Chapter 5 Parameters|VFD-S Series
5.1 Summary of Parameter Settings
�: The parameter can be set during operation.
Group 0 User Parameters
Factory
Pr. Explanation Settings NOTE
Setting
0-00 Identity Code of the AC Motor Drive Read-only d #
0-01 Rated Current Display of the AC Read-only d##.#
Motor Drive
0-02 Parameter Reset d09: All parameters are reset to d0
factory settings (50Hz,
220V/380V)
d10: All parameters are reset to
factory settings (60Hz,
220V/440V)
d0: Display the frequency command
value (LED F)
d1: Display the actual output
frequency (LED H)
�0-03 Start-up Display Selection d2: Multifunction display, see Pr.00- d0
04
d3: Display output current (LED A)
d4: Display forward/reverse
command (Frd/rEv)
d0: Display User-Defined Unit (u)
d1: Display Counter Value (C)
d2: Display Process Operation (1.tt)
u
d3: Display DC-BUS Voltage ( )
�0-04 Content of Multi-Function Display d4: Display output voltage (E) d0
d5: Display frequency commands of
PID (P)
d6: Display analog feedback signal
value (b) (%)
�0-05 User-Defined Coefficient K d0.1 to d160 d1.0
0-06 Software Version Read-only d#.#
0-07 Password Input d0 to d999 d0
0-08 Password Set d0 to d999 d0
�0-09 Memory Mode Selections d0 to d63 d8
Group 1 Basic Parameters
Factory
Pr. Explanation Settings NOTE
Setting
1-00 Maximum Output Frequency (Fmax) d50.0 to d400 Hz d60.0
1-01 Maximum Voltage Frequency (Fbase) d10.0 to d400 Hz d60.0
230V series: d2.0V to d255V d220
1-02 Maximum Output Voltage (Vmax)
460V series: d4.0V to d510V d440
1-03 Mid-Point Frequency (Fmid) d1.0 to d400 Hz d1.0
1-04 Mid-Point Voltage (Vmid) 230V series: d2.0V to d255V d12
5-2 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Factory
Pr. Explanation Settings NOTE
Setting
460V series: d4.0V to d510V d24
1-05 Minimum Output Frequency (Fmin) d1.0 to d60.0 Hz d1.0
Minimum Output Voltage (Vmin) 230V series: d2.0V to d255V d12.0
1-06
460V series: d4.0V to d510V d24.0
1-07 Output Frequency Upper Limit d1 to d110% d100
1-08 Output Frequency Lower Limit d0 to d100% d0
�1-09 Accel Time 1 d0.1 to d600 Sec d10.0
�1-10 Decel Time 1 d0.1 to d600 Sec d10.0
�1-11 Accel Time 2 d0.1 to d600 Sec d10.0
�1-12 Decel Time 2 d0.1 to d600 Sec d10.0
�1-13 Jog Acceleration / Deceleration Time d0.1 to d600 Sec d10.0
�1-14 Jog Frequency d1.0 Hz to d400 Hz d6.0
d0: Linear Accel/Decel
d1: Auto Accel, Linear Decel
d2: Linear Accel, Auto Decel
d3: Auto Accel/Decel (Set by load)
Auto acceleration / deceleration (refer
1-15 d0
d4: Linear Accel; Auto Decel, Stall
to Accel/Decel time setting)
Prevention during Decel
d5: Auto Accel/Decel, Stall
Prevention during Decel
1-16 Acceleration S-Curve d0 to d7 d0
1-17 Deceleration S-Curve d0 to d7 d0
d0.0 Jog Decelerating Time
1-18 Jog Decelerating Time Determined by Pr.1-13 d0.0
d0.1 to d600
Group 2 Operation Method Parameters
Factory
Pr. Explanation Settings NOTE
Setting
d0: Master Frequency input
determined by digital keypad.
(record the frequency of power
loss and it can do analog
overlap plus)
d1: Master Frequency determined
by analog signal DC 0V-10V
(external terminal AVI). (won’t
record the frequency of power
loss and it can’t do analog
Source of Master Frequency overlap plus)
2-00 d0
Command d2: Master Frequency determined
by analog signal DC 4mA -
20mA (external terminal AVI).
(won’t record the frequency of
power loss and it can’t do
analog overlap plus)
d3: Master Frequency determined
by Potentiometer on the digital
keypad. (won’t record the
frequency of power loss and it
can do analog overlap plus)
Revision August 2006, SE08, SW V2.61 5-3
Chapter 5 Parameters|VFD-S Series
Factory
Pr. Explanation Settings NOTE
Setting
d4: Master Frequency operated by
RS-485 serial communication
interface and record frequency
of power loss. (record the
frequency of power loss and it
can do analog overlap plus)
Source of Master Frequency
2-00 d5: Master Frequency operated by d0
Command
RS-485 serial communication
interface and won’t record
frequency before power loss.
(won’t record the frequency of
power loss and it can do analog
overlap plus)
d0: Digital Keypad
d1: External terminals. Keypad
STOP/RESET enabled.
d2: External terminals. Keypad
STOP/RESET disabled.
Source of Operation
2-01 d3: RS-485 serial communication d0
Command
(RJ-11) .Keypad STOP/RESET
enabled.
d4: RS-485 serial communication
(RJ-11). Keypad STOP/RESET
disabled.
d0: STOP: ramp to stop; E.F.: coast
to stop
2-02 Stop Method d0
d1: STOP: coast to stop; E.F.: coast
to stop
d3: 3KHz
d4: 4KHz
d5: 5KHz
d6: 6KHz
2-03 PWM Carrier Frequency Selections d10
d7: 7KHz
d8: 8KHz
d9: 9KHz
d10: 10KHz
d0: Enable forward/reverse
2-04 Motor Direction Control operation d0
d1: Disable reverse operation
d0: Decelerate to 0 Hz
d1: Coast to stop and display “EF”
2-05 Loss of ACI Signal d0
d2: Continue operation by last
frequency command
d0: Disable
d1: Enable + AVI
2-06 Analog Auxiliary Frequency Operation d0
d2: Enable + ACI
Group 3 Output Function Parameters
5-4 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Factory
Pr. Explanation Settings NOTE
Setting
d0: analog frequency meter
3-00 Analog Output Signal d0
d1: analog current meter
�3-01 Analog Output Gain d1 to d200% d100
3-02 Desired Frequency Attained d1.0 to d400 Hz d1.0
3-03 Terminal Count Value d0 to d999 d0
3-04 Preliminary Count Value d0 to d999 d0
Multi-Function Output Terminal 1
3-05 d0: No Function d1
(Photocoupler Output)
d1: AC Drive Operational
d2: Master Frequency Attained
d3: Zero Speed
d4: Over Torque Detection
d5: Base-Block (B.B.) Indication
d6: Low-Voltage Indication
d7: Operation Mode Indication
d8: Fault Indication
d9: Desired Frequency Attained
Multi-Function Output Terminal 2 d10: PLC Program Running
3-06 d8
(Relay Output) d11: PLC Program Step Completed
d12: PLC Program Completed
d13: PLC Program Operation
Paused
d14: Terminal Count Value Attained
d15: Preliminary Count Value
Attained
d16: AC Motor Drive Ready
d17: FWD command Indication
d18: REV command Indication
Group 4 Input Function Parameters
Factory
Pr. Explanation Settings NOTE
Setting
�4-00 Potentiometer Bias Frequency d 0.0 to d 100.0% d0.0
d0: Positive Bias
Potentiometer Bias
�4-01 d0
d1: Negative Bias
Polarity
Potentiometer
�4-02 d1 to d200 % d100
Frequency Gain
d0: Forward Motion Only
Potentiometer Reverse
4-03 d0
d1: Reverse Motion enabled
Motion Enable
d0: No Function
d1: FWD/STOP, REV/STOP
d2: FWD/REV, RUN/STOP
d3: 3-wire Operation Control Mode
Multi-Function Input Terminal 1 (M0, d4: E.F. External Fault Input (N.O.)
4-04 d1
M1) d5: E.F. External Fault Input (N.C.)
d6: Reset
d7: Multi-Step Speed Command 1
d8: Multi-Step Speed Command 2
d9: Multi-Step Speed Command 3
Revision August 2006, SE08, SW V2.61 5-5
Chapter 5 Parameters|VFD-S Series
Factory
Pr. Explanation Settings NOTE
Setting
Multi-Function Input Terminal 2 (M2) d10: Jog Operation
4-05 d6
d11: Accel/decel Inhibit
Multi-Function Input Terminal 3 (M3) d12: First or Second
Acceleration/deceleration Time
4-06 Selection d7
d13: External base block (N.O.)
d14: External base block (N.C.)
Multi-Function Input Terminal 4 (M4) d15: Up: Increment master
frequency
4-07 d16: Down: Decrement master d8
frequency
d17: Run PLC Program
d18: Pause PLC Program
d19: Counter Trigger Signal
d20: Counter Reset
d21: Select ACI / Deselect AVI
d22: PID Function Disabled
d23: JOG FWD
d24: JOG REV
d25: The source of master
frequency is AVI.
4-08 Multi-Function Input Terminal 5(M5) d9
d26: The source of master
frequency is ACI.
d27: Press UP/DOWN key to switch
forward/reverse (N.O.) motion
d28: Press UP/DOWN key to switch
forward/reverse (N.C.) motion
d29: M0: 0: RUN 1: STOP, M1: no
function, Direction is controlled
by keypad
d0: Disable
4-09 Line Start Lockout d0
d1: Enable
d0: Based on accel/decel time
d1: Up frequency according to
constant speed, down frequency
according to deceleration time
4-10 Up/Down Mode d2: Up frequency according to d3
acceleration time, down
frequenc according to constant
speed
d3: Constant speed
Accel/Decel Rate of Change of
4-11 UP/DOWN Operation with Constant 0~1000, unit: 5 Hz/sec d1
Speed
Group 5 Multi-Step Speed and PLC Parameters
Factory
Pr. Explanation Settings NOTE
Setting
5-00 1st Step Speed Freq. d0.0 to d400 Hz d0.0
5-01 2nd Step Speed Freq. d0.0 to d400 Hz d0.0
5-6 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Factory
Pr. Explanation Settings NOTE
Setting
5-02 3rd Step Speed Freq. d0.0 to d400 Hz d0.0
5-03 4th Step Speed Freq. d0.0 to d400 Hz d0.0
5-04 5th Step Speed Freq. d0.0 to d400 Hz d0.0
5-05 6th Step Speed Freq. d0.0 to d400 Hz d0.0
5-06 7th Step Speed Freq. d0.0 to d400 Hz d0.0
d0: Disable PLC Operation
d1: Execute one program cycle
d2: Continuously execute program
cycles
d3: Execute one program cycle step
by step
5-07 PLC Mode d0
d4: Continuously execute one
program cycle step by step
d5: Disable PLC operation, but can
set direction of 1st speed to 7th
speed
5-08 PLC Forward/ Reverse Motion d0 to d255 (0: FWD 1: REV) d0
5-09 Time Duration of Zero Step Speed d0 to d65500 Sec d0
5-10 Time Duration of 1st Step Speed d0 to d65500 Sec d0
5-11 Time Duration of 2nd Step Speed d0 to d65500 Sec d0
5-12 Time Duration of 3rd Step Speed d0 to d65500 Sec d0
5-13 Time Duration of 4th Step Speed d0 to d65500 Sec d0
5-14 Time Duration of 5th Step Speed d0 to d65500 Sec d0
5-15 Time Duration of 6th Step Speed d0 to d65500 Sec d0
5-16 Time Duration of 7th Step Speed d0 to d65500 Sec d0
Group 6 Protection Parameters
Factory
Pr. Explanation Settings NOTE
Setting
d0: Disable
6-00 Over-Voltage Stall Prevention d1
d1: Enable
Over-Voltage Stall Prevention Level 115V/230V series: d350 to d410V d390
6-01
460V series: d700 to d820V d780
6-02 Over-Current Stall Prevention Level d20 to d150% d130
d0: Disabled
d1: Enabled during constant speed
operation. After the over-torque
is detected, keep running until
OL1 or OL occurs.
d2: Enabled during constant speed
operation. After the over-torque
6-03 Over-Torque Detection Mode is detected, stop running. d0
d3: Enabled during running and
continues before Continuous
Output Time Limit (Pr.6-05) is
reached
d4: Enabled during running. After
the over-torque is detected, stop
running.
6-04 Over-Torque Detection Level d30 to d200% d150
Revision August 2006, SE08, SW V2.61 5-7
Chapter 5 Parameters|VFD-S Series
Factory
Pr. Explanation Settings NOTE
Setting
6-05 Over-Torque Detection Time d0.1 to d10.0 Sec d0.1
Electronic Thermal Overload Relay
6-06 d0 to d2 d2
Selection
Electronic Thermal
�6-07 d30 to d600 Sec d60
Characteristic
6-08 Present Fault Record d0: No fault
d1: Over current (oc)
d2: Over voltage (ov)
d3: Over heat (oH)
d4: Over load (oL)
6-09 Second Most Recent Fault Record d5: Over load (oL1)
d6: External fault (EF)
d7: Reserved
d0
d8: Reserved
d9: Excess current during
acceleration (ocA)
d10: Excess current during
6-10 Third Most Recent Fault Record
deceleration (ocd)
d11: Excess current during steady
state (ocn)
d12: Ground fault (GF)
d13: Reserved
d14: Low voltage (Lv)
d15: CPU failure 1 (cF1)
d16: CPU failure 2 (cF2)
d17: Base block (b.b.)
d18: Overload (oL2)
d19: Auto acceleration/deceleration
failure (cFA)
d20: Software protection enable
(codE)
d21: Reserved
d22: CPU failure (cF3.1)
d23: CPU failure (cF3.2)
d24: CPU failure (cF3.3)
d25: CPU failure (cF3.4)
d26: CPU failure (cF3.5)
d27: CPU failure (cF3.6)
d28: CPU failure (cF3.7)
d29: Hardware protection failure
(HPF.1)
d30: Hardware protection failure
(HPF.2)
d31: Hardware protection failure
(HPF.3)
d32: Communication time-out
(CE10)
d33: Reserved
d34: Software error (SErr)
d35: Reserved
d36: PID error (Pld) d0
d37: Reserved
d38: Phase loss (PHL)
5-8 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Group 7 Motor Parameters
Factory
Pr. Explanation Settings NOTE
Setting
�7-00 Motor Rated Current d30 to d120% d85
Motor No-Load Current
�7-01 d0 to d90% d50
Torque Compensation
�7-02 d0 to d10 d1
�7-03 Slip Compensation d0.0 to d10.0 d0.0
Group 8 Special Parameters
Factory
Pr. Explanation Settings NOTE
Setting
8-00 DC Braking Voltage Level d0 to d30% d0
8-01 DC Braking Time during Start-Up d0.0 to d60.0 Sec d0.0
8-02 DC Braking time during Stopping d0.0 to d60.0 Sec d0.0
8-03 Start-Point for DC Braking d0.0 to d400 Hz d0.0
d0: Operation stops after
Momentary Power Loss
d1: Operation continues after
momentary power loss, speed
Momentary Power Loss Operation search starts with the Master
8-04 d0
Selection Frequency reference value
d2: Operation continues after
momentary power loss, speed
search starts with the minimum
frequency
8-05 Maximum Allowable Power Loss Time d0.3 to d5.0 Sec d2.0
8-06 B.B. Time for Speed Search d0.3 to d5.0 Sec d0.5
8-07 Current Limit for Speed Search d30 to d200% d150
8-08 Skip Frequency 1 Upper Limit d0.0 to d400 Hz d0.0
8-09 Skip Frequency 1 Lower Limit d0.0 to d400 Hz d0.0
8-10 Skip Frequency 2 Upper Limit d0.0 to d400 Hz d0.0
8-11 Skip Frequency 2 Lower Limit d0.0 to d400 Hz d0.0
8-12 Skip Frequency 3 Upper Limit d0.0 to d400 Hz d0.0
8-13 Skip Frequency 3 Lower Limit d0.0 to d400 Hz d0.0
8-14 Auto Restart After Fault d0 to d10 d0
d0: Enable
8-15 AVR Function d1: Disable d2
d2: Disable when deceleration
Software Braking Level 115V/230V series: d350 to d450V d380
8-16
460V series: d700 to d900V d760
8-17 DC Braking Lower Bound Limit d0.0 to d400 Hz d0.0
Group 9 Communication Parameters
Revision August 2006, SE08, SW V2.61 5-9
Chapter 5 Parameters|VFD-S Series
Factory
Pr. Explanation Settings NOTE
Setting
Communication
�9-00 d1 to d254 d1
Address
d0: Baud Rate 4800 bps
�9-01 Transmission Speed d1
d1: Baud Rate 9600 bps
d2: Baud Rate 19200 bps
�9-01 Transmission Speed d1
d3: Baud Rate 38400 bps
d0: Warn and Keep Operating
Transmission Fault d1: Warn and Ramp to Stop
�9-02 d0
Treatment
d2: Warn and Coast to Stop
d3: Keep Operating without Warning
d0: Disable
�9-03 Time-out Detection d0
d1 to d20: time setting (1 sec
increment)
d0: 7,N,2 (Modbus, ASCII)
d1: 7,E,1 (Modbus, ASCII)
d2: 7,O,1 (Modbus, ASCII)
d3: 8,N,2 (Modbus, ASCII)
Communication
�9-04 d0
d4: 8,E,1 (Modbus, ASCII)
Protocol
d5: 8,O,1 (Modbus, ASCII)
d6: 8,N,2 (Modbus, RTU)
d7: 8,E,1 (Modbus, RTU)
d8: 8,O,1 (Modbus, RTU)
Group A PID Parameters
Factory
Pr. Explanation Settings NOTE
Setting
d0: Disable PID function
d1: Negative PID feedback from
external terminal (AVI) 0 to
+10V
d2: Negative PID feedback from
external terminal (ACI) 4 to
A-00 Input terminal for PID Feedback 20mA d0
d3: Positive PID feedback from
external terminal (AVI) 0 to
+10V
d4: Positive PID feedback from
external terminal (ACI) 4 to
20mA
A-01 Gain over PID Detection value d0 to d999 d100
A-02 Proportional Gain (P) d0 to d999 d100
A-03 Integral Time (I) d0 to d999 d100
A-04 Derivative Control (D) d0 to d100 d0
A-05 Upper Bound for Integral Control d0 to d100% d100
A-06 Primary Delay Filter Time d0 to d999 d0
5-10 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Factory
Pr. Explanation Settings NOTE
Setting
A-07 PID Output Freq. Limit d0 to d110% d100
A-08 Feedback Signal Detection Time d0.0 to d650 seconds d0.0
Treatment of the Erroneous d0: warn and RAMP to stop
A-09 d0
Feedback Signals d1: warn and COAST to stop
A-10 Sleep Frequency d0.0 to d400Hz d0.0
A-11 Wakeup Frequency d0.0 to d400Hz d0.0
A-12 Sleep Period d0.0 to d650 seconds d0.0
A-13 PID User Defined d0.0 to d400 d0.0
Revision August 2006, SE08, SW V2.61 5-11
Chapter 5 Parameters|VFD-S Series
5.2 Parameter Settings for Applications
� Speed Search
Related
Applications Purpose Functions
Parameters
Windmill, winding Restart free- Before the free-running motor is
8-06
machine, fan and all running motor completely stopped, it can be restarted
8-07
inertia loads without detection of motor speed. The
AC motor drive will auto search motor
speed and will accelerate when its
speed is the same as the motor speed.
� DC Braking before Running
Related
Applications Purpose Functions
Parameters
When e.g. windmills, Keep the free- If the running direction of the free-
8-00
fans and pumps rotate running motor at running motor is not steady, please
8-01
freely by wind or flow standstill. execute DC braking before start-up.
8-17
without applying power
� Multi-step Operation
Related
Applications Purpose Functions
Parameters
4-04~4-08
Cyclic operation by To control 7-step speeds and duration
Conveying machinery
multi-step speeds. by simple contact signals.
5-00~5-06
� Switching acceleration and deceleration times
Related
Applications Purpose Functions
Parameters
Switching
1-09~1-12
When an AC motor drive drives two or
Auto turntable for acceleration and
more motors, it can reach high-speed 4-04~4-08
conveying machinery deceleration times
but still start and stop smoothly.
by external signal
� Operation Command
Related
Applications Purpose Functions
Parameters
Selecting the Selection of AC motor drive control by
2-01
General application source of control external terminals, digital keypad or
4-04~4-08
signal RS485.
5-12 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
� Two-wire/three-wire
Related
Applications Purpose Functions
Parameters
FWD/STOP
4-04~4-08
M0 "Open": Stop, "Close": FWD Run
REV/STOP
M1 "Open": Stop, "Close":REV Run
GND
M0 "Open": Stop, "Close": Run
To run, stop,
RUN/STOP
forward and
General application
M1 "Open": FWD, "Close":REV
reverse by external
REV/FWD
terminals GND
3-wire
STOP RUN
M0 Run command, Runs when "close"
M2 Stop command, stops when "Open"
M1 REV/FWD Run selection
"Open": FWD Run
RUN/FWD
"Close": REV Run
GND
� Frequency Hold
Related
Applications Purpose Functions
Parameters
Acceleration/ Hold output frequency during
4-04~4-08
General application
deceleration pause Acceleration/deceleration
� Auto Restart after Fault
Related
Applications Purpose Functions
Parameters
For continuous and
8-14
The AC motor drive can be
Air conditioners, reliable operation
restarted/reset automatically up to 10
remote pumps without operator
times after a fault occurs.
intervention
� Emergency Stop by DC Braking
Related
Applications Purpose Functions
Parameters
AC motor drive can use DC braking
8-00
Emergency stop for emergency stop when quick stop is
8-02
High-speed rotors without brake needed without brake resistor. When
8-03
resistor used often, take motor cooling into
consideration.
Revision August 2006, SE08, SW V2.61 5-13
Chapter 5 Parameters|VFD-S Series
� Over-torque Setting
Related
Applications Purpose Functions
Parameters
The over-torque detection level can be
6-03~6-05
set. Once OC stall, OV stall and over-
To protect
torque occurs, the output frequency
Pumps, fans and machines and to
will be adjusted automatically. It is
extruders have continuous/
suitable for machines like fans and
reliable operation
pumps that require continuous
operation.
� Upper/Lower Limit Frequency
Related
Applications Purpose Functions
Parameters
When user cannot provide
1-07
Control the motor
upper/lower limit, gain or bias from
Pump and fan 1-08
speed within
external signal, it can be set
upper/lower limit
individually in AC motor drive.
� Skip Frequency Setting
Related
Applications Purpose Functions
Parameters
The AC motor drive cannot run at
8-08~8-13
To prevent constant speed in the skip frequency
Pumps and fans
machine vibrations range. Three skip frequency ranges
can be set.
� Carrier Frequency Setting
Related
Applications Purpose Functions
Parameters
The carrier frequency can be
2-03
General application Low noise increased when required to reduce
motor noise.
� Keep Running when Frequency Command is Lost
Related
Applications Purpose Functions
Parameters
When the frequency command is lost
2-05
For continuous by system malfunction, the AC motor
Air conditioners
operation drive can still run. Suitable for
intelligent air conditioners.
5-14 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
� Output Signal during Running
Related
Applications Purpose Functions
Parameters
Signal available to stop braking (brake
3-05~3-06
release) when the AC motor drive is
Provide a signal for
General application running. (This signal will disappear
running status
when the AC motor drive is free-
running.)
� Output Signal in Zero Speed
Related
Applications Purpose Functions
Parameters
When the output frequency is lower
3-05~3-06
Provide a signal for than the min. output frequency, a
General application
running status signal is given for external system or
control wiring.
� Output Signal at Desired Frequency
Related
Applications Purpose Functions
Parameters
When the output frequency is at the
3-05~3-06
Provide a signal for
General application desired frequency, a signal is given for
running status
external system or control wiring.
� Over-torque Detection
Related
Applications Purpose Functions
Parameters
To protect The over-torque detection level can be
3-05~3-06
Pumps, fans and machines and to set. Once over-torque occurs, a signal
6-04
extruders have continuous/ will occur to prevent the AC motor
6-05
reliable operation drive damage.
� Output Signal at Low-voltage
Related
Applications Purpose Functions
Parameters
When the voltage between P-N is low
3-05~3-06
Provide a signal for
General application voltage, a signal is given for external
running status
system or control wiring.
Revision August 2006, SE08, SW V2.61 5-15
Chapter 5 Parameters|VFD-S Series
� Output Signal when Frequency Attained
Related
Applications Purpose Functions
Parameters
When the output frequency is at the
3-05~3-06
desired frequency (by frequency
Provide a signal for 3-04
General application command), a signal is given for
running status
3-10
external system or control wiring
(frequency attained).
� Output Signal for Base Block
Related
Applications Purpose Functions
Parameters
When executing Base Block, a signal
3-05~3-06
Provide a signal for
General application is given for external system or control
running status
wiring.
� Overheat Warning for Heat Sink
Related
Applications Purpose Functions
Parameters
When heat sink is overheated, it will
3-05~3-06
General application For safety send a signal for external system or
control wiring.
� Multi-function Analog Output
Related
Applications Purpose Functions
Parameters
The value of frequency, output
3-05
Display running current/voltage can be read by
General application
status connecting a frequency meter or
voltage/current meter.
5-16 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
5.3 Description of Parameter Settings
Group 0: User Parameters �This parameter can be set during operation.
0-00 Identity Code of the AC Motor Drive
Settings Read Only Factory setting: d#
0-01 Rated Current Display of the AC motor drive
Settings Read Only Factory setting: d ##.#
� Pr. 0-00 displays the identity code of the AC motor drive. The capacity, rated current, rated
voltage and the max. carrier frequency relate to the identity code. Users can use the following
table to check how the rated current, rated voltage and max. carrier frequency of the AC
motor drive correspond to the identity code.
� Pr. 0-01 displays the rated current of the AC motor drive. By reading this parameter the user
can check if the AC motor drive is correct.
115V/230V Series
KW 0.2 0.4 0.75 1.5 2.2
HP 0.25 0.5 1.0 2.0 3.0
Pr.0-00 d0 d2 d4 d6 d8
Rated Output Current (A) 1.6 2.5 4.2 7.5 11.0
Max. Carrier Frequency 10kHz
460V Series
KW 0.4 0.75 1.5 2.2
HP 0.5 1.0 2.0 3.0
Pr.0-00 d3 d5 d7 d9
Rated Output Current (A) 1.5 2.5 4.2 5.5
Max. Carrier Frequency 10kHz
0-02 Parameter Reset
Factory Setting: d0
Settings d9 All parameters are reset to factory settings (50Hz, 220V/380V)
d10 All parameters are reset to factory settings (60Hz, 220V/440V)
� This setting allows the user to return all parameters to the factory default settings.
�Start-up Display Selection
0-03
Factory Setting: d0
Settings d0 Display the frequency command value (LED F)
d1 Display the actual output frequency (LED H)
d2 Multifunction display, see Pr.0-04
d3 Display output current (LED A)
Revision August 2006, SE08, SW V2.61 5-17
Chapter 5 Parameters|VFD-S Series
d4 Display forward/reverse command (Frd/rEv)
0-04 �Content of Multi-function Display
Factory Setting: d0
Settings d0 Display the user-defined unit (u)
d1 Display the counter value (C)
d2 Display the content of PLC time (1.tt)
d3 Display the DC BUS voltage (U)
d4 Display the output voltage (E)
d5 Display frequency commands of PID (P)
d6 Display analog feedback signal value (b) (%)
� Display the user-defined unit, where unit = H X Pr.0-5-
0-05 �User Defined Coefficient K Unit: 0. 1
Settings d0.1 to d160 Factory Setting: d1.0
� The coefficient K determines the multiplying factor for the user-defined unit.
The display value is calculated as follows:
Display value = (output frequency x K)
� The display window is only capable of showing three digits, yet you could use Pr.0-05 to
create larger numbers. The display windows uses decimal points to signify numbers up to five
digits as illustrated in the following:
Display Number Represented
999 The absence of a decimal point indicates a three–digit integer.
A signal decimal point between the middle and the right-most numbers is a true
99.9
decimal point; it separates ones and tenths as in “30.5” (thirty and one-half).
A single decimal point after the right-most numbers is not a true decimal point,
999. instead it indicates that a zero follows the right-most number. For example, the
number 1230 would be displayed as “123.”
Two decimal points (one between the middle and the right-most numbers, and
one after the right-most number) are not true decimal points; instead they indicate
99.9.
that two zeros follow the right-most number. For example, the number 34500
would be displayed as “34.5.”.
0-06 Software Version
Settings Read Only
Display d #.#
5-18 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
0-07 Password Input Unit: 1
Settings d0 to d999 Factory Setting: d0
� Pr.0-07 and Pr.0-08 work together to provide data security for the AC drive. When Pr.0-08 is
set to a value other than 0, a password must be entered to alter the values of parameters.
The password is the number set in Pr.0-08, which ranges from 1 to 999. Pr.0-07 is where the
password is entered to allow parameter values to be altered.
� Display states:
d0: no password / correct password has been input
d1: parameters are locked
Password Set Unit: 1
0-08
Settings d0 to d999 Factory Setting: d0
Display 0 No password set or successful input in Pr. 0-07
1 Password has been set
� To set a password to protect your parameter settings.
If the display shows 0, no password is set or password has been correctly entered in Pr.0-07.
All parameters can then be changed, including Pr.0-08.
The first time you can set a password directly. After successful setting of password the
display will show 1.
Be sure to record the password for later use.
To cancel the parameter lock, set the parameter to 0 after inputting correct password into Pr.
0-07.
The password consists of min. 1 digits and max. 3 digits.
� How to make the password valid again after decoding by Pr.0-07:
Method 1: Re-input original password into Pr.0-08 (Or you can enter a new password if you
want to use a changed or new one).
Method 2: After rebooting, password function will be recovered.
Password Decode Flow Chart
Revision August 2006, SE08, SW V2.61 5-19
Chapter 5 Parameters|VFD-S Series
0-08 0-07
Displays 0 when
Correct Password Incorrect Password
entering correct
END END
password into
Pr.0-07.
0-08 0-07
Displays 0 when
3 chances to enter the correct
entering correct
password.
password into
1st time displays "d 1" if
Pr.0-07.
password is incorrect.
2nd time displays "d 2", if
password is incorrect.
3rd time displays " codE"
(blinking)
If the password was entered
incorrectly after three tries,
the keypad will be locked.
Turn the power OFF/ON to
re-enter the password.
�Memory Mode Selections Unit: 1
0-09
Settings d0 to d63 Factory Setting: d8
� This parameter is determined to save frequency, operation direction and parameter setting
after power off or not.
� Setting method: input to this parameter after converting binary 6-bit to decimal. Refer to
following two tables for detail.
Bit 0 Reserved
0: save frequency
Bit 1
1: not save frequency
Bit 2 Reserved
0: save direction
Bit 3
1: not save direction
0: save parameters (except Pr.0-09 and Pr.0-02)
Bit 4
1: not save parameters
0: save Pr.0-09
Bit 5
1: not save Pr. 0-09
5-20 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
bit 5 bit4 Bit 3 bit 1 Setting for Pr. 0-09
0 0
0
1 2
0
0 8 (factory setting)
1
1 10
0
0 16
0
1 18
1
0 24
1
1 26
0 32
0
1 34
0
0 40
1
1 42
1
0 48
0
1 50
1
0 56
1
1 58
� When Pr. 0-09 is set to b5=0, Pr. 0-09 setting will be saved after power on again.
� When Pr. 0-02 is set to d10, all parameters (includes Pr.0-09) will be set to factory setting.
Revision August 2006, SE08, SW V2.61 5-21
Chapter 5 Parameters|VFD-S Series
Group 1: Basic Parameters
Maximum Output Frequency (Fmax) Unit: 0.1
1-00
Settings d50.0 to d400 Hz Factory Setting: d60.0
� This parameter determines the AC motor drive’s Maximum Output Frequency. All the AC
motor drive frequency command sources (analog inputs 0 to +10V and 4 to 20mA) are scaled
to correspond to the output frequency range.
1-01 Maximum Voltage Frequency (Fbase) Unit: 0.1
Settings d10.0 to d400 Hz Factory Setting: d60.0
� This value should be set according to the rated frequency of the motor as indicated on the
motor nameplate. Maximum Voltage Frequency determines the v/f curve ratio. For example, if
the drive is rated for 460 VAC output and the Maximum Voltage Frequency is set to 60Hz, the
drive will maintain a constant ratio of 7.66 V/Hz (460V/60Hz=7.66V/Hz). This parameter value
must be equal to or greater than the Mid-Point Frequency (Pr.1-03).
1-02 Maximum Output Voltage (Vmax) Unit: 0.1
Settings 115V/230V seriesd2.0 to d255V Factory Setting: 220.0
460V series d4.0 to d510V Factory Setting: 440.0
� This parameter determines the Maximum Output Voltage of the AC motor drive. The
Maximum Output Voltage setting must be smaller than or equal to the rated voltage of the
motor as indicated on the motor nameplate. This parameter value must be equal to or greater
than the Mid-Point Voltage (Pr.1-04).
1-03 Mid-Point Frequency (Fmid) Unit: 0.1
Settings d1.0 to d400Hz Factory Setting: d1.0
� This parameter sets the Mid-Point Frequency of the V/f curve. With this setting, the V/f ratio
between Minimum Frequency and Mid-Point frequency can be determined. This parameter
must be equal to or greater than Minimum Output Frequency (Pr.1-05) and equal to or less
than Maximum Voltage Frequency (Pr.1-01).
1-04 Mid-Point Voltage (Vmid) Unit: 0.1
Settings 115V/230V seriesd2.0 to d255V Factory Setting: d12.0
460V series d4.0 to d510V Factory Setting: d24.0
5-22 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
� This parameter sets the Mid-Point Voltage of any V/f curve. With this setting, the V/f ratio
between Minimum Frequency and Mid-Point Frequency can be determined. This parameter
must be equal to or greater than Minimum Output Voltage (Pr.1-06) and equal to or less than
Maximum Output Voltage (Pr.1-02).
1-05 Minimum Output Frequency (Fmin) Unit: 0.1
Settings d1.0 to d60.0Hz Factory Setting: d1.0
� This parameter sets the Minimum Output Frequency of the AC drive. This parameter must be
equal to or less than Mid-Point Frequency (Pr.1-03).
1-06 Minimum Output Voltage (Vmin) Unit: 0.1
Settings 115V/230V seriesd2.0 to d255V Factory Setting: d12.0
460V series d4.0 to d510V Factory Setting: d24.0
� This parameter sets Minimum Output Voltage of the AC drive. This parameter must be equal
to or less than Mid-Point Voltage (Pr.1-04).
Voltage
Pr.1-02
Pr.1-04
Pr.1-06
Freq.
0
Pr.1-03
Pr.1-00
Pr.1-05
Pr.1-01
Standard V/F Curve
1-07 Output Frequency Upper Limit Unit: 1
Settings d1 to d110% Factory Setting: d100
� This parameter must be equal to or greater than the Output Frequency Lower Limit (Pr.1-08).
The Maximum Output Frequency (Pr.1-00) is regarded as 100%.
� Output Frequency Upper Limit value = (Pr.1-00 * Pr.1-07)/100.
1-08 Unit: 1
Output Frequency Lower Limit
Settings d0 to d100% Factory Setting: d0
� The Upper/Lower Limit is to prevent operation error and machine damage.
Revision August 2006, SE08, SW V2.61 5-23
Chapter 5 Parameters|VFD-S Series
� If the Upper Limit of Output Frequency is 50Hz and the Maximum Output Frequency is 60Hz,
the Maximum Output Frequency will be limited to 50Hz.
� If the Lower Limit of Output Frequency is 10Hz, and the Minimum Output Frequency (Pr.1-05)
is set at 1.0Hz, then any Command Frequency between 1-10Hz will generate a 10Hz output
from the drive.
� This parameter must be equal to or less than the Upper Limit of Output Frequency (Pr.1-07).
1-09 �Acceleration Time 1 (Taccel 1) Unit: 0.1
1-10 �Deceleration Time 1 (Tdecel 1) Unit: 0.1
1-11 �Acceleration Time 2 (Taccel 2) Unit: 0.1
1-12 �Deceleration Time 2 (Tdecel 2) Unit: 0.1
Settings d0.1 to d600Sec Factory Setting: d10.0
� Pr.1-9- This parameter is used to determine the time required for the AC drive to ramp from 0
Hz to its Maximum Output Frequency (Pr.1-00). The rate is linear unless S-Curve is
“Enabled.”
� Pr.1-10. This parameter is used to determine the time required for the AC drive to decelerate
from the Maximum Output Frequency (Pr.1-00) down to 0 Hz. The rate is linear unless S-
Curve is “Enabled.”
� The acceleration/deceleration time 2 determines the time for the AC drive to
acceleration/deceleration from 0Hz to Maximum Output Frequency (Pr.1-00)
(acceleration/deceleration time 1 is the default). A Multi-Function Input terminal must be
programmed to select acceleration/deceleration time 2 and the terminals must be closed to
select acceleration/deceleration time 2. See Pr.4-04 to Pr.4-8-
� In the diagram shown below, the acceleration/deceleration time of the AC drive is the time
between 0 Hz to Maximum Output Frequency (Pr.1-00). Suppose the Maximum Output
Frequency is 60 Hz, start-up frequency (Pr.1-05) is 1.0 Hz, and acceleration/deceleration time
is 10 seconds. The actual time for the AC drive to accelerate from start-up to 60 Hz is 9.83
seconds and the deceleration time is also 9.83 seconds.
1-13 � Jog Acceleration/Deceleration Time Unit: 0.1Sec
Settings d0.1 to d600Sec Factory Setting: d10.0
1-14 � Jog Frequency Unit: 0.1Hz
Settings d1.0 to d400Hz Factory Setting: d6.0
5-24 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
� The JOG function can be selected using Multi-function Input terminals (Pr.4-04 to Pr.4-08) if
programmed for Jog (d10). When the Jog terminal is “closed”, the AC drive will accelerate
from Minimum Output Frequency (Pr.1-05) to Jog Frequency (Pr.1-14). When the Jog
terminal “open”, the AC drive will decelerate from Jog Frequency to zero. The
acceleration/deceleration time is decided by the Jog acceleration/deceleration time (Pr.1-13).
During operation, the AC drive cannot perform Jog command. And during Jog operation,
other operation commands cannot be accepted, except command of FORWARD, REVERSE
and STOP keys on the digital keypad.
Frequency
Max.
Output
freq.
Pr.1-00
Jog
Freq.
Pr.1-14
Time
Pr. 1-13 Pr. 1-13
Acceleration Time Deceleration Time
Jog operation
OFF
ON
command
1-15 �Auto-Acceleration / Deceleration
Factory Setting: d0
Settings d0 Linear Accel/Decel
d1 Auto Accel, Linear Decel
d2 Linear Accel, Auto Decel
d3 Auto Accel/Decel (Set by load)
d4 Linear Accel; Auto Decel, Stall Prevention during Decel
d5 Auto Accel/Decel, Stall Prevention during Decel
� If the auto acceleration/deceleration is selected, the AC drive will acceleration/deceleration in
the fastest and smoothest means possible by automatically adjusting the time of
acceleration/deceleration.
Revision August 2006, SE08, SW V2.61 5-25
Chapter 5 Parameters|VFD-S Series
1-16 Acceleration S-Curve
1-17 Deceleration S-Curve
Settings d0 to d7 Factory Setting: d0
� These two parameters allow you to configure whether the acceleration and/or deceleration
ramps are linear or S-shaped. The S-curve is enabled when set at d1-d7. Setting d1 offers
the quickest S-curve and d7 offers the longest and smoothest S-curve. The AC drive will not
follow the acceleration/deceleration time in Pr.1-09 to Pr.1-12. To Disable the S-curve, set
Pr.1-16 and Pr.1-17 to d0.
� From the diagram shown below, the original setting acceleration/deceleration time will be for
reference when the function of the S-curve is enabled. The actual acceleration/deceleration
time will be determined based on the S-curve selected (d1 to d7).
1 2
3
4
2
1
3
4
1 2
3 4
Disable S curve
Enable S curve
Acceleration/deceleration Characteristics
1-18 Jog Decelerating Time Unit: 0.1Sec
Settings d0.0 to d600 Factory Setting: d0.0
� When Pr.1-18 is set to d0.0 Jog decelerating time determined by the setting of Pr.1-13 0.1 to
600 sec, Jog decelerating time can be set independently, separates from Pr.1-13.
� When Pr.1-18 is set to 0.0, Pr.1-13 determines both Jog acceleration and deceleration time.
When Pr.1-18 is set between 0.1 to 600 seconds, which will determine Jog Decelerating Time
and Pr.1-13 will only determine Jog Accelerating Time.
5-26 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Group 2: Operation Method Parameters
2-00 Source of Master Frequency Command
Factory Setting: d0
Settings d0 Master Frequency input determined by digital keypad. (record the
frequency of power loss and it can do analog overlap plus)
d1 Master Frequency determined by analog signal DC 0V-10V
(external terminal AVI). (won’t record the frequency of power loss
and it can’t do analog overlap plus)
d2 Master Frequency determined by analog signal DC 4mA-20mA
(external terminal AVI). (won’t record the frequency of power loss
and it can’t do analog overlap plus)
d3 Master Frequency determined by Potentiometer on the digital
keypad. (won’t record the frequency of power loss and it can do
analog overlap plus)
d4 Master Frequency operated by RS-485 serial communication
interface and record frequency of power loss. (record the frequency
of power loss and it can do analog overlap plus)
d5 Master Frequency operated by RS-485 serial communication
interface and won’t record frequency before power loss. (won’t
record the frequency of power loss and it can do analog overlap
plus)
� This parameter sets the Frequency Command Source of the AC drive.
� If the Frequency Command Source is external (DC 0 to +10V or 4 to 20mA), please make
sure the (AVI) terminal jumper is in the proper position as shown below.
� Position of jumper: Please open the top cover. It is at the lower-left corner of the panel. The
jumper J1 determines the type of external analog input, either DC voltage signal or current
signal.
J1
Voltage signal input(0-10V)
Current signal input(4-20mA)
� When setting analog overlap plus, it needs to set Pr. 2-06 to select AVI or ACI.
Revision August 2006, SE08, SW V2.61 5-27
Chapter 5 Parameters|VFD-S Series
2-01 Source of Operation Command
Factory Setting: d0
Settings d0 Controlled by the keypad
d1 External terminals. Keypad STOP/RESET enabled.
d2 External terminals. Keypad STOP/RESET disabled.
d3 RS-485 serial communication (RJ-11). Keypad STOP/RESET
enabled.
d4 RS-485 serial communication (RJ-11). Keypad STOP/RESET
disabled.
� When the AC drive is controlled by an external source, please refer to parameter group 4 for
detailed explanations on related parameter settings.
2-02 Stop Method
Factory Setting: d0
Settings d0 STOP: ramp to stop E.F.: coast to stop
d1 STOP: coast to stop E.F.: coast to stop
� The parameter determines how the motor is stopped when the AC motor drive receives a
valid stop command or detects External Fault.
Ramp: the AC motor drive decelerates to Minimum Output Frequency (Pr.1-05)
according to the deceleration time set in Pr.1-10 or Pr.1-12 and then stops.
Coast: the AC motor drive stops the output instantly upon command, and the motor
free runs until it comes to a complete standstill.
The motor stop method is usually determined by the characteristics of the motor load and
how frequently it is stopped.
(1) It is recommended to use “ramp to stop” for safety of personnel or to prevent
material from being wasted in applications where the motor has to stop after
the drive is stopped. The deceleration time has to be set accordingly.
(2) If motor free running is allowed or the load inertia is large, it is recommended to
select “coast to stop”. For example: blowers, punching machines, centrifuges
and pumps.
5-28 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Frequency
Frequency
output
output
frequency
frequency
motor
motor
speed
speed
Time
Time
stops according to
free run to stop
operation
operation
decel eration time
command RUN
RUN
STOP command STOP
ramp to stop and free run to stop
2-03 Unit: 1
PWM Carrier Frequency Selections
115V/230V/460V Series
Power 0.25 to 3hp (0.2kW to 2.2kW)
Setting Range d3 to d10 kHz
Factory Setting d10 kHz
� This parameter determines the PWM carrier frequency of the AC motor drive.
Electromagnetic
Current
Carrier Heat
Acoustic
Noise or leakage
Wave
Frequency Dissipation
Noise
current
Minimal Minimal Minimal
Significant
3kHz
10kHz
Minimal
Significant Significant
Significant
� From the table, we see that the PWM carrier frequency has a significant influence on the
electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise.
2-04 Motor Direction Control
Factory Setting: d0
Settings d0 Enable forward/reverse operation
d1 Disable reverse operation
� The parameter determines whether the AC drive can operate in the reverse direction.
Revision August 2006, SE08, SW V2.61 5-29
Chapter 5 Parameters|VFD-S Series
2-05 Loss of ACI Signal (4-20mA)
Factory Setting: d0
Settings d0 Decelerate to 0 Hz
d1 Coast to stop and display “EF”
d2 Continue operation by last frequency command
� This parameter is only effective when the Source of Frequency is commanded by a 4 to
20mA signal. The ACI input is considered lost when the ACI signal falls below 2mA.
2-06 Analog Auxiliary Frequency Operation
Factory Setting: d0
Settings d0 Disable
d1 Enable + AVI (0~10V)
d2 Enable + ACI (4~20mA)
� This parameter is used to determinate that the analog signal to overlap is 0~10V (AVI) or
4~20mA (ACI).
� To make sure the short PIN of J1 on the panel is correct position before setting this parameter.
5-30 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Group 3: Output Function Parameters
3-00
Analog Output Signal (AFM)
Factory Setting: d0
Settings d0 Analog Frequency Meter (0 to Maximum Output Frequency)
d1 Analog Current Meter (0 to 250% of rated AC motor drive current)
� This parameter sets the function of the AFM output 0~+10VDC (ACM is common).
� The voltage output type for this analog signal is PWM. It needs to read value by the movable
coil meter and is not suitable for A/D signal conversion.
3-01 �Analog Output Gain Unit: 1
Settings d1 to d200% Factory Setting: d100
� The parameter sets the voltage range of the analog output signal at terminals AFM, that
corresponds with either the output frequency or the output current of the VFD.
AFM GND
AFM GND
+- +-
Analog Frequency Meter Analog Current Meter
� The analog output voltage is directly proportional to the output frequency of the AC drive. With
the factory setting of 100%, the Maximum Output Frequency (Pr.1-00) of the AC drive
corresponds to +10VDC analog voltage output. (The actual voltage is about +10VDC, and
can be adjusted by Pr.3-01).
� The analog output voltage is directly proportional to the output current of the AC drive. With
the factory setting of 100%, the 2.5 times rated current of the AC drive corresponds to
+10VDC analog voltage output. (The actual voltage is about +10VDC, and can be adjusted by
Pr. 3-01)
NOTE
Voltmeter specification: The sourcing capability of the output is limited to 0.21mA. Sourcing voltage:
10V. Output resistance: 47kΩ.
If the meter reads full scale at a voltage less than 10 volts, then Pr.3-01 should be set by
the following formula: Pr.3-01 = ((meter full scale voltage)/10) ×100%
For example: When using the meter with full scale of 5 volts, adjust Pr.3-01 to 50%.
Revision August 2006, SE08, SW V2.61 5-31
Chapter 5 Parameters|VFD-S Series
3-02 Desired Frequency Attained Unit: 0.1
Settings d1.0 to d400 Hz Factory Setting: d1.0
� If a multi-function output terminal is set to function as Desired Frequency Attained (Pr.3-05 or
3-06=d9), then the output will be activated when the programmed frequency is attained.
Freq.
Detection range
Max. Output
Detection range
+
Freq. 4Hz
+ -
2Hz
-
Desired Freq.
Detection
Pr.3-02
range
-2Hz
Time
Preset Freq.
Attained
indication
OFF
OFF
ON
Pr.3-05 to 3-06
Desired Freq.
Attained
OFF
ON
OFF
Indication
Pr.3-05 to 3-06
Desired Freq. Attained & Preset Freq. Attained
3-03 Terminal Count Value Unit: 1
Settings d0 to d999 Factory Setting: d0
� The parameter determines the upper limit value of the internal counter. The internal counter
can be triggered by the external terminal (Pr.4-4 to Pr.4-8, d19). Upon completion of counting,
the specified output terminal will be activated. (Pr.3-05, Pr.3-06, d14).
3-04 Preliminary Count Value Unit: 1
Settings d0 to d999 Factory Setting: d0
� When the counter value is counted up from “1” to the setting value of this parameter, the
corresponding multi-function output terminal which set to d15 as Preliminary Counter Value
Attained will be closed. The application can be that closing the multi-function output terminal
makes the AC drive operate at low speed until stop before the counting value is going to be
attained.
� The timing diagram is shown below:
5-32 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Display
(Pr.0-04=d1)
2ms
TRG
Counter Trigger Signal
Multi-function Input Terminal
2ms
Preliminary Counter Value Attained Output
The width of trigger signal
(Pr. 3-04=d3)
should not be less than
(Pr. 3-05 to Pr. 3-06=d15)
2ms(<250 Hz)
Terminal Count Value Attained Output
(Pr.3-03=d5)
(Pr.3-05 to Pr.3-06=d14)
3-05
Multi-function Output Terminal 1 (Photocoupler output)
Factory Setting: d1
3-06
Multi-function Output Terminal 2 (relay output)
Factory Setting: d8
Settings d0 to d18
Setting Function Description
d0 No Function
d1 AC Drive Operational the output terminal will be activated when the drive is
running.
Master Frequency Attained the output will be activated when the AC drive attains
d2
Maximum Output Frequency.
d3 Zero Speed the output will be activated when Command Frequency
is lower than the Minimum Output Frequency.
d4 Over Torque Detection the output will be activated as long as the over-torque is
detected. Pr.6-04 determines the Over-Torque detection
level.
d5 Base-Block (B.B.) Indication the output will be activated when the output of the AC
drive is shut off by external Baseblock.
d6 Low-Voltage Indication the output will be activated when low voltage is detected.
d7 Operation Mode Indication the output will be activated when the operation of the AC
drive is controlled by External Control Terminals.
d8 Fault Indication the output will be activated when faults occur (oc, ov,
oH, oL, oL1, EF, cF3, HPF, ocA, ocd, ocn, GF).
d9 Desired Frequency Attained the output will be activated when the desired frequency
(Pr.3-02)is attained.
Revision August 2006, SE08, SW V2.61 5-33
Chapter 5 Parameters|VFD-S Series
Setting Function Description
d10 PLC Program Running the output will be activated when the PLC program is
running.
d11 PLC Program Step the output will be activated for 0.5 sec. when each multi-
Completed step speed is attained.
d12 PLC Program Completed the output will be activated for 0.5 sec. when the PLC
program cycle has completed.
d13 PLC Operation Paused the output will be activated when PLC operation is
paused.
Terminal Count Value counter reaches Terminal Count Value.
d14
Attained
Preliminary Counter Value counter reaches Preliminary Count Value.
d15
Attained
d16 AC Motor Drive Ready
d17 FWD Command Indication When AC drive receives the command of forward
running, it will output immediately no matter AC drive is
in the state of run or stop.
d18 REV Command Indication When AC drive receives the command of reverse
running, it will output immediately no matter AC drive is
in the state of run or stop.
5-34 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Group 4: Input Function Parameters
4-00 � Potentiometer Bias Frequency Unit: 0. 1
Settings d0.0 to d100.0% Factory Setting: d0.0
4-01 � Potentiometer Bias Polarity
Factory Setting: d0
Settings d0 Positive Bias
d1 Negative Bias
4-02 � Potentiometer Frequency Gain Unit: 1
Settings d1 to d200% Factory Setting: d100
4-03 Potentiometer Reverse Motion Enable
Factory Setting: d0
Settings d0 Forward motion only
d1 Reverse motion enable (must be negative bias)
� Pr.4-00 to Pr.4-03 are used when the source of frequency command is the analog signal (0 to
+10V DC or 4 to 20 mA DC). Refer to the following examples.
Example 1:
The following is the most common method. Set parameter 2-00 to d1 (0 to +10V signal) or d2 (4 to
20mA current signal).
Example 2:
In this example with the potentiometer set to 0V the Output Frequency is 10 Hz. The mid-point of
the potentiometer becomes 40 Hz. Once the Maximum Output Frequency is reached any further
increase of the potentiometer will not increase output frequency.
Revision August 2006, SE08, SW V2.61 5-35
Chapter 5 Parameters|VFD-S Series
Example 3:
The example also shows the popular method. The whole scale of the potentiometer can be used as
desired. In addition to signals of 0 to 10V and4 to 20mA, the popular voltage signals also include
signals of 0 to 5V, 20 to 4mA or that under 10V. Regarding the setting, please refer to the following
examples.
Example 4:
This example shows a potentiometer range of 0 to 5 Volts.
Example 5:
In this example a 1 volt negative bias is used. In a noise environment, it is advantageous to use
negative bias to provide a noise margin (1V in this example).
5-36 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Example 6:
In this example, a negative bias is used to provide a noise margin. Also a potentiometer frequency
gain is used to allow the Maximum Output Frequency to be reached.
Max.
Pr.1-00
Output
Freq.
Gain adjustment
27
60Hz
Factory Settings
Pr.1-00=60Hz--Max. output Freq.
Pr.4-00=10%--Potentiometer bias freq.
Pr.4-01=1 -- Bias polarity It's 0Hz
0
Pr.4-02=111% -- Pot. freq. gain
within
Pr.4-03=0 -- Forward motion only
this
54
Hz
range.
Calculation of gain
10V
0V
10V
0Hz
Pr.4-02=( )X100%=111%
Negative 9V
0V Potentiometer Scale
1V 10V
bias 6Hz
Example 7:
In this example, the potentiometer is programmed to run a motor is both forward and reverse
direction. A motor will be idle when the potentiometer position is at mid-point of its scale. Using
Pr.4-03 will disable the external FWD and REV controls.
Max.
Output
Pr.1-00
Freq.
60Hz
0
FWD
FWD.
REV.
Factory Settings
30Hz
Pr.1-00=60Hz--Max. output Freq.
0Hz
0V
Pr.4-00=30Hz--Potentiometer bias freq.
5V 10V
Pr.4-01=1 -- bias polarity
Pr.4-02=200% -- pot. freq. gain
30Hz
Pr.4-03=1 -- pot. REV motion enable
60
60
REV
Hz
0V 10V
60Hz
Potentiometer Scale
Example 8:
In this example, the option of anti-slope is shown. Anti-slope is used in an application where control
of pressure, temperature, or flow is needed. Under a high pressure or flow situation, a sensor will
generate a large signal such as 20 mA or 10V. With anti-slope enable, the large signal will slow or
stop the AC drive.
Revision August 2006, SE08, SW V2.61 5-37
Chapter 5 Parameters|VFD-S Series
Max.
Output Pr.1-00
Freq.
30
60Hz
Factory Settings
anti-slope
Pr.1-00=60Hz--Max. output Freq.
Pr.4-00=60Hz--Potentiometer bias freq.
Pr.4-01=1 -- bias polarity
Pr.4-02=100% -- pot. freq. gain
Pr.4-03=1 -- pot. REV. motion enable 60 0
10V
0V Hz
20mA
4mA
0Hz
Potentiometer Scale
0V 10V
4mA 20mA
4-04 Multi-function Input Terminal (M0, M1)
Settings d0 to d29 Factory Setting: d1
4-05 Multi-function Input Terminal (M2)
Factory Setting: d6
4-06 Multi-function Input Terminal (M3)
Factory Setting: d7
4-07 Multi-function Input Terminal (M4)
Factory Setting: d8
4-08 Multi-function Input Terminal (M5)
Factory Setting: d9
Parameters & Functions table:
Value Function Value Function
d0 No Function d15 Up: Increment master frequency
d1 M0: FWD / STOP, M1: REV / STOP d16 Down: Decrement master frequency
d2 M0: RUN / STOP, M1: FWD / REV d17 Run PLC Program
3-Wire Operation Control mode (M0,
d3 d18 Pause PLC Program
M1, M2)
d4 External Fault (Normally Open) d19 Counter Trigger Signal
d5 External Fault (Normally Closed) d20 Counter Reset
Select ACI / Deselect AVI (the priority is
d6 External Reset d21
higher than Pr. 2-00 and d26)
d7 Multi-Step Speed Command1 d22 PID function disable
d8 Multi-Step Speed Command2 d23 JOG FWD
d9 Multi-Step Speed Command3 d24 JOG REV
The source of master frequency is AVI. (The
d10 Jog operation d25
priority is higher than Pr. 2-00 and d26)
Acceleration/Deceleration Speed The source of master frequency is ACI. (The
d11 d26
Inhibit priority is higher than Pr. 2-00)
First or Second Acceleration or Press UP/DOWN key to switch
d12 d27
Deceleration Time Selection forward/reverse (N.O.) motion
External Base Block (N.O.) Press UP/DOWN key to switch
d13 d28
(Normally Open Contact Input) forward/reverse (N.C.) motion
External Base Block (N.C.) M0: 0: RUN 1: STOP, M1: no function,
d14 d29
(Normally Close Contact Input) Direction is controlled by keypad
5-38 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Explanations:
d0 Parameter Disable:
Enter value (d0) to disable any Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08).
NOTE
The purpose of this function is to provide isolation for unused Multi-Function Input Terminals. Any
unused terminals should be programmed to d0 to insure they have no effect on drive operation.
d1 Two wire operation: Restricted to Pr.4-04 and external terminals M0, M1.
FWD/STOP
M0 "Open": Stop, "Close": FWD Run
REV/STOP
M1 "Open": Stop, "Close":REV Run
GND
d2 Two wire operation: Restrict to Pr. 4-04 and external terminals M0, M1.
M0 "Open": Stop, "Close": Run
RUN/STOP
M1 "Open": FWD, "Close":REV
REV/FWD
GND
NOTE
Multi-function Input Terminal M0 does not have its own parameter designation. M0 must be used in
conjunction with M1 to operate two and three wire control.
d3 Three Wire Control: Restricted to Pr.4-04 control terminals M0, M1, M2.
STOP RUN
M0 Run command, Runs when "close"
M2 Stop command, stops when "Open"
M1 REV/FWD Run selection
"Open": FWD Run
RUN/FWD
"Close": REV Run
GND
Revision August 2006, SE08, SW V2.61 5-39
Chapter 5 Parameters|VFD-S Series
NOTE
When value d3 is selected for Pr. 4-04, this will over ride any value entered in Pr.4-05, since Pr.4-05
must be used for three wire control as shown above.
d4, d5 External Faults:
Parameter values d4, d5 programs Multi-Function Input Terminals: M1 (Pr. 4-04), M2 (Pr. 4-05), M3
(Pr. 4-06), M4 (Pr. 4-07) or M5 (Pr. 4-08) to be External Fault (E.F.) inputs.
E.F.(N.O.)
Mx "Close": Operation available.
setting by d4
E.F(N.C.)
Mx "Open":Operation available.
setting by d5
GND
NOTE
When an External Fault input signal is received, the AC drive will stop all output and display “ E.F.”
on Digital Keypad, the motor will free run. Normal operation can resume after the External Fault is
cleared and the AC drive is reset.
d6 External Reset:
Parameter value d6 programs a Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08) to be an External Reset.
RESET
Mx "Close": Operation available
setting by d6
GND
NOTE
the External Reset has the same function as the Reset key on the Digital keypad. After external fault
such as O.H., O.C. and O.V. are clear, this input can be used to reset the drive.
d7, d8, d9 Multi-Step Speed Command:
Parameter values d7, d8, d9 programs any three of the following Multi-Function Input Terminals: M1
(Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) for multi-step speed command
function.
5-40 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
D7 Multi-step 1
Mx "Close": Operation available
Mx "Close": Operation available
D8 Multi-step 2
Mx "Close": Operation available
D9 Multi-step 3
GND
These three inputs select the multi-step speeds defined by Pr.5-00 to Pr.5-06 as shown in the
following diagram. Pr.5-07 to Pr.5-16 can also control output speed by programming the AC drive’s
internal PLC function.
Freq. Pr.5-00
Pr.5-04
Step 1
Step 5
Pr.5-05
Pr.5-01
Step 6
Pr.5-03
Step 2
Step 4
Pr.5-02
Pr.5-06
Step 3
Step 7
Time
Master Freq.
ON ON ON ON
Mx1-GND
ON ON ON ON
Mx2-GND
ON ON ON ON
Mx3-GND
Operation
ON OFF
Command
d10 Jog Operation Control:
Parameter value d10 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08) for Jog control.
Mx "Close": Operation available
d10 jog operation
command
GND
NOTE
Jog operation programmed by d10 can only be initiated while the motor is stopped. (Refer to Pr.1-13,
Pr.1-14.)
d11 Acceleration/Deceleration Speed Inhibit:
Parameter value d11 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08) for Acceleration/deceleration Inhibit. When the command is
received, acceleration and deceleration is stopped and the AC drive maintains a constant speed.
Revision August 2006, SE08, SW V2.61 5-41
Chapter 5 Parameters|VFD-S Series
Frequency
Master Frequency
Deceleration
Acceleration
inhibit
inhibit
Acceleration Deceleration
inhibit inhibit
Actual operation frequency
Time
ON ON ON ON
Mx-GND
Operation
OFF
ON
command
d12 First or Second Acceleration/Deceleration Time Selection:
Parameter value d12 programs a Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3
(Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to control selection of First or Second
Acceleration/deceleration time. (Refer to Pr.1-09 to Pr.1-12.)
Mx "Close": 2nd Acceleration/Deceleraion
"Open": 1st Acceleration/Deceleration
Mx set d12
GND
Frequency
Master
Pr. Pr.
Pr. Pr. Pr. Pr.
Frequency1-09
1-10 1-11 1-12 1-09 1-12
2nd
Deceleration
1st
2nd 1st
Acceleration/
Acceleration/ Acceleration
Deceleration
Deceleration
Time
ON
ON
Mx-GND
operation
ON ON ON
OFF
command
d13, d14 External Base Block:
Parameter values d13, d14 program Multi-Function Input Terminals: M1 (Pr.4-04), M2 (Pr.4-05), M3
(Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) for external Base Block control. Value d13 is for normally
open (N.O.) input, and value d14 is for a normally closed (N.C.) input.
5-42 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
B.B.(N.O.)
Mx "Close": Operation available.
setting by d13
B.B.(N.C.)
Mx "Open":Operation available.
setting by d14
GND
NOTE
When a Base-Block signal is received, the AC drive will stop all output and the motor will free run.
When base block control is deactivated, the AC drive will start its speed search function and
synchronize with the motor speed, and then accelerate to Master Frequency.
External
base-block
signal
Speed synchronization
Pr.8-04=d1
detection
Output
Speed search starts with the
frequency
reference value
Output
Pr.8-06
voltage
Min. base-block time
Speed search operation
d15, d16 Increase/Decrease Master Frequency:
Parameter values d15, d16 program the Multi-Function Input Terminals: M1 (Pr.4-04), M2 (Pr.4-05),
M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to incrementally increase/ decrease the Master
Frequency each time an input is received.
UP
Mx "Close": Freq. will increase
by one unit.
setting by d15
DOWN
Mx "Close":Freq. will decrease
by one unit.
setting by d16
GND
d17, d18 PLC Function Control:
Parameter value d17 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08) to enable the AC drive internal PLC program. Parameter value
d18 programs an input terminal to pause the PLC program.
Revision August 2006, SE08, SW V2.61 5-43
Chapter 5 Parameters|VFD-S Series
PLC operation
Mx "Close": Run PLC.
setting by d17
Mx "Close":Pause PLC.
setting by d18
GND
NOTE
Pr.5-00 to Pr.5-16 define the PLC program.
d19 Counter Trigger:
Parameter value d19 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08) to increase the AC drive’s internal counter. When an input is
received, the counter is increased by 1.
Trigger
Mx counter value increase by
1 when closed.
D19 counter trigger
signal input.
GND
NOTE
The Counter Trigger input can be connected to an external Pulse Signal Generator to count a
processing step or unit of material. See the diagram below.
5-44 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
d20 Counter Reset:
Parameter value d20 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr. 4-05), M3 (Pr.4-
06), M4 (Pr.4-07) or M5 (Pr.4-08) to reset the counter.
Reset counter
Mx "close": reset counter.
d20 reset the counter
value.
GND
d21 Select ACI / Deselect AVI:
Parameter value d21 allows the user to select the input type ACI or AVI via an external switch. AVI is
selected when the contact is open and ACI is selected when the contact is closed. Please note: the
use of this feature will override Pr.2-00 programming and the jumper of the front of the drive must be
moved to the correct location either across the AVI or ACI pin head.
d22 PID function disable:
When input ON with this setting, PID function will be disabled.
d23 JOG FWD:
This function could be operated only when the AC motor drive is stop. The operation direction is
forward, can’t be changed and can be stopped by the STOP key on the keypad. When the contact
is OFF, the AC motor drive will stop by the JOG decel time. Refer to the Pr.1-13 and Pr. 1-14 for
detail.
d24 JOG REV:
This function could be operated only when the AC motor drive is stop. The operation direction is
forward, can’t be changed and can be stopped by the STOP key on the keypad. When the contact
is OFF, the AC motor drive will stop by the JOG decel time. Refer to the Pr.1-13 and Pr. 1-14 for
detail.
d25 The source of master frequency is AVI. (The priority is higher than Pr. 2-00 and d26)
d26 The source of master frequency is ACI. (The priority is higher than Pr. 2-00)
d27 Press UP/DOWN key to switch forward/reverse (N.O.) motion:
When this function is enabled, press key for forward motion and key to REV (N.O.)
motion. The keys and will be disabled.
d28 Press UP/DOWN key to switch forward/reverse (N.C.) motion:
When this function is enabled, press key for forward motion and key to REV (N.C.)
motion. The keys and will be disabled.
Revision August 2006, SE08, SW V2.61 5-45
Chapter 5 Parameters|VFD-S Series
d29 M0: 0: RUN 1: STOP, M1: no function, Direction is controlled by keypad
RUN/STOP
M0 "Open": Stop, "Close": Run
M1 No Function
GND
4-09 Line Start Lockout
Factory Setting: d0
Settings d0 Disable
d1 Enable
� When enabled, the AC drive will not start when powered up with run commands applied. To
start in Line Start Lockout mode, the AC drive must see the run command go from stop to run
after power up. When Line Start Lockout is disable (also known as Auto-Start), the drive will
start when powered-up with run commands applied.
4-10 Up/Down Mode
Factory Setting: d0
Settings d0 Based on accel/decel time
d1 up frequency according to constant speed, down frequency
according to deceleration time
d2 up frequency according to acceleration time, down frequency
according to constant speed
d3 Constant speed
Accel/Decel Rate of Change of UP/DOWN Operation
Unit: 5
4-11
with Constant Speed
Settings d0 to d1000 Hz/sec Factory Setting: d1
� This parameter is used to set the acceleration/deceleration speed mode when multi-function
terminal is set to up/down frequency. (Pr. 4-04 ~ Pr.4-08, function d15, d16)
5-46 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Group 5: Multi-step speeds and PLC (Process Logic Control) parameters
5-00 �1st Step Speed Frequency Unit: 0.01
5-01 �2nd Step Speed Frequency Unit: 0.01
5-02 �3rd Step Speed Frequency Unit: 0.01
5-03 �4th Step Speed Frequency Unit: 0.01
5-04 �5th Step Speed Frequency Unit: 0.01
5-05 �6th Step Speed Frequency Unit: 0.01
5-06 �7th Step Speed Frequency Unit: 0.01
Settings d0.0 to d400 Hz Factory Setting: 0.00
� The Multi-Function Input Terminals (refer to Pr.4-04 to 4-08) are used to select one of the AC
drive Multi-Step speeds. The speeds (frequencies) are determined by Pr.5-00 to 5-06 shown
above.
5-07 PLC Mode
Factory Setting: d0
Settings d0 Disable PLC operation
d1 Execute one program cycle
d2 Continuously execute program cycles
d3 Execute one program cycle step by step
d4 Continuously execute program cycles step by step
st th
d5 Disable PLC operation, but can set direction of 1 speed to 7
speed
� This parameter selects the mode of PLC operation for the AC drive. The PLC program can
be used in lieu of any External Controls, Relays or Switches. The AC drive will change
speeds and directions according to the user’s desired programming.
� When this parameter is set to d5 and it is running by external multi-speed, the high priority of
the operation direction is Pr. 5-08.
Example 1 (Pr.5-07 = d1): Execute one cycle of the PLC program. Its relative parameter settings
are:
st th
1. Pr.5-00 to 5-06: 1 to 7 step speed (sets the frequency of each step speed).
2. Pr.4-04 to 4-08: Multi-Function Input Terminals (set one multi-function terminal as d17- PLC
auto-operation).
3. Pr.3-05 to 3-06: Multi-Function Output Terminals (set a Multi-Function Terminal as d10-PLC
operation indication, d11-one cycle in PLC auto mode or d12-PLC operation fulfillment
attainment).
4. Pr.5-07: PLC mode.
st th
5. Pr.5-08: Direction of operation for Master Frequency and1 to 7 step speed.
6. Pr.5-09 to 5-16: operation time setting of Master Frequency and1st to 7th step speed.
Revision August 2006, SE08, SW V2.61 5-47
Chapter 5 Parameters|VFD-S Series
Frequency
Master freq.=5Hz
Pr.5-03 5-00=10 Hz
4-07=d17 5-09=10 Sec
60Hz
5-01=20 Hz 3-05=d10
5-10=10 Sec
5-02=40 Hz
3-06=d11 5-11=12 Sec
Pr.5-04
5-03=60 Hz
50Hz 5-07=d1 5-12=15 Sec
5-04=50 Hz 5-08=d0 5-13=15 Sec
Pr.5-02 5-05=30 Hz
5-14=8 Sec
40Hz 5-06=15 Hz
5-15=17 Sec
5-16=17 Sec
Pr.5-05
30Hz
Pr.5-01
20Hz
Pr.5-06
15Hz
Pr.5-00
Master
10Hz
Freq. Time
5Hz
(Sec)
0Hz
5-16
5-11 5-12 5-13 5-14 5-15
5-10
5-09
Program operation
command
Program operation
output indication
Program step
complete
Program operation
completed
NOTE
The above diagram shows one complete PLC cycle. To restart the cycle, turn the PLC program off
and then back on.
Example 2 (Pr.5-07 = d2): Continuously executes program cycles
The diagram below shows the PLC program stepping through each speed and the automatically
starting again. To stop the PLC program, one must either pause the program or turn it off (Refer to
Pr.4-05 to 4-08 value d17 and d18).
Frequency
Master freq.=5Hz
5-03
5-00=10 Hz
60Hz 4-07=d17 5-09=10 Sec
5-01=20 Hz
3-05=d11 5-10=10 Sec
5-04
5-02=40 Hz
3-06=d12 5-11=12 Sec
50Hz
5-03=60 Hz
5-07=d2 5-12=15 Sec
5-04=50 Hz
5-08=d0 5-13=15 Sec
5-02
40Hz 5-05=30 Hz
5-14=8 Sec
5-06=15 Hz
5-15=17 Sec
5-05 5-16=17 Sec
30Hz
5-01
5-00
20Hz
5-06
15Hz
5-00
10Hz
5Hz
Time
0Hz
(Sec)
5-11 5-12 5-13 5-14 5-15 5-16 5-09 5-10
5-10
5-09
Program step
complete
Program operation
completed
5-48 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Example 3 (Pr. 5-07 = d3) Execute one cycle step by step:
The example shows how the PLC can perform one cycle at a time, within a complete cycle. Each
step will use the acceleration/deceleration times in Pr.1-09 to Pr.1-12. It should be noticed that the
time each step spends at its intended frequency is diminished, due to the time spent during
acceleration/deceleration.
Frequency
Master freq.=5Hz
5-00=10 Hz
4-07=d17 5-09=10 Sec
5-03
5-01=20 Hz 3-05=d11
5-10=10 Sec
60Hz
5-02=40 Hz
3-06=d12 5-11=12 Sec
5-03=60 Hz
5-07=d3 5-12=15 Sec
5-04
50Hz 5-04=50 Hz
5-08=d0 5-13=15 Sec
5-05=30 Hz
5-14=8 Sec
5-06=15 Hz
5-15=17 Sec
40Hz
5-16=17 Sec
5-05
30Hz
20Hz
5-06
15Hz
10Hz
5Hz
0Hz
Time
(Sec)
t t tt
5-13 5-15
5-16
5-14
5-09
Program step
complete
Program operation
completed
Example 4 (Pr. 5-07 =d4) Continuously execute PLC cycles step by step:
In this explanation, the PLC program runs continuously step by step. Also shown are examples of
steps in the Reverse direction.
Frequency
Master freq.=5Hz
5-00=10 Hz 4-07=d17
5-09=10 Sec
60Hz
5-01=20 Hz
3-05=d10 5-10=10 Sec
5-02=40 Hz 3-06=d11 5-11=12 Sec
5-03=60 Hz
50Hz 5-07=d4 5-12=15 Sec
5-04=50 Hz
5-08=d68 5-13=15 Sec
5-05=30 Hz
5-14=8 Sec
40Hz 5-06=15 Hz
5-15=17 Sec
5-16=17 Sec
FWD
15Hz
10Hz
Time
0Hz
(Sec)
5-09
t
REV
20Hz
30Hz
Revision August 2006, SE08, SW V2.61 5-49
Chapter 5 Parameters|VFD-S Series
Example 5 (Pr. 5-07 = d1 Execute one cycle of the PLC program):
In this example, the PLC program runs continuously. It should be noted that the times of reserve
motion may be shorter than expected, due to the acceleration/deceleration times.
Frequency
Master freq.=5Hz
5-00=10 Hz 4-07=d17 5-09=10 Sec
60Hz
5-01=20 Hz
3-05=d10 5-10=10 Sec
5-02=40 Hz
3-06=d11 5-11=12 Sec
50Hz
5-03=60 Hz
5-07=d1 5-12=15 Sec
5-04=50 Hz
5-08=d68 5-13=15 Sec
5-05=30 Hz
40Hz 5-14=8 Sec
5-06=15 Hz
5-15=17 Sec
5-16=17 Sec
FWD
15Hz
10Hz
Time
0Hz
(Sec)
5-09
REV
20Hz
30Hz
* The calculation of time for Pr.5-11, Pr.5-12, Pr.5-15 and Pr.5-16 should be carefully planned.
5-08 PLC Forward/Reverse Motion Unit: 1
Settings d0 to d255 Factory Setting: d0
� This parameter controls the direction of motion for the Multi-Step Speed Pr.5-00 to Pr.5-06
and the Master Frequency. The original direction of Master Frequency will become invalid.
NOTE
The equivalent 8-bit number is used to program the forward/reverse motion for each of the 8 speed
steps (including Master Frequency). The binary notation for the 8-bit number must be translated into
decimal notation and then be entered.
0=Forward
Weights
1=Reverse
Bit 7 6 5 4 3 2 1 0
Director of Master Frequency during PLC
Direction of 1st speed for Pr.5-00
Direction of 2nd speed for Pr.5-01
Direction of 3rd speed for Pr.5-02
Direction of 4th speed for Pr.5-03
Direction of 5th speed for Pr.5-04
Direction of 6th speed for Pr.5-05
Direction of 7th speed for Pr.5-06
5-50 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Weights
0=Forward
1=Reverse
Bit
7 6 5 4 3 2 1 0
Direction 0 1 1 0 0 1 0 0
WD
Direction of 1st speed for Pr.5-00 =FWD
Direction of 2nd speed for Pr.5-01 =REV
Direction of 3rd speed for Pr.5-02 = FWD
Direction of 4th speed for Pr.5-03 = FWD
Direction of 5th speed for Pr.5-04 = FWD
Direction of 6th speed for Pr.5-05 = REV
Direction of 7th speed for Pr.5-06 = FWD
7 6 5 4 3 2 1 0
The setting value = bit7 x 2 +bit6 x 2 +bit5 x 2 +bit4 x 2 +bit3 x 2 +bit2 x 2 +bit1 x 2 +bit0 x 2
7 6 5 4 3 2 1 0
= 0 x 2 +1 x 2 +0 x 2 +0 x 2 +0 x 2 +1 x 2 +0 x 2 +0 x 2
= 0+64+0+0+0+4+0+0
= 68
Setting Pr.5-08 as d68.
5-09 Time Duration of Zero Step Speed Unit: 1
5-10 Time Duration of 1st Step Speed Unit: 1
5-11 Time Duration of 2nd Step Speed Unit: 1
5-12 Time Duration of 3rd Step Speed Unit: 1
5-13 Time Duration of 4th Step Speed Unit: 1
5-14 Time Duration of 5th Step Speed Unit: 1
5-15 Time Duration of 6th Step Speed Unit: 1
5-16 Time Duration of 7th Step Speed Unit: 1
Settings d0 to d65500 Factory Setting: d0
� Pr.5-10 to Pr.5-16 correspond to operation time of each multi-step speed defined by
parameters 5-00 to 5-06. The maximum value of these parameters is 65500 sec., and it’s
displayed as d65.5.
NOTE
If a parameter is set to “d0” (0 Sec), the corresponding step will be skipped. This is commonly used
to reduce number of program steps.
Revision August 2006, SE08, SW V2.61 5-51
Chapter 5 Parameters|VFD-S Series
Group 6: Protection Parameters
6-00 Over-Voltage Stall Prevention Unit: 0.1
Factory Setting: d1
Settings d0 Disable
d1 Enable
� During deceleration, the motor DC bus voltage may exceed its Maximum Allowable Value due
to motor regeneration. When this function is enabled, the AC drive will stop decelerating.
Maintaining a constant output frequency when it happens. The AC drive will only resume
deceleration when the voltage drops below preset value.
NOTE
With a moderate inertial load, the over-voltage during deceleration won’t happen, and the drive will
stop in programmed time. The AC drive will automatically extend the deceleration time with high
inertial loads. If deceleration time is critical for the application, then dynamic braking resistors should
be used.
Over-Voltage Stall Prevention Level
6-01 Unit: 1
Settings 230V Series d350 to d410V Factory Setting: 390
460V Series d700 to d820V Factory Setting: 780
� During deceleration, the DC bus voltage may exceed its maximum allowable value due to
motor regeneration. When this function is enabled, the AC drive will stop decelerating.
Maintaining a constant output frequency when it happens. The AC drive will resume
deceleration when the voltage drops below preset value.
� With a moderate inertial load, the over-voltage during deceleration won’t happen, and the
drive will stop in programmed time. The AC drive will automatically extend the deceleration
time with high inertial loads. If deceleration time is critical for the application, then dynamic
braking resistors should be used.
5-52 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
DC bus voltage
Over-voltage
Band=20V
detection
level Pr.6-01
time
Output
Freq.
time
Over-voltage Stall Prevention
6-02 Unit: 1
Over-Current Stall Prevention Level
Settings d20 to d150% Factory Setting: d130
� A setting of 100% is equal to the Rated Output Current of the drive.
� During acceleration and steady-state operation, the AC drive output current may increase
abruptly to exceed the value specified by Pr.6-02 due to rapid acceleration or excessive load
on the motor. When this function is enabled, the AC drive will decrease. The AC drive will only
resume acceleration when the current drops below the level specified by Pr. 6-02.
Output current
Over-current
ON
detection
Band=5%
OFF
level
Pr.6-02
time
Output
frequency
time
Over-current Stall Prevention Level
Revision August 2006, SE08, SW V2.61 5-53
Chapter 5 Parameters|VFD-S Series
6-03 Over-Torque Detection Mode (OL2)
Factory Setting: d0
Settings d0 Over-Torque detection disabled.
d1 Enabled during constant speed operation. After the over-torque is
detected, keep running until OL1 or OL occurs.
d2 Enabled during constant speed operation. After the over-torque is
detected, stop running.
d3 Over-Torque detection enabled during running, and continues to run
till OL1 or OL.
d4 Enabled during running. After the over-torque is detected, stop
running.
6-04 Over-Torque Detection Level Unit: 1
Settings d30 to d200% Factory Setting: d150
� This setting is proportional to the Rated Output Current of the drive.
6-05 Over-Torque Detection Time Unit: 0.1
Settings d0.1 to d10.0 sec Factory Setting: d0.1
� If a Multi-Function Output Terminal is set as Over-Torque Detection Indication and the output
current exceeds the Over-Torque Detection Level (Pr.6-04, Factory Setting: 150%), the Over-
Torque Detection Time (Pr.6-05, Factory setting: 0.1) and the setting of multi-function terminal
is Over-Torque Detection Indication, the contact will be “close”.
6-06 Electronic Thermal Overload Relay Selection
Factory Setting: d2
Settings 0 Operate with a Standard Motor (self-cooled by fan)
1 Operate with a Special Motor (forced external cooling)
2 Operation disabled
� This function is used to protect the motor from overloading or overheating.
6-07 �Electronic Thermal Characteristic Unit: 1
Settings d30 to d600Sec Factory Setting: d60
2
� The parameter determines the time required activating the I t electronic thermal protection
2
function. The graph below shows I t curves for 150% output power for 1 minute.
5-54 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Operation
time(min)
5
60Hz or more
4
50Hz
3
10Hz
2
5Hz
1
Load
factor (%)
0 20 40 60 80 100 120 140 160 180 200
6-08 Present Fault Record
6-09 Second Most Recent Fault Record
6-10 Third Most Recent Fault Record
Factory Setting: d0
Readings d0 No fault
d1 Over-current (oc)
d2 Over-voltage (ov)
d3 Overheat (oH)
d4 Overload (oL)
d5 Overload1 (oL1)
d6 External fault (EF)
d7 Reserved
d8 Reserved
d9 Current exceeds 2 times rated current during accel. (ocA)
d10 Current exceeds 2 times rated current during decel.(ocd)
d11 Current exceeds 2 times rated current during steady state operation
(ocn)
d12 Ground fault (GF)
d13 Reserved
d14 Low voltage (Lv)
d15 CPU failure 1 (cF1)
d16 CPU failure 2 (cF2)
d17 Base block (b.b.)
d18 Overload (oL2)
d19 Auto acceleration/deceleration failure (cFA)
Revision August 2006, SE08, SW V2.61 5-55
Chapter 5 Parameters|VFD-S Series
d20 Software protection enable (codE)
d21 Reserved
d22 CPU failure (cF3.1)
d23 CPU failure (cF3.2)
d24 CPU failure (cF3.3)
d25 CPU failure (cF3.4)
d26 CPU failure (cF3.5)
d27 CPU failure (cF3.6)
d28 CPU failure (cF3.7)
d29 Hardware protection failure (HPF.1)
d30 Hardware protection failure (HPF.2)
d31 Hardware protection failure (HPF.3)
d32 Communication time-out (CE10)
d33 Reserved
d34 Software error (SErr)
d35 Reserved
d36 PID error (Pld)
d37 Reserved
d38 Phase loss (PHL)
� Pr.6-08 to 6-10 store records of the three most recent faults that had occurred. Use the reset
key to reset the drive when the fault no longer exits.
5-56 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Group 7: Motor Parameters
7-00 �Motor Rated Current Unit: 1
Settings d30 to d120% Factory Setting: d85
� This parameter will limit the AC drive output current in order to prevent the motor from
overheating.
�Motor No-load Current
7-01 Unit: 1
Settings d0 to d90% Factory Setting: d50
� The rated current of the AC drive is regarded as 100%. Motor setting of no-load current will
effect the slip compensation. The setting value must be less than motor rated current setting
Pr.7-00
7-02 �Torque Compensation Unit: 0.1
Settings d0 to d10 Factory Setting: d1
� This parameter may be set so that the AC drive will increase its voltage output during start-up
to obtain a higher initial starting torque.
7-03 �Slip Compensation Unit: 0.01
Settings d0.0 to d10.0 Factory Setting: d0.0
� While driving an asynchronous motor, load on the AC drive will increase, causing an increase
in slip. This parameter may be used to compensate the nominal slip within a range of 0 to 10.
When the output current of the AC drive is greater than the motor no-load current (Pr.7-01),
the AC drive will adjust its output frequency according to this parameter.
Revision August 2006, SE08, SW V2.61 5-57
Chapter 5 Parameters|VFD-S Series
Group 8: Special Parameters
8-00 DC Braking Current Level Unit: 1
Settings d0 to d30% Factory Setting: d0
� This parameter determines the level of DC Braking Voltage Level output to the motor during
start-up and stopping. When setting DC Braking Voltage, the Maximum Output Voltage (Pr.1-
02) is regarded as 100%. It is recommended to start with a low DC Braking Voltage Level and
then increase until proper holding torque has been attained.
8-01 DC Braking Time during Start-up Unit: 0.1
Settings d0.0 to d60.0 sec Factory Setting: d0.0
� This parameter determines the duration of time that the DC Braking Current will be applied to
the motor during the AC drive start-up.
8-02 DC Braking Time during Stopping Unit: 0.1
Settings d0.0 to d60.0 sec Factory Setting: d0.0
� This parameter determines the duration of time that the DC braking voltage will be applied to
the motor during stopping. If stopping with DC Braking is desired, then Pr.2-02 must be set to
RAMP stop (d0).
8-03 Start-Point for DC Braking Unit: 0.1
Settings d0.0 to d400Hz Factory Setting: d0.0
� This parameter determines the frequency when DC Braking will begin during deceleration.
Output Frequency
Start-Point for
DC Braking
Time during
01-05
Stopping
Minimum Output
Frequency
08-03
Time
08-01
Operation
08-02
Command ON OFF
DC Braking Voltage %
5-58 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
� DC Braking during Start-up is used for loads that may move before AC drive starts, such as
fans and pumps. These loads may also be moving in the wrong direction. Under such
circumstances, DC Braking can be executed to hold the load in position before applying a
forward motion.
� DC Braking during stopping is used to decrease stopping time and also to hold a stopped
load in position. For high inertial loads, a dynamic braking resistor may be needed for quick
decelerations.
8-04 Momentary Power Loss Operation Selection
Factory Setting: d0
Settings d0 Operation stops after momentary power loss
d1 Operation continues after momentary power loss, speed search
starts with the Master Frequency reference value
d2 Operation continues after momentary power loss, speed search
starts with the minimum frequency
8-05 Maximum Allowable Power Loss Time Unit: 0.1
Settings d0.3 to d5.0Sec Factory Setting: d2.0
� During a power loss, if the power loss time is less than the time defined by this parameter, the
AC drive will resume operation. If the Maximum Allowable Power Loss Time is exceeded, the
AC drive output is then turned off.
8-06 Base Block Speed Search Unit: 0.1
Settings d0.3 to d5.0Sec Factory Setting: d0.5
� When a momentary power loss is detected, the AC drive turns off for a specified time interval
determined by Pr.8-06 before resuming operation. This time interval is called Base-Block.
This parameter should be set to a value where the residual output voltage is nearly zero,
before the drive resumes operation.
� This parameter also determines the searching time when performing external Base-Block and
fault reset.
8-07 Current Limit for Speed Search Unit: 1
Settings
d30 to d200% Factory Setting: d150
Revision August 2006, SE08, SW V2.61 5-59
Chapter 5 Parameters|VFD-S Series
� Following a power failure, the AC drive will start its speed search operation, only if the output
current is greater than the value determined by Pr.8-07. When the output current is less than
that of Pr.8-07, the AC drive output frequency is at a “speed synchronization point”. The drive
will start to accelerate or decelerate back to the operating frequency at which it was running
prior to the power failure.
Maximum Allowable
Maximum
Power Power Loss Time
Allowable Power
08-05 08-05
Input
Speed
Synchronization
Speed Search
08-04=d1 Detection
08-04=d2
Speed search starts
Output
Speed search starts with
with the Master
Frequency
Min. Output Frequency
Frequency
Output 08-06 08-06
Voltage Baseblock Time
Baseblock Time
8-08 Skip Frequency 1 Upper Limit Unit: 0.1
8-09 Skip Frequency 1 Lower Limit Unit: 0.1
8-10 Skip Frequency 2 Upper Limit Unit: 0.1
8-11 Skip Frequency 2 Lower Limit Unit: 0.1
8-12 Skip Frequency 3 Upper Limit Unit: 0.1
8-13 Skip Frequency 3 Lower Limit Unit: 0.1
Settings d0.0 to d400Hz Factory Setting: d0.0
� These parameters determine Skip frequency. It will cause the AC drive to skip operation at
these frequency ranges with continuous frequency output.
� Pr.8-9, Pr.8-11, Pr.8-13 are for Lower Bound setting, and the settings should follow as Pr.8-9
≧Pr.8-11≧Pr.8-13.
8-14 Auto Restart After Fault Unit: 1
Settings d0 to d10 Factory Setting: d0
� After fault occurs (allowable faults: over-current OC, over-voltage OV), the AC drive can be
reset/restarted automatically up to 10 times. Setting this parameter to 0 will disable the
reset/restart operation after any fault has occurred. When enabled, the AC drive will restart
with speed search, which starts at the Master Frequency.
5-60 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
8-15 Automatic Voltage Regulation (AVR)
Factory Setting: d0
Settings d0 AVR function enabled
d1 AVR function disabled
d2 AVR function disabled when deceleration
� AVR function automatically regulates the AC drive output voltage to the Maximum Output
Voltage (Pr.1-02). For instance, if Pr.1-02 is set at 200 VAC and the input voltage is at 200V
to 264VAC, then the Maximum Output Voltage will automatically be reduced to a maximum of
200 VAC.
� Without AVR function, the Maximum Output Voltage may vary between 180V to 264VAC, due
to the input voltage varying between 180V to 264 VAC.
� Selecting program value d2 enables the AVR function and also disables the AVR function
during deceleration. This offers a quicker deceleration.
Software Braking Level
8-16 Unit: 1
Settings 230V series: d350 to d450V Factory Setting: d380
460V series: d700to d900V Factory Setting: d760
� During deceleration, the DC-bus voltage will increase due to motor regeneration. When DC
bus voltage level exceeds the Software Braking Level, the DC brake output pins (B1, B2) will
be activated.
8-17 Lower Bound of DC Braking Start-up Frequency Unit: 0.1
Settings d0.0 to d400 Hz Factory Setting: d0.0
� The setting frequency is lower than Pr.8-17, the DC Braking will not be activated when stops.
Revision August 2006, SE08, SW V2.61 5-61
Chapter 5 Parameters|VFD-S Series
Group 9: Communication Parameters
9-00 �Communication Address
Settings d1 to d254 Factory Setting: d1
� If the AC drive is controlled by RS-485 serial communication, the communication address
must be set via this parameter.
RS485
Computer
d2 d3
d1
S1 S1 S1
9-01 �Transmission Speed
Factory Setting: d1
Settings d0 Baud rate 4800 bps (bits / second)
d1 Baud rate 9600 bps
d2 Baud rate 19200 bps
d3 Baud rate 38400 bps
� Users can set parameters and control the operation of the AC drive via the RS-485 serial
interface of a personal computer. This parameter is used to set the transmission speed
between the computer and AC drive.
9-02 �Transmission Fault Treatment
Factory Setting: d0
Settings d0 Warn and keep operating
d1 Warn and RAMP to stop
d2 Warn and COAST to stop
d3 No warning and keep operating
5-62 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
9-03 �Time-out Detection
Factory Setting: d0
Settings d0 Disable
d1 1 sec
d2 2 sec
:
d20 20 sec
� If this function is enabled, the timer will start counting once the first valid Modbus
communication signal is received after power-up or reset. The timer will reset to 0 after each
valid Modbus communication message is received. If the watchdog timer reaches the value
set in Pr. 9-03, the drive will stop its output and display the message "CE10" on the digital
keypad. This fault can reset by an external terminal, keypad or a Modbus communication
reset command.
9-04 �Communication Protocol
Factory Setting: d0
Settings d0 Modbus ASCII mode, protocol <7,N,2>
d1 Modbus ASCII mode, protocol <7,E,1>
d2 Modbus ASCII mode, protocol <7,O,1>
d3 Modbus ASCII mode, protocol <8,N,2>
d4 Modbus ASCII mode, protocol <8,E,1>
d5 Modbus ASCII mode, protocol <8,O,1>
d6 Modbus RTU mode, protocol <8,N,2>
d7 Modbus RTU mode, protocol <8,E,1>
d8 Modbus RTU mode, protocol <8,O,1>
� 1. Computer Control
1: +EV
2: GND
3: SG-
4: SG+
6 1
� There is a built-in RS-485 serial interface, marked (RJ-11 Jack) on the control terminal
block, for VFD-S Series. The pins are defined above. Each VFD-S AC drive has a pre-
assigned communication address specified by Pr. 9-00. The computer then controls
each AC drive according to its communication address.
� VFD-S can be setup to communicate on Modbus networks using one of the following
modes: ASCII (American Standard Code for Information Interchange) or RTU (Remote
Revision August 2006, SE08, SW V2.61 5-63
Chapter 5 Parameters|VFD-S Series
Terminal Unit). Users can select the desired mode along with the serial port
communication protocol in Pr. 9-04.
�Code Description:
ASCII mode:
Each 8-bit data is the combination of two ASCII characters. For example, a 1-byte data:
64 Hex, shown as ‘64’ in ASCII, consists of ‘6’ (36Hex) and ‘4’ (34Hex).
Character ‘0’ ‘1’ ‘2’ ‘3’ ‘4’ ‘5’ ‘6’ ‘7’
ASCII code 30H 31H 32H 33H 34H 35H 36H 37H
Character ‘8’ ‘9’ ‘A’ ‘B’ ‘C’ ‘D’ ‘E’ ‘F’
ASCII code 38H 39H 41H 42H 43H 44H 45H 46H
RTU mode:
Each 8-bit data is the combination of two 4-bit hexadecimal characters. For example, 64
Hex.
� 2. Data Format
2.1 10-bit character frame (For 7-bit character):
( 7.N.2)
Start
Stop
Stop
5
01 2 34 6
bit
bit bit
7-bit character
10-bit character frame
( 7.E.1)
Start
Even Stop
0 12 34 56
bit parity
bit
7-bit character
10-bit character frame
( 7.O.1)
Start
Odd Stop
01 2 34 56
bit parity
bit
7-bit character
10-bit character frame
2.2 11-bit character frame (For 8-bit character):
5-64 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
( 8.N.2 )
Start Stop Stop
01 2 34 56 7
bit bit bit
8-bit character
11-bit character frame
( 8.E.1 )
Start Even Stop
01 2 34 5 6 7
parity
bit bit
8-bit character
11-bit character frame
( 8.O.1 )
Odd
Start Stop
01 2 34 5 6 7
parity
bit bit
8-bit character
11-bit character frame
� 3. Communication Protocol
3.1 Communication Data Frame:
ASCII mode:
STX Start character ‘:’ (3AH)
ADR 1 Communication address:
8-bit address consists of 2 ASCII codes
ADR 0
CMD1 Command code:
CMD0 8-bit command consists of 2 ASCII codes
Contents of data:
DATA (n-1)
n x 8-bit data consist of 2n ASCII codes.
…….
n <= 25,maximum of 50 ASCII codes
DATA 0
LRC CHK 1 LRC check sum:
LRC CHK 0 8-bit check sum consists of 2 ASCII codes
END1 End characters:
END1= CR (0DH), END0= LF (0AH)
END0
RTU mode:
START A silent interval of more than 10 ms
ADR Communication address: 8-bit address
CMD Command code: 8-bit command
DATA (n-1)
Contents of data:
…….
n x 8-bit data, n<= 25
DATA 0
CRC CHK
Low CRC check sum:
CRC CHK 16-bit check sum consists of 2 8-bit characters
High
END A silent interval of more than 10 ms
Revision August 2006, SE08, SW V2.61 5-65
Chapter 5 Parameters|VFD-S Series
3.2 ADR (Communication Address)
Valid communication addresses are in the range of 0 to 254. A communication address equal to
0, means broadcast to all AC drives (AMD). In this case, the AMD will not reply any
message to the master device.
00H: broadcast to all AC drives
01H: AC drive of address 01
0FH: AC drive of address 15
10H: AC drive of address 16
:
FEH: AC drive of address 254
For example, communication to AMD with address 16 decimal (10H):
ASCII mode: Address=’1’,’0’ => ‘1’=31H, ‘0’=30H
RTU mode: Address=10H
3.3 CMD (Command code) and DATA (data characters)
The format of data characters depends on the command code. The available command codes
are described as followed: Command code: 03H, read N words. The maximum value
of N is 12. For example, reading continuous 2 words from starting address 2102H of
AMD with address 01H.
ASCII mode:
Response message:
Command message:
STX ‘:’ STX ‘:’
ADR 1 ‘0’ ADR 1 ‘0’
ADR 0 ADR 0
‘1’ ‘1’
‘0’ ‘0’
CMD 1 CMD 1
‘3’
CMD 0 CMD 0
‘3’
‘2’ Number of data ‘0’
(Count by byte)
Starting data ‘1’ ‘4’
address ‘0’ ‘1’
Content of starting
‘2’ ‘7’
address
‘0’ ‘7’
2102H
Number of data ‘0’ ‘0’
(count by word)
‘0’ ‘0’
‘2’ Content of address ‘0’
2103H
LRC CHK 1 ‘D’ ‘0’
LRC CHK 0 ‘7’ ‘0’
END 1 CR LRC CHK 1 ‘7’
END 0 LF LRC CHK 0 ‘1’
END 1 CR
END 0 LF
5-66 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
RTU mode:
Command message:
Response message:
ADR 01H ADR
01H
CMD 03H CMD 03H
Starting data 21H Number of data
04H
address (count by byte)
02H
Number of data 00H Content of address 17H
(count by word) 2102H
02H 70H
CRC CHK Low 6FH Content of address 00H
2103H
CRC CHK High F7H 00H
CRC CHK Low FEH
CRC CHK High 5CH
(2) 06H: single write, write single data to register.
Example: writing data 6000(1770H) to register 0100H. AMD address is 01H.
ASCII mode:
Command message: Response message:
STX ‘:’ STX ‘:’
ADR 1 ‘0’ ADR 1 ‘0’
ADR 0 ‘1’ ADR 0 ‘1’
CMD 1 ‘0’ CMD 1 ‘0’
CMD 0 CMD 0
‘6’ ‘6’
‘0’ ‘0’
‘1’ ‘1’
Data address Data address
‘0’ ‘0’
‘0’ ‘0’
‘1’ ‘1’
‘7’ ‘7’
Data content Data content
‘7’ ‘7’
‘0’ ‘0’
LRC CHK 1 ‘7’ LRC CHK 1 ‘7’
LRC CHK 0 ‘1’ LRC CHK 0 ‘1’
END 1 CR END 1 CR
END 0 LF END 0 LF
RTU mode:
Response message:
Command message:
ADR 01H ADR 01H
CMD 06H CMD 06H
01H 01H
Data address Data address
00H 00H
17H 17H
Data content Data content
70H 70H
CRC CHK Low 86H CRC CHK Low 86H
CRC CHK High 22H CRC CHK High 22H
(3) Command code: 10H, write n word, n<=12
For example, writing 6000(1770H) to Pr 5-00 (address 0500H) and1000(03E8H) to Pr 5-01
(address 0501H) with slave address 01H.
Revision August 2006, SE08, SW V2.61 5-67
Chapter 5 Parameters|VFD-S Series
ASCII Mode:
Command message: Response message:
STX ‘:’ STX ‘:’
ADR 1 ‘0’ ADR 1 ‘0’
ADR 0 ‘1’ ADR 0 ‘1’
CMD1 ‘1’ CMD1 ‘1’
CMD0 ‘0’ CMD0 ‘0’
Starting Data address‘0’ Starting Data ‘0’
address
‘5’ ‘5’
‘0’ ‘0’
‘0’ ‘0’
Number of data ‘0’ Number of data ‘0’
(count by word) (count by word)
‘0’ ‘0’
‘0’ ‘0’
‘2’ ‘2’
Number of data ‘0’ LRC CHK 1 ‘E’
(count by byte)
‘4’ LRC CHK 0 ‘8’
Data content of ‘1’ END1 CR
address 0500H
‘7’ END0 LF
‘7’
‘0’
Data content of ‘0’
address 0501H ‘3’
‘E’
‘8’
LRC CHK 1 ‘7
LRC CHK 0 ‘2
END1 CR
END0 LF
RTU mode:
Command message: Response message:
ADR 01H ADR 01H
CMD 10H CMD 10H
Starting Data address 05H Starting Data address05H
00H 00H
Number of data 00H Number of data 00H
(count by word) 02H (count by word) 02H
Number of data 04H CRC CHK Low 41H
(count by Byte)
CRC CHK High 04H
Data content of address 0500H17H
70H
Data content of address 0501H03H
E8H
CRC CHK Low C8H
CRC CHK High 2EH
3.4 Check sum
5-68 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
ASCII mode:
LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the values of
the bytes from ADR1 to last data character then calculating the hexadecimal
representation of the 2’s-complement negation of the sum.
For example, reading 1 word from address 0401H of the AC drive with address 01H
STX ‘:’
ADR 1 ‘0’
ADR 0
‘1’
CMD1 ‘0’
CMD0 ‘3’
Starting data address ‘0’
‘4’
‘0’
‘1’
Number of data ‘0’
‘0’
‘0’
‘1’
LRC CHK 1 ‘F’
LRC CHK 0
‘6’
END1 CR
END0
LF
01H+03H+04H+01H+00H+01H=0AH, the 2’s-complement negation of 0AH is F6H.
RTU mode:
ADR 01H
CMD 03H
Starting address 21H
02H
Number of data 00H
(count by word)
02H
CRC CHK Low 6FH
CRC CHK High F7H
CRC (Cyclical Redundancy Check) is calculated by the following steps:
Step 1: Load a 16-bit register (called CRC register) with FFFFH.
Step 2: Exclusive OR the first 8-bit byte of the command message with the low order
byte of the 16-bit CRC register, putting the result in the CRC register.
Step 3: Examine the LSB of CRC register.
Step 4: If the LSB of CRC register is 0, shift the CRC register one bit to the right with MSB zero
filling, then repeat step 3. If the LSB of CRC register is 1, shift the CRC register one
bit to the right with MSB zero filling, Exclusive OR the CRC register with the
polynomial value A001H, then repeat step 3.
Revision August 2006, SE08, SW V2.61 5-69
Chapter 5 Parameters|VFD-S Series
Step 5: Repeat step 3 and 4 until eight shifts have been performed. When this is done, a
complete 8-bit byte will have been processed.
Step 6: Repeat step 2 to 5 for the next 8-bit byte of the command message. Continue doing this
until all bytes have been processed. The final contents of the CRC register are the
CRC value. When transmitting the CRC value in the message, the upper and lower
bytes of the CRC value must be swapped, i.e. the lower order byte will be transmitted
first.
The following is an example of CRC generation using C language. The function takes two
arguments:
Unsigned char* data � a pointer to the message buffer
Unsigned char length � the quantity of bytes in the message buffer
The function returns the CRC value as a type of unsigned integer.
Unsigned int crc_chk(unsigned char* data, unsigned char length){
int j;
unsigned int reg_crc=0xFFFF;
while(length--){
reg_crc ^= *data++;
for(j=0;j<8;j++){
if(reg_crc & 0x01){ /* LSB(b0)=1 */
reg_crc=(reg_crc>>1) ^ 0xA001;
}else{
reg_crc=reg_crc >>1;
}
}
}
return reg_crc;
}
3.5 Address list
The contents of available addresses are shown as below:
Content Address Functions
AC drive ggnnH gg means parameter group, nn means parameter number, for
Parameters example, the address of Pr 4-01 is 0401H. Referencing to
chapter 5 for the function of each parameter. When reading
parameter by command code 03H, only one parameter can be
read at one time.
5-70 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Content Address Functions
Command 2000H Bit 0-1 00: No function
01: Stop
10: Run
11: Jog + Run
Bit 2-3 Not used
00: No function
01: FWD
Bit 4-5
10: REV
11: Change direction
Bit 6-15 Not used
2001H Freq. command
2002H Bit 0 1: EF (external fault) on
Bit 1 1: Reset
Bit 2-15 Not used
Status 2100H Error code:
monitor 0: No errors occurred
Read only 1: Over-current (oc)
2: Over-voltage (ov)
3: Overheat (oH)
5: Overload1 (oL1)
6: External fault (EF)
7: Not used
8: Not used
9: Current exceeds 2 times rated current during acceleration
(ocA)
10: Current exceeds 2 times rated current during deceleration
(ocd)
11: Current exceeds 2 times rated current during steady state
operation (ocn)
12: Ground Fault (GF)
13: Reserved
14: Low voltage (Lv)
15: CPU failure 1 (cF1)
16: CPU failure 2 (cF2)
17: Base block
18: Overload (oL2)
19: Auto acceleration/deceleration failure (cFA)
20: Software protection enable (codE)
21: Reserved
22: CPU failure (cF3.1)
23: CPU failure (cF3.2)
24: CPU failure (cF3.3)
25: CPU failure (cF3.4)
26: CPU failure (cF3.5)
27: CPU failure (cF3.6)
28: CPU failure (cF3.7)
29: Hardware protection failure (HPF.1)
30: Hardware protection failure (HPF.2)
31: Hardware protection failure (HPF.3)
32: CE 10
33: Reserved
34: Software error (SErr)
Revision August 2006, SE08, SW V2.61 5-71
Chapter 5 Parameters|VFD-S Series
Content Address Functions
35: Reserved
36: PID error (Pld)
37: Reserved
38: Phase loss (PHL)
2101H Status of AC Drive
00: RUN LED light off, STOP LED light up
01: RUN LED blink, STOP LED light up
Bit 0-1
10: RUN LED light up, STOP LED blink
11: RUN LED light up, STOP LED light off
Bit 2 01: Jog active
00: REV LED light off, FWD LED light up
01: REV LED blink, FWD LED light up
Bit 3-4
10: REV LED light up, FWD LED blink
11: REV LED light up, FRD LED light off
Bit 5-7 Not used
Bit 8 1: Main freq. Controlled by communication
Bit 9 1: Main freq. Controlled by external terminal
1: Operation command controlled by communication
Bit 10
Bit 11 1: Parameters have been locked
Bit 12-15 Not Used
2102H Frequency command F (XXX.XX)
2103H Output Frequency H (XXX.XX)
2104H Output Current A (XXX.XX)
2105H DC-BUS Voltage U (XXX.XX)
2106H Output Voltage E (XXX.XX)
2107H Step number of Multi-Step Speed Operation
2108H Step number of PLC operation
2109H Time of PLC Operation
210AH Counter Value
3.6 Exception response:
The AC motor drive is expected to return a normal response after receiving command
messages from the master device. The following depicts the conditions when no
normal response is replied to the master device.
The AC motor drive does not receive the messages due to a communication error; thus, the AC
motor drive has no response. The master device will eventually process a timeout
condition.
The AC motor drive receives the messages without a communication error, but cannot handle
them. An exception response will be returned to the master device and an error
message “CExx” will be displayed on the keypad of AC motor drive. The xx of “CExx”
is a decimal code equal to the exception code that is described below.
In the exception response, the most significant bit of the original command code is set to 1, and
an exception code which explains the condition that caused the exception is
returned.
5-72 Revision August 2006, SE08, SW V2.61
Chapter 5 Parameters|VFD-S Series
Example of an exception response of command code 06H and exception code 02H:
ASCII mode: RTU mode:
STX ‘:’ ADR 01H
ADR 1 ‘0’ CMD 86H
ADR 0 ‘1’ Exception code 02H
CMD1 ‘8’ CRC CHK Low C3H
CMD0 ‘6’ CRC CHK High A1H
‘0’
Exception code
‘2’
LRC CHK 1 ‘7’
LRC CHK 0 ‘7’
END1 CR
END0 LF
The explanation of exception codes:
Exception Meaning
code
Illegal command code: The command code received in the command
1
message is not available for the AC drive.
Illegal data address: The data address received in the command
2
message is not available for the AC drive.
Illegal data value: The data value received in the command message
3
is not available for the AC drive.
Slave device failure: The AC drive is unable to perform the requested
4
action.
The AC drive receives the messages, but detects a communication error, thus, no response is
returned, but there will be error message “CExx” displayed on the keypad of AC drive. The master
device will eventually process a timeout condition. The xx of “CExx” is a decimal code, the meaning
of the error message is below:
Error
Meaning
message
5
eserved
AC drive busy:
The time interval between commands is too short. Please keep an
6
interval of 10ms at least after the return of a command. If no command
returned, please keep a 10ms interval at least for the same reason.
7 Reserved
8 Reserved
9 Check Sum Error: Check if the Check Sum is correct.
Watchdog Timer: The timer will reset to 0 after each valid Modbus
10
communication message is received.
11 Frame Error: Check if the Baud rate complies with the data format.
12 The command message is too short.
13 Command message length is out of range.
The command messages include the data that does not belong to ‘0’ to
14 ‘9’, ‘A’ to ‘F except starting and end character (only for Modbus ASCII
mode).
Revision August 2006, SE08, SW V2.61 5-73
Chapter 5 Parameters|VFD-S Series
3.7 Communication program of PC:
The following is a simple example of how to write a communication program for Modbus ASCII
mode on a PC in C language.
#include
Frequently asked questions
What makes Elite.Parts unique?
What kind of warranty will the VFD007S11B have?
Which carriers does Elite.Parts work with?
Will Elite.Parts sell to me even though I live outside the USA?
I have a preferred payment method. Will Elite.Parts accept it?
Why buy from GID?
Quality
We are industry veterans who take pride in our work
Protection
Avoid the dangers of risky trading in the gray market
Access
Our network of suppliers is ready and at your disposal
Savings
Maintain legacy systems to prevent costly downtime
Speed
Time is of the essence, and we are respectful of yours
Manufacturers








What they say about us
FANTASTIC RESOURCE
One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!
Bucher Emhart Glass
EXCELLENT SERVICE
With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.
Fuji
HARD TO FIND A BETTER PROVIDER
Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.
Applied Materials
CONSISTENTLY DELIVERS QUALITY SOLUTIONS
Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.
Nidec Vamco
TERRIFIC RESOURCE
This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.
Trican Well Service
GO TO SOURCE
When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.
ConAgra Foods